HomeMy WebLinkAboutBUILDING REVIEW RESPONSE - 16-00313 - Complete Family Care A&R AdditionComplete Family Care A&R Addition
Building ReviewReview Date: 05/10/2016
Permit Number: 16-00313
Reviewed By: Quinton Owens Current Building Review Status: REVISIONS
D ESCRIPTION COMMENTS STATUS
Use classification is shown on plans as per IBC
Section 302
not shown REVISIONS
Building height and area meets the requirements
of IBC Section 500 & Table 503
only additional sf shown. Total bldg sf?REVISIONS
What is the type of construction & sq footage?
Please Specify in comments
Not shown (V-B assumed)YES
Exterior walls meet the requirements of IBC
Section 705
REQUIRED: 1 hour rated west wall (from both
sides)
COMPLETED
Exterior wall openings meet the requirements of
IBC Section 705.8
openings < 10% (UP,NS) Wall with attic gable
included
COMPLETED
fireblocking and draftstopping meet the
requirements of IBC Section 717.
Not shown, approval based on inspection COMPLETED
Occupant load is identified on plans as per IBC
Section 1004
not shown REVISIONS
Handrails and Guards meet the requirements of
IBC Sections 1011 and 1012
REQUIRED: Handrails on both sides of stairs
per IBC (extensions also required).
Guards required per IBC where adjacent grade is
greater than 30" below walking surface.
COMPLETED
Exterior Exit Ramps and Stairs meet the
requirements of IBC Section 1026
REQUIRED: Stair construction to comply with
IBC, Section 1009 (no details)
COMPLETED
Toilets, Bathing Fac., Sinks, Kit. and Drink. Fount.
meet IBC Sec. 1109
REQUIRED: Vertical grab bar for water closet
per A117.1
COMPLETED
Ventilation is provided as per IBC Section 1203 How is crawl space being ventilated? (insulation
shown in floor and on foundation walls).
REVISIONS
An Energy Review is provided Need energy compliance report or plans are to
meet prescriptive requirements of IECC.
REVISIONS
Concrete Documentation provided as per IBC
Section 1901.4
Incomplete REVISIONS