Loading...
HomeMy WebLinkAboutBUILDING REVIEW RESPONSE - 16-00313 - Complete Family Care A&R AdditionComplete Family Care A&R Addition Building ReviewReview Date: 05/10/2016 Permit Number: 16-00313 Reviewed By: Quinton Owens Current Building Review Status: REVISIONS D ESCRIPTION COMMENTS STATUS Use classification is shown on plans as per IBC Section 302 not shown REVISIONS Building height and area meets the requirements of IBC Section 500 & Table 503 only additional sf shown. Total bldg sf?REVISIONS What is the type of construction & sq footage? Please Specify in comments Not shown (V-B assumed)YES Exterior walls meet the requirements of IBC Section 705 REQUIRED: 1 hour rated west wall (from both sides) COMPLETED Exterior wall openings meet the requirements of IBC Section 705.8 openings < 10% (UP,NS) Wall with attic gable included COMPLETED fireblocking and draftstopping meet the requirements of IBC Section 717. Not shown, approval based on inspection COMPLETED Occupant load is identified on plans as per IBC Section 1004 not shown REVISIONS Handrails and Guards meet the requirements of IBC Sections 1011 and 1012 REQUIRED: Handrails on both sides of stairs per IBC (extensions also required). Guards required per IBC where adjacent grade is greater than 30" below walking surface. COMPLETED Exterior Exit Ramps and Stairs meet the requirements of IBC Section 1026 REQUIRED: Stair construction to comply with IBC, Section 1009 (no details) COMPLETED Toilets, Bathing Fac., Sinks, Kit. and Drink. Fount. meet IBC Sec. 1109 REQUIRED: Vertical grab bar for water closet per A117.1 COMPLETED Ventilation is provided as per IBC Section 1203 How is crawl space being ventilated? (insulation shown in floor and on foundation walls). REVISIONS An Energy Review is provided Need energy compliance report or plans are to meet prescriptive requirements of IECC. REVISIONS Concrete Documentation provided as per IBC Section 1901.4 Incomplete REVISIONS