Loading...
HomeMy WebLinkAboutTAB REPORT - 16-00521 - 30 N 2nd E - Freddy's Freddy ’s 42 North 2nd East Rexburg, Idaho 83440 Testing, Adjusting, Balancing Report Certification No. 3624 FINELY TUNED BUILDIINGS Certification FINELY TUNED BUILDINGS Project Name: Freddy’s Project Address: 42 North 2nd East Rexburg, Idaho 83440 Architect: Larson Architects, PA Boise, Idaho Mechanical Engineer: Musgrove Engineering, P.A. Meridian, Idaho Mechanical Contractor: KMD Mechanical Boise, Idaho NEBB Certified Firm: Blue Sky Consulting Services 3440 W. Scenic Drive Boise, Idaho 83703 NEBB Certified Professional: Sean T. Rasmussen Certification Number: 3624 Expires: 3/31/2017 TAB Technician: Brady Oliver TAB Technician: Jarrod Morrison THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS. THE MEASUREMENTS SHOWN, AND THE INFORMATION GIVEN, IN THIS REPORT ARE CERTIFIED TO BE ACCURATE AND COMPLETE, AT THE TIME AND DATE INFORMATION WAS GATHERED. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST-ADJUST-BALANCE REPORT PROJECT SUMMARY. Table of Contents FINELY TUNED BUILDINGS Section 1: Instrument Calibration  Section 2: Abbreviations  Section 3: Executive Summary  Section 4: Project Notes / Open Issues  Section 5: Air Handler Unit Test Reports  Section 6:  Make‐up Air Unit Test Report  Section 7: Kitchen Hood Exhaust Fan Test Reports  Section 8: Cabinet Exhaust Fan Test Reports              Instrument Calibration FINELY TUNED BUILDINGS FUNCTION INSTRUMENT CALIBRATION DATE / FREQUENCY MANUFACTURER MODEL # SERIAL # ACCURACY RANGE Air Pressure Measurement Pressure / Velocity Module 07/2016 12 months Evergreen Telemetry S-PVF-1 1600261 +/– 2% of Reading 0.01–10.00 in. w.g. Air Velocity Measurement Pressure / Velocity Module 07/2016 12 months Evergreen Telemetry S-PVF-1 1600261 +/- 3% of Reading 50-8000 FPM Direct Air Volume Measurement Airflow Capture Hood 07/2016 12 months Evergreen Telemetry CH-15D 1400135 +/– 3% of Reading 100-2000 CFM Electrical Measurement Clamp Meter 03/2016 12 months UEI DL389 TRMS 160102937 +/- 3% of Full Scale Reading 0-400 Amps 0-750 VAC 0-1000 VDC Humidity Measurement Hygrometer 09/2015 12 months Evergreen Telemetry S-H-3-5 1500325 2% RH 10-90% RH Hydronic Differential Pressure Measurement Hydronic Manometer 06/2016 12 months Evergreen Telemetry S-DP-125 1600101 +/- 2% of Full Scale Reading 0-100 in w.g. Rotation Measurement Tachometer 03/2016 12 months Sanpo SM6236E S888045 +/- 2% of Full Scale Reading 0-5000 RPM Temperature Measurement Thermometer 03/2016 12 months Amprobe TMD-56 15080249 +/- 1% of Reading -40°F-240°F Abbreviations FINELY TUNED BUILDINGS Abbreviation Definition Abbreviation Definition AC Air Conditioning FCU Fan Coil Unit AHU Air Handler Unit ft. w.c. Feet in water column (pressure) BTU(H) British Thermal Unit (per hour) GPM Gallons Per Minute (flow) C.S. Circuit Setter HP Horse Power (power) CD Ceiling Diffuser HRU Heat Recovery Unit CFM Cubic Feet / Minute (flow) HW Heating / Hot Water CHW Chilled Water HZ Hertz (frequency) D Diffuser in. w.c. Inches in water column (pressure) D.B. Dry Bulb (temperature) LD Linear Diffuser DCV Demand Control Ventilation LG Linear Grille D.P. Differential Pressure MAU Make-up Air Unit DP Discharge Pressure OBD Opposable Blade Damper DVR Design Ventilation Rate OSA Outside Air ECM Electronically Commutated Motor ppm Parts Per Million (dilution) EF Exhaust Fan PSI Pounds per Square Inch (pressure) EG Exhaust Grille RG Return Grille E.S.P. External Static Pressure RF Return / Relief Fan ERU Energy Recovery Unit RPM Revolutions Per Minute (rotation) F Furnace (unit) RTU Roof Top Unit F.L.A. Full Load Amperage (current) S.F. Service Factor S.P. Static Pressure VAV Variable Air Volume (unit) SP Suction Pressure VDC Voltage Output Sheave Pulley, usually in reference to fan drives VFD Variable Frequency Drive SWR Side-wall Register V Voltage T.S.P. Total Static Pressure VVT Variable Volume Terminal (unit) T1,2,3 Electrical Terminal Connections W.B. Wet Bulb (temperature) TDH Total Dynamic Head ZD Zone Damper Executive Summary FINELY TUNED BUILDINGS This project consists of testing, adjusting, and balancing of three packaged roof-top AC units serving the dining/seating area, kitchen, and restrooms. Two kitchen hood with two exhaust fan and make-up air unit and two cabinet exhaust fans. The following systems and equipment were included in the Testing, Adjusting and Balancing scope for this project.  (3) Air Handler / AC units  (1) Make-up Air Unit  (2) Roof Mounted Exhaust Fans  (2) Cabinet Exhaust Fans  Associated registers, diffusers, and grilles Testing Adjusting and Balancing Procedures / System Posturing Constant Volume Supply / Exhaust Systems (AHU / EF): The systems and fans on this project are all constant volume systems. Fan totals on these systems were first measured and set at or above design flow if possible, connected diffusers and grilles were then proportioned via the proportional balance method as outlined in NEBBs procedural standards, outside air minimum levels were set, and the fan speeds were adjusted again to achieve the design air flow requirements. Final unit operating data was then collected. Project Notes / Open Issues FINELY TUNED BUILDINGS Items of note and open TAB issues for this project are outlined below. No Open Issues. Make-Up Unit Test Report PROJECT:DATE: LOCATION:CONTACT: Area: 2,680 2,775 Not Listed 749 Volts Amps Amps ID#Type Size Des. CFM Pre. CFM Act. CFM % Design Notes 1 Ducted 12"258 301 274 106% 2 Ducted 12"258 287 266 103% 3 Ducted 12"258 255 255 99% 4 Ducted 12"258 320 274 106% 5 Ducted 12"258 289 255 99% 6 Ducted 12"258 275 262 102% 7 Ducted 12"258 309 269 104% 8 Ducted 12"258 244 276 107% 9 Ducted 10"154 249 155 101% 10 Ducted 10"154 218 168 109% 11 Ducted 10"154 263 157 102% 12 Ducted 10"154 97 164 106% Total 2,680 3,107 2,775 104% Notes: Hood 1B Hood 2 Hood 2 Hood 2 Hood 2 Design Motor Amps:4.64 Hood 1A Hood 1A Hood 1B Hood 1B Hood 1B Outlet Summary Room # Hood 1A Hood 1A CFM CFM AK66 x 1" 1 / AX50 86.5% 76.0% Motor Sheave Dia. / Bore (in.): Fan Sheave Dia. / Bore (in.): No. Belts / Size:RPM 1VL40 x 5/8" Freddy's Rexburg, Idaho Design Airflow: Actual Airflow: Unit: 208 / 3 / 60 4.64 / 1.15Test Data Volts / Phase / Hertz: Full Load Amps / S.F.: February 22, 2017 Jarrod Morrison Kitchen HoodsMAU-1 Captive Aire / A2-D.250-G15 2761062 Direct Fire Make-Up Air Unit Unit Data Motor Data 1.5 / 1760 / 56HHP / RPM / Frame: Manufacturer / Model: Serial #: Type / Size: Supply Fan Motor Make:Weg Motor Amps T1/T2/T3:4.11 / 3.81 / 3.75 RPM Efficiency (%): Power Factor (%): Supply Fan Design RPM: Actual RPM: Motor Volts T1/T2/T3:212 / 212 / 214 FINELY TUNED BUILDINGS Roof Top Unit Test Report PROJECT:DATE: LOCATION:CONTACT: Area: 3,040 3,195 500 502 2,540 2,693 Not Listed 1.00 1181 0.25 Volts 0.08 Amps 0.17 Amps ID#Type Size Des. CFM Pre. CFM Act. CFM % Design Notes 1 D-5 12"440 496 459 104% 2 D-5 12"400 486 423 106% 3 D-3 8"175 223 188 107% 4 D-5 12"425 327 469 110% 5 D-3 8"100 139 103 103% 6 D-3 8"100 124 100 100% 7 D-3 8"125 228 132 106% 8 D-5 12"425 311 451 106% 9 D-5 12"425 472 426 100% 10 D-5 12"425 469 444 104% Total 3,040 3,275 3,195 105% Notes: 4 / 16" x 24" x 2" Volts / Phase / Hertz: Full Load Amps / S.F.: Efficiency (%): Power Factor (%): Motor Sheave Dia. / Bore (in.): 208 / 3 / 60 9.5 / 1.15 Not Available Not Available 1VM50 x 7/8" Design External: Actual External: Fan Outlet: Fan Inlet: Fan Sheave Dia. / Bore (in.): No. Belts / Size: in w.c. Test Pressures in w.c. AK61 x 1" 1 / A49 Filter # / Size / Rating: Room # 100 100 CFM CFM 212 / 214 / 211 9.50 Design Return Air: Actual Return Air: Supply Fan 106 101 February 22, 2017 Jarrod Morrison Unit: Freddy's Rexburg, Idaho Type / Size: DiningRTU - 1 York / ZF090N18D2B1A N1N6257842 Packaged RTU / 4.5 Tons Unit Data Motor Data 3.0 / 1725 / 56HZHP / RPM / Frame: Motor Make:Marathon Supply FanManufacturer / Model: Serial #: Test Data Actual Airflow: Design RPM: Actual RPM: Actual Volts T1/T2/T3: Design Outdoor Air: Actual Outdoor Air: CFM CFM CFM CFM Design Airflow: RPM RPM 112 100 in w.c. in w.c.Design Amps: 108 107 101 101 Actual Amps T1/T2/T3:7.63 / 7.85 / 6.72 Outlet Summary FINELY TUNED BUILDINGS Roof Top Unit Test Report PROJECT:DATE: LOCATION:CONTACT: Area: 3,000 3,048 500 524 2,500 2,524 Not Listed 1.00 1185 0.28 Volts 0.09 Amps 0.19 Amps ID#Type Size Des. CFM Pre. CFM Act. CFM % Design Notes 1 D-5 12"500 536 523 105% 2 D-5 12"500 479 512 102% 3 D-5 12"500 481 498 100% 4 D-5 12"500 566 501 100% 5 D-5 12"500 529 522 104% 6 D-5 12"500 555 492 98% Total 3,000 3,146 3,048 102% Notes: Filter # / Size / Rating:4 / 16" x 24" x 2" Freddy's February 22, 2017 Rexburg, Idaho Jarrod Morrison Unit:RTU - 2 Dining Serial #:N1N6257843 Motor Make:Marathon Type / Size:Packaged RTU / 4.5 Tons Unit Data Motor Data Manufacturer / Model:York / ZF090N18D2B1A Supply Fan HP / RPM / Frame:3.0 / 1725 / 56HZ 9.5 / 1.15 Actual Airflow:CFM Power Factor (%):Not Available Design Airflow:CFM Efficiency (%):Not Available Volts / Phase / Hertz:208 / 3 / 60 Test Data Full Load Amps / S.F.: Design Outdoor Air:CFM Motor Sheave Dia. / Bore (in.):1VM50 x 7/8" Actual Outdoor Air:CFM Fan Sheave Dia. / Bore (in.):AK61 x 1" No. Belts / Size:1 / A49 Design RPM:RPM Design External:in w.c. Design Return Air:CFM Actual Return Air:CFM Supply Fan Test Pressures Actual RPM:RPM Actual External:in w.c. Actual Volts T1/T2/T3:211 / 213 / 211 Fan Inlet:in w.c. 101 Design Amps:9.50 Fan Outlet:in w.c. Actual Amps T1/T2/T3:6.50 / 7.39 / 6.86 Outlet Summary Room # 100 100 100 101 101 FINELY TUNED BUILDINGS Roof Top Unit Test Report PROJECT:DATE: LOCATION:CONTACT: Area: 4,700 4,872 304 328 4,396 4,544 Not Listed 1.00 1263 0.27 Volts 0.12 Amps 0.15 Amps ID#Type Size Des. CFM Pre. CFM Act. CFM % Design Notes 1 D-4 8"150 182 152 101% 2 D-2 12"500 473 510 102% 3 D-2 12"400 449 409 102% 4 D-2 12"300 369 315 105% 5 D-2 12"450 486 457 102% 6 Ducted 8"124 137 132 106% 7 Ducted 8"124 112 121 98% 8 Ducted 8"124 108 131 106% 9 D-2 12"450 496 467 104% 10 Ducted 8"102 132 108 106% 11 Ducted 8"102 122 104 102% 12 Ducted 8"102 149 109 107% 13 D-2 12"400 439 432 108% 14 Ducted 8"124 124 129 104% 15 Ducted 8"124 133 132 106% 16 Ducted 8"124 146 124 100% 17 D-2 12"500 531 523 105% 18 D-2 12"500 399 517 103% Total 4,700 4,987 4,872 104% Notes: Filter # / Size / Rating:4 / 20" x 24" x 2" 111 KH1 KH1 103 KH3 Freddy's February 22, 2017 Rexburg, Idaho Jarrod Morrison Unit:RTU - 3 Kitchen Serial #:N1N6257849 Motor Make:Baldor Type / Size:Packaged RTU / 12 Tons Unit Data Motor Data Manufacturer / Model:York / ZF150N18D2B1A Supply Fan HP / RPM / Frame:5.0 / 1750 / 184T 14.0 / 1.15 Actual Airflow:CFM Power Factor (%):80.0% Design Airflow:CFM Efficiency (%):89.5% Volts / Phase / Hertz:208 / 3 / 60 Test Data Full Load Amps / S.F.: Design Outdoor Air:CFM Motor Sheave Dia. / Bore (in.):1VM56 x 1 1/8" Actual Outdoor Air:CFM Fan Sheave Dia. / Bore (in.):BK77 x 1" Actual Return Air:CFM Supply Fan Test Pressures No. Belts / Size:1 / BX56 Actual RPM:RPM Actual External:in w.c. Design RPM:RPM Design External:in w.c. Design Return Air:CFM Actual Volts T1/T2/T3:213 / 212 / 212 Fan Inlet:in w.c. 102 Design Amps:14.00 Fan Outlet:in w.c. Actual Amps T1/T2/T3:10.80 / 12.35 / 10.60 Outlet Summary Room # Office 102 102 KH1 KH3 104 103 KH3 103 KH2 KH2 KH2 FINELY TUNED BUILDINGS Kitchen Hood Test Report PROJECT:DATE: LOCATION:CONTACT: Test Data EF Design Airflow:2,584 EF Actual Airflow:2,749 Exhaust Fan Design RPM:Not Listed 1380 Volts Amps Amps Test Type Area (Ft²) Velocity FPM Filter Factor Design CFM Actual CFM % Design Notes Velgrid 15.17 151 1.2 2,584 2,749 106% Total Notes: 1.5 / 1760 / 56HHP / RPM / Frame: 4.64 / 1.15 86.5% 76.0% Belt 1VL40 x 5/8" Actual Amps T1/T2/T3: Size (in.) 78" x 14" x 2 Exhaust Air Test Summary Job #: Captive Aire / NCA16HPFA 2761062 February 22, 2017 Jarrod Morrison Freddy's Rexburg, Idaho Manufacturer / Model: Unit Data Motor Data Unit ID:EF-1 Type I Kitchen Grease Hood Exhaust Fan Motor Make:Weg 3.86 / 4.11 / 3.75 Type:Roof Upblast Volts / Phase / Hertz:208 / 3 / 60 CFM CFM Full Load Amps / S.F.: Efficiency (%): Power Factor (%): Motor Type: Motor Sheave Dia. / Bore (in.): Fan Sheave Dia. / Bore (in.): No. Belts / Size: Actual Volts T1/T2/T3: Design Amps: 211 / 211 / 213 4.64 RPM Actual RPM:RPM AK46 x 1" 1 / AX22 FINELY TUNED BUILDINGS Kitchen Hood Test Report PROJECT:DATE: LOCATION:CONTACT: Test Data EF Design Airflow:710 EF Actual Airflow:762 Exhaust Fan Design RPM:Not Listed 953 Volts Amps Amps Test Type Area (Ft²) Velocity FPM Filter Factor Design CFM Actual CFM % Design Notes Velgrid 4.57 139 1.2 710 762 107% Total Notes: Unit Data Motor Data Freddy's February 22, 2017 Rexburg, Idaho Jarrod Morrison Type I Kitchen Grease Hood Unit ID:EF-2 Exhaust Fan Manufacturer / Model:Captive Aire / DU50HFA Motor Make:HSSA Job #:2761062 HP / RPM / Frame:1/2 / 1625 / 48Y Type:Roof Upblast Volts / Phase / Hertz:115 / 1 / 60 Full Load Amps / S.F.:5.6 / 1.0 Motor Type:Direct Drive CFM CFM RPM Actual RPM:RPM Actual Volts T1/T2/T3:119 Design Amps:5.60 Actual Amps T1/T2/T3:4.33 Exhaust Air Test Summary Size (in.) 47" x 14" FINELY TUNED BUILDINGS Exhaust Fan Test Report PROJECT:DATE: LOCATION:CONTACT: Area: Not Listed 710 ID#Des. CFM Act. CFM % Design Amps Notes EF-1 150 138 92%1.3 EF-2 150 141 94%1.2 Total Notes: Test Data Exhaust Fan Inlet Summary Actual RPM:RPM Volts / Phase / Hertz:120 / 1 / 60 Full Load Amps / S.F.:1.3 Design RPM:RPM Motor Type:Direct Drive Type:Ceiling Cabinet Motor Make:Not Available HP / RPM / Frame:100 Watts / 710 Unit Data Motor Data Manufacturer / Model:Broan / L150 Exhaust Fan Freddy's February 22, 2017 Rexburg, Idaho Jarrod Morrison Unit:EF-1 & 2 Restrooms Type Cabinet Cabinet Room # 108 107 FINELY TUNED BUILDINGS