Building ReviewReview Date: 09/22/2016
Permit Number: 16-00521
Reviewed By: Quinton Owens Current Building Review Status: REVISIONS
D ESCRIPTIO N CO MMEN TS STATUS
What is the type of construction & sq
footage? Please Specify in comments
V-B construction.YES
Special Inspections are required as per IBC
Chapter 17
Required as per on structural notes COMPLETED
Special Inspection Contractor is identified Submit name of special inspection
contractor as soon as one is selected.
COMPLETED
Geotech Insp. is provided or Bldg. Off. has
waived reqs. as per IBC Sec. 1803
Is there a Geotechnical report as
mentioned on the structural notes. Backfill
was brought in after removal of the
previous building. Has the backfill been
approved by the engineer or will it be
replaced?
REVISIONS
Anchorage to concrete is identified on plans
as per IBC Section 1911 and 1912
3x3 square washers required by code at
bottom plate anchor bolts (not noted on
plans)
COMPLETED
Glass and Glazing meets the requirements
of IBC Chapter 24
Tempered glass will be required at
hazardous locations identified in IBC (did
not see it identified on window schedule),
COMPLETED