HomeMy WebLinkAboutLOAD SHORT FORM - 16-00644 - 1121 Adams Ct - SFRcC7uN7RY Load Short Form Basement Katchner 601 West 1700 south, Logan, Utah 84321 Phone: 435-755-7080 Project Information For: Job: FS265 Date: By: Vince HEATING EQUIPMENT Area Design Information Make Goodman Mfg. Htg Clg Infiltration Outside db (*F) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Average Design TD (°F) 74 14 Fireplaces 0 Daily range - H 0 Inside humidity (%) 50 50 AHRI ref 7365235 Moisture difference (gr/Ib) 57 -31 168 Efficiency 11.5 EER, 14 SEER Heating input 40000 Btuh HEATING EQUIPMENT Area COOLING EQUIPMENT Clg load Make Goodman Mfg. Clg AVF Make Goodman Mfg. (Btuh) Trade GOODMAN (cfm) (cfm) Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960402BN 779 76 Cond GSX130181E Room2 AHRI ref 7365095 500 0 Coil CAPF1824D6D 0 Room3 544 3128 AHRI ref 7365235 245 Efficiency 96.1 AFLIE 168 Efficiency 11.5 EER, 14 SEER Heating input 40000 Btuh Sensible cooling 12180 Btuh Heating output 32000 Btuh Latent cooling 5220 Btuh Temperature rise 77 OF Total cooling 17400 Btuh Actual air flow 450 cfm Actual air flow 450 cfm Air flow factor 0.078 cfm/Btuh Air flow factor 0.320 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat I ecn I Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft') (Btuh) (Btuh) (cfm) (cfm) Room1 110 969 779 76 249 Room2 66 500 0 39 0 Room3 544 3128 629 245 201 Room4 168 1148 0 90 0 Basement d 888 5746 1408 450 450 Other equip loads 1368 259 Equip. @ 0.94 RSM 1566 Latent cooling 0 T/1TAI C I 000 I 744 I ncr_r_ I ecn I v, - VVV /1IY IJVU `ju 'Du Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016 -Sep -17 10:30:58 Arm Wrlght5QfL` Right -Suite® Universal 2017 17.0.03 RSU20477 Pagel 194.�m...ER\Documents\wrightsoftwaie\Kanchner\F52B5.rup Calc=MJ8 Front Door faces: NW Load Short Form Job: FS2B5 Date: Main And Up By: Vince ` Katchner Nnae ntF '.r nnnmafnp. 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 For: HEATING EQUIPMENT Make Goodman Mfg. Design Information Model Htg CIg Infiltration Outside db ('F) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Average Design TO (°F) 74 14 Fireplaces 0 Daily range - H 94 Inside humidity (%) 50 50 1237 Moisture difference (gr/Ib) 57 -31 60 534 112 16 6 HEATING EQUIPMENT Make Goodman Mfg. Trade GOODMAN Model GMSS960603BN AHRI ref 7365096 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 96.1 AFUE Goodman Mfg. 60000 Btuh 48000 Btuh 61 OF 850 cfm 0.029 cfm/Btuh 0.70 in H2O COOLING EQUIPMENT Make Goodman Mfg. Trade GOODMAN; JANITROL; AMANA DISTI... Cond GSX130301B Coil CAPF3030B6D AHRI ref 7365372 Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 11.5 EER, 13.5 SEER 19600 Btuh 8400 Btuh 28000 Btuh 850 cfm 0.057 cfm/Btuh 0.70 in H2O 1.00 162 ROOM NAME Area (ft') Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) CIg AVF (cfm) Room9 176 2181 783 64 45 Room11 162 834 267 25 15 Room92 270 3540 1659 104 94 Room13 84 600 1237 18 70 Room14 60 534 112 16 6 Room15 180 2630 1549 77 88 Room18 391 3961 2034 116 116 Room5 1064 12648 5774 372 329 Pn 11R 04n 4 n7 nonce Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. x 2016 -Sep -1710:30:58 wrIghtstaft Right -Suite® Universal 201717.0.03 RSU20477 Page ...ER\Documentslwrightsoflware\KanchneAFS2B5.rup Calc=MJ8 Front Door faces: NW Main And Up d 2597 28907 14922 850 850 Other equip loads 4736 896 Equip. @ 0.94 RSM 14869 Latent cooling 0 Tr)TG112 I 9 07 I aacno I enon_n I I w.., .1Vw OW OOU Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wri htSOf#° 2016-Sep-1710:30:58 ,n� g Right-Suite®Univ ersa1201717.0.03 RSU20477 Page3 JCM... ER\Documents\wrightsoftware\Kartchner\FS2B5.fup Calc=MJ8 Front Door faces: NW Building Analysis Job: FS2B5 y Date: Basement By: Vince ° Katchner Ihoenp er Itianlnl 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information For: 3esian Conditin Location: Btuh/ft2 Indoor: Heating Cooling Idaho Falls, ID, US 3260 Indoor temperature (°F) 68 75 Elevation: 4741 ft 16.5 Design TD (°F) 74 14 Latitude: 44°N Ceilings Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 57.0 -31.5 Dry bulb (°F) -6 89 Infiltration: Ducts Dailyrange (°F) - 34 (H ) Method Simplified 0 Wet bulb (°F) - 60 Construction quality Average 0 Wind speed (mph) 15.0 7.5 Fireplaces 0 Adjustments Heating Component Btuh/ft2 Btuh % of load Walls 2.9 3260 45.8 Glazing 24.4 1172 16.5 Doors 0 0 0 Ceilings 0 0 0 Floors 1.5 1314 18.5 Infiltration 0 0 0 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 1368 19.2 Adjustments 0 Total 1 1 7114 100.0 Cooling Component Btu h/ft2 Btuh % of load Walls 0 0 0 Glazing 24.5 1178 70.7 Doors 0 0 p Ceilings 0 0 0 Floors 0 0 0 Infiltration 0 0 0 Ducts 0 0 Ventilation 259 15.5 Internal gains 230 13.8 Blower 0 0 Adjustments 0 Total 1 1 1666 100.0 Latent Cooling Load = 0 Btuh Overall U -value = 0.038 Btuh/ft' °F Data entries checked. ^ /�`�- ' 1' ,{. WCIgh�of�' Rig hl-Suite®2016-Sep-17 10:30:58 Universal RSU20477 Page 1 0+M._ER\Documents\wrightsoftware\Kadchner\FS2B5.fup Calc =MJ8 Front Door faces: NW Building Analysis Main And Up o Katchner Hfplmp. pp IGn91r» 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project• • For: Job: FS2B5 Date: By: Vince Location: Btu h/112 Indoor: Heating Cooling Idaho Falls, ID, US 10387 Indoor temperature (°F) 68 75 Elevation: 4741 ft 24.8 Design TD (°F) 74 14 Latitude: 44'N Ceilings Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 57.0 -31.5 Dry bulb (°F) -6 89 Infiltration: Ducts Dailyrange (°F) - 34 (H ) Method Simplified 0 Wet bulb (°F) - 60 Construction quality Average 0 Wind speed (mph) 15.0 7.5 Fireplaces 0 Adjustments 0 Total 1 1 33643 100.0 Component Btu h/112 Btuh % of load Walls 4.8 10387 30.9 Glazing 24.4 8330 24.8 Doors 12.6 264 0.8 Ceilings 1.5 2304 6.8 Floors 1.5 990 2.9 Infiltration 2.6 6631 19.7 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 4736 14.1 Adjustments 0 Total 1 1 33643 100.0 Cooling Component Btuh/ft' Btuh % of load Walls 0.5 1025 6.5 Glazing 25.7 8761 55.4 Doors 3.1 66 0.4 Ceilings 0.8 1308 8.3 Floors 0 0 0 Infiltration 0.3 672 4.2 Ducts 0 0 Ventilation 896 5.7 Internal gains 3090 19.5 Blower 0 0 Adjustments 0 Total 1 1 158181 100.0 Latent Cooling Load = 0 Btuh Overall U -value = 0.063 Btuh/fig °F Data entries checked. 2016 -Sep -17 10:3058 Wright oft' Right -Suite® Universal 2017 17.0.03 RSU20477 Page ._ER\Documents\wrightsoftware\Kartchner\F52B5.rup Colo =MJ8 Front Door faces: NW Component Constructions Job: FS2135 Date: Basement By: Vince Katchner dNidp 7P M I RRifi� 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 For: Location: Indoor: Heating Cooling Idaho Falls, ID, US Indoor temperature (°F) 68 75 Elevation: 4741 ft Design TD (°F) 74 14 Latitude: 44°N Relative humidity (°/fi) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 57.0 -31.5 Dry bulb -6 89 Infiltration: Daily range (°F) - 34 ( H ) Method Simplified Wet bulb (°F) - 60 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U -value Insul R Htg HTM Loss Clg HTM IN Gain ft' BtuhO-T ft? °FMWh BWh/V Btuh StuhRt Btuh Walls 15819-0wc-8: Bg wall, heavy dry or light damp soil, 2"x4" wood int frm, in 272 0.040 19.0 2.83 771 concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh a 272 0.040 19.0 2.71 736 0 0 0 0 S 288 0.040 19.0 2.96 852 0 0 W 304 0.040 19.0 2.96 900 0 0 all 1136 0.040 19.0 2.87 3260 0 0 Partitions (none) Windows 61C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (4 ft n 16 0.330 0 24.4 391 9.46 151 window ht,.2 ft sep.); 6.67 8 head ht a 32 0.330 0 24.4 781 30.3 969 all 48 0.330 0 24.4 1172 23.3 1120 Doors (none) Ceilings (none) Floors 21A -32c: Bg floor, heavy dry or light damp soil, 8' depth, carpet fir fnsh 888 0.020 0 1.48 1314 0 0 �,+ 'I^ Wrlght$Oftt Right -Suite® Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:30:58 ...ER\Documents\wrightsof[ware\Kartchner\FS2B5.rup Calc = MJ8 Front Doorfaoes: NW Page 1 Component Constructions Job: FS2B5 Date: Main And Up By: Vince " Katchner BcnLr it en irlbsihp 601 West 1700 South, Logan, Utah 84321 Phone: 435-755.7080 For: Location: Idaho Falls, ID, US Elevation: 4741 ft Latitude: 44°N Outdoor: Dry bulb (°F) Daily range (°F) Wet bulb (°F) Wind speed (mph) Heating Cooling -6 89 - 60 (H ) 15.0 7.5 Indoor: Heating Cooling Indoor temperature (T) 68 75 Design TD (°F) 74 14 Relative humidity (%) 50 50 Moisture difference (gr/Ib) 57.0 -31.5 Infiltration: Method Simplified Construction quality Average Fireplaces 0 Construction descriptions or Area U -value Insul R Htg HTM Loss Clg HTM Gain 0 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (5 ft fV Btuh&-°F ft'-°FlBtuh Btuh]F Btuh BtuhW Btuh Walls se 316 w 0.330 all 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (1 It e window ht, 2 ft sep.); 6.67 ft head ht Firm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int n 556 0.065 22.0 4.81 2674 '0.47 264 fnsh, 2"x6" wood frm, 16" o.c. stud: Firm wall, vnl ext, 3/8" wood shth, ne 14 0.065 22.0 4.81 67 0.47 7 r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c.stud a 454 0.065 22.0 4.81 2182 0.47 215 24.7 se 14 0.065 22.0 4.81 67 0.47 7 6 S 610 0.065 22.0 4.81 2934 0.47 289 0 w 512 0.065 22.0 4.81 2464 0.47 243 220 all 2160 0.065 22.0 4.81 10387 0.47 1025 Partitions 0.330 (none) 24.4 Windows 30.3 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (4 ft e window ht, 2 ft sep.); 6.67 ft head ht 0 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (5 ft n window ht, 2 ft sep.); 6.67 ft head ht ne 15 e 0 e 366 se 316 w 0.330 all 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (1 It e window ht, 2 ft sep.); 6.67 ft head ht s 40 all 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (3 ft e window ht, 2 I sep.); 6.67 ft head ht 30.3 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (8 It e window ht, 2 It sep.); 6.67 ft head ht 0 61 C: ul .30 shgc .31; 50% outdoor insect screen; 1.6 ft overhang (2.6 w ft window ht, 2 ft sep.); 6.67 ft head ht 401 Doors metal: Door, mtl pur core type w 16 0.330 0 24.4 391 30.3 484 60 0.330 0 24.4 1465. 9.46 .567 15 0.330 0 24.4 366 21.1 316 30 0.330 0 24.4 733 30.3 908 40 0.330 0 24.4 987 30.3 1223 15 0.330 0 24.4 366. 26.7 401 100 0.330 0 24.4 2442 30.3 3027 260 0.330 0 24.4 6359 24.7 6443 3 0.330 0 24.4 73 30.3 91 6 0.330 0 24.4 147 9.46 '57 9 0.330 0 24.4 220 16.4 148 9 0.330 0 24.4 220 30.3 272 40 0.330 0 24.4 977 30.3 1211 7 0.330 0 24.4 164 30.3 203 21 0.170 6.0 12.6 264 3.14 66 wrightssaft' Right -Suite@" Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:30:58 Page 2 CN ... ER\Documents\Wrightsoftware\Kartchner\FS265.rup Cale =MJB Front Door faces: NW Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 112" 1557 0.020 50.0 gypsum board int fnsh 260 0 0 Floors 730 0 0 21A -32c: Bg floor, heavy dry or light damp soil, 8' depth, carpet flr fnsh 176 0.020 0 493 0.020 0 all 669 0.020 0 ,,A- "r' Wriijhtsoft' Right-SWWDUniversal 201717.0.03 RSU20477 AGCA... ER\Documents\wrightsoftware\KartchnoAFS2B5.rup Calc=MJ8 Front Door faces: NW 1.48 2304 0.84 1308 1.48 260 0 0 1.48 730 0 0 1.48 990 0 0 2016 -Sep -17 10:30:58 Page 3 Project Summary Job: FS2B5 Date: Basement By: Vince o NKatchner llling r o hlorNg 601 West 1700 South, Lagan, Utah 84321 Phone: 435-755-7080 Project• For: Notes: Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN Design Information Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960402BN Weather: Idaho Falls, ID, US Cond GSX130181E Winter Design Conditions Summer Design Conditions Coil CAPF1824D6D Outside db -6 OF Outside db 89 OF Inside db 68 OF Inside db 75 OF Design TD 74 OF Design TD 14 OF Temperature rise 77 OF Daily range H Actual air flow 450 cfm Actual air flow Relative humidity 50 % Air flow factor 0.320 cfm/Btuh Moisture, difference 31 gr/Ib Heating Summary Space thermostat Sensible Cooling Equipment Load Sizing Structure 5746 Btuh Structure 1408 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent (20 cfm) 1368 Btuh Central vent (20 cfm) 259 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 7114 Btuh Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load 1566 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 200 Btuh Ducts 0 Btuh Heating Cooling Central vent (20 cfm) -360 Btuh Area (ft') 888 888 Equipment latent load 0 Btuh Volume (fte) 0 0 Air changes/hour 0 0 Equipment total load 1566 Btuh Equiv. AVF (cfm) 0 0 Req. total capacity at 0.70 SHR 0.2 ton Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960402BN Cond GSX130181E AHRI ref 7365095 Coil CAPF1824D6D AHRI ref 7365235 Efficiency 96.1 AFUE Efficiency 11.5 EER, 14 SEER Heating input 40000 Btuh Sensible cooling 12180 Btuh Heating output 32000 Btuh Latent cooling 5220 Btuh Temperature rise 77 OF Total cooling 17400 Btuh Actual air flow 450 cfm Actual air flow 450 cfm Air flow factor 0.078 cfm/Btuh Air flow factor 0.320 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 1„ ►r it hYsafte2016-Sep-1710:30:58 RightSuiteO Univ ersa1201717.0.03 RSU20477 Page ...ER\Documents\wrightsoftware\KartchneAFS2B5.rup Calc=MJ8 Front Door faces: NW Project Summary Main And Up Katchner HBI11tlP ! 0 w11oQr9 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project• • For: Notes: Desi n Information Weather: Winter Design Conditions Outside db -6 OF Inside db 68 OF Design TD 74 OF Heating Summary 0.28 Structure 28907 Btuh Ducts 0 Btuh Central vent (69 cfm) 4736 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 33643 Btuh Infiltration Method Construction quality Fireplaces Idaho Falls, ID, US Simplified Average 0 Heating Equipment Summary Make Heating Cooling Area (ft') 2597 2597 Volume (ft) 20776 20776 Air changes/hour 0.28 0.15 Equiv. AVF (cfm) 97 52 Heating Equipment Summary Make Goodman Mfg. Trade GOODMAN Model GMSS960603BN AHRI ref 7365096 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 96.1 AFUE 60000 Btuh 48000 Btuh 61 OF 850 cfm 0.029 cfm/Btuh 0.70 in H2O Job: FS2B5 Date: By: Vince Summer Design Conditions Outside db 89 OF Inside db - - 75 OF Design TO 14 OF Daily range H Use manufacturer's data Relative humidity 50 % Moisture difference -31 gr/Ib Sensible Cooling Equipment Load Sizing Structure 14922 Btuh Ducts 0 Btuh Central vent (69 cfm) 896 Btuh Blower 0 Btuh Use manufacturer's data n Btuh Rate/swing multiplier 0.94 ton Equipment sensible load 14869 Btuh Latent Cooling Equipment Load Sizing Structure -334 Btuh Ducts 0 Btuh Central vent (69 cfm) -1245 Btuh Equipment latent load 0 Btuh Equipment total load 14869 Btuh Req. total capacity at 0.70 SHR 1.8 ton Cooling Equipment Summary Make Goodman Mfg. Trade GOODMAN; JANITROL; AMANA DISTI... Cond GSX130301B Coil CAPF3030661) AHRI ref 7365372 Efficiency 11.5 EER, 13.5 SEER Sensible cooling 19600 Btuh Latent cooling 8400 Btuh Total cooling 28000 Btuh Actual air flow 850 cfm Air flow factor 0.057 cfm/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. a:: Wry htsoft- 2016 -Sep -1710:30:58 �v Rig htSuite®Univ ersa1201717.0.03 RSU20477 .-ER1Documents\wrightsoftware\Kaachner\FS2B5.rup Calc =MJ8 Front Door faces: NW Paget AED Assessment Job: FS2B5 Date: Basement By: Vince ° Katchner tlralla¢ , 7( ¢n INeaing 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project• • For: Location: Idaho Falls, ID, US Elevation: 4741 ft Latitude: 44°N Outdoor: Heating Cooling Dry bulb (°F) -6 89 Dailyrange (°F) - 34 ( H Wetbulb(°F) - 60 Wind speed (mph) 15.0 7.5 Indoor: Heating Indoor temperature (OF) 68 Design TD (°F) 74 Relative humidity (%) 50 Moisture difference (gr/Ib) 57.0 Infiltration: K)urly Glazing Load / Nourry / Average / A'DSfit Maximum hourly glazing load exceeds average by 35.6%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 58 Btuh (PFG-1.3*AFG) Cooling 75 14 50 -31.5 wriglhtsoft' 2016 -Sep -1 I Rig ht -Su ite®Universal 2017 17.0.03 RSU20477 Page m ... ER\Documents\wrightsoftware\Kartchner\FS2B5.rup Cale =We Front Door faces: NW AED Assessment Job: FS2135 Date: Main And Up By: Vince "'. Katchner *Iwo, 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 For: Location: Indoor: Heating Cooling Idaho Falls, ID, US Ind oor temperature (°F) 68 75 Elevation: 4741 ft Design TD (°F) 74 14 Latitude: 440N Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 57.0 -31.5 Dry bulb (°F) -6 89 Infiltration: Dailyrange (°F) - 34 ( H ) Wet bulb (°F) - 60 Wind speed (mph) 15.0 7.5 Hourly Glazing toad xon i aeaee � emumc Maximum hourly glazing load exceeds average by 17.0%. Zone has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh wri htSofC 2016 -Sep -1710:30:58 Q+---- RightSulte® U niversa1201717.0.03 RSU20477 Page2 Ar:>{yA... ER\Documents\wrightsof(ware\Kartchner\FS2B5.rup Ca1c=MJ8 Front Door faces: NW RighW@ Worksheet Job: FS2B5 Basement Date: B Katchner x Vince 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Basement Rooml 2 Exposed wall 148.0 ft 21.0 ft 3 Room height 8.0 ft d 8.0 ft heaticool 4 Room dimensions 11.0 x 10.0 ft 5 Room area 888.0 ft' 110.0 ft. Ty Construction U-valueOr HTM I Area (f6) I Load 1 Area (fl') I Load I number (Btuh/ft'-T.1 uh/ft') (BH or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6V"15B19 0wo-8 0.069 n 2.83 0.00 288 272 771 0 0 0 0 0 61C. 0.330 n 24.42 .9.46 16 - 0 391 .151 0 '. 0 - 0 0 W Frm wall, vnl ext, 3 0.065 n 0.00 0:00 0 0 0 0 0 0 0 0 61C _ 0.330 n 0.00 0.00 0 0 0 0 0 0 0 0 11 4y Frm wall, vnl ext, 3 0.065 no 0.00 0.00 0 0 : 0 0 0 0 0 0 I -G 61C:. .0.330 ne .:0.00 0.00 0 0 '._0 0 .0 0 0 '.0. W L 15819-0wo-8 0.069 a 2.71 0.00 304 272 736 0 88 72 179 0 61C 0.330 e 24.42 30.27 32 0 781 969 16 0 391 484 -G Frm wall, vni ext, 3 .0.065 a 0.00 0.00 0 0 0 0 0 - 0 0 0 :61C x0.330 a 0.00. 0.00 0 0- 0 0 0 0 0: 0 61C 0.330 a 0.00 0.00 0 0 r. 0 '.0 0 0 0 0 61C 0.330 e" 0.00 0.00 0 0 0 ":0 0 0 0 0 61C 0.330 a 0.00 0.00 0 0 0 ' :0 0 0 0 -0 61C 0.330 e 0.00 0.00 0 0 0 '0 0 0 0 0 61C: 0.330 a 0.00 0.00 0 0 0 0 _0 0 0 ':`-0 Vy Frm wall, vnl ext, 3 0.065 se 0.00 0.00 0 0 0 0 0 0 0: 0 t -G -61C - 0.330 as 0.00 - 0.00 0 0 0 0 0 0 0 0 W 15879-Owc-8 0.069. s 2.96 0.00 288 288 `.. 852 0 80 ` 80 237 - 0 Vy Frm wall, vnl ext, 3 0.065 s 0.00 0.00 0 0 0 0 0 0 0 0 `G 61C 0.330 s 0.00 = 0.00 0 0 0 0 0 0 0 0 W lffilMwo-8 0.069 w 2,96 0,00 304 ` 304 --.900 0 0 '. 0 0 -0 Frm wall, vnl ext, 30.065 w 0.00 0.00 0 0 0 0 0 0 0 0 1� :61C 0.330 w 0.00 0.00 0 0 0: 0 0 0 0: 0 61C 0.330 w 0.00 0.00 0 0 0 0 0 0 0 0 metal 0.170 w 0.00 0.00 0 0 0 0 0 0 0 0 C 168-50ad _ 0.020 .:0.00 0.00 0 0 0 0 0- 0 0 0 F 21A -32c 0.020 - 1.48 0.00 888 888 1314 0 110 110 163 0 F 21A -32c 0.020 -0.00 0.00 0 0 0 ',0 0 0 0 -. 0 F 21A -32c 0.020 0.00 - 0.00 0 0 0 0 0 0 0: 0 61 b) AED excursion 1581 1 1 64 Envelope loss/gain 5746 1178 1 969 549 12 a) Infiltration 0 O 0 0 b) Room ventilation 0 0 0 0 13 Internal. gains: Occupants@ 230 1 230 1 230 Appliances/other : 0 0 Subtotal (lines 6 to 13) 5746 1408 .969 779 Less external load 0 0 00 Less transfer 0 0 0. 0 Redistribution 0 0 0 0 14 Subtotal 5748 1408 969 779 15 Duct loads 0% 0% _0 0 -0% 0% 0 0 1 1 Total room load I 1 5746 1408 969 779 Air required (cfm) 1 4501 4501 1 1 61 2491 �try� Calculations aooroved by ACCA to meet all reouirements of Manual J 8th Ed -Wrightoofft" 2016 -Sep -1710:30:58 Rig htSu ite®Universal 2017 17.0.03 RSU20477 "'...ER\Documents\wrightsaftware\Kaftchner\FS2B5.rup Calc =MJ8 Front Door faces: NW Page Right -M) Worksheet Job: FS2135 Basement Date: Katchner By: Vince 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room2 Room3 2 Exposed wall 17.0 ft 72.0 ft 3 Room height 8.0 ft heat/cool 8.0 It heat/cool 4 Room dimensions 11.0 x 6.0 it 1.0 x 544.0 ft 5 Room area 66.0 ft' 544.0 ft2 Ty Construction U -value Or HTM I Area (f t2) I Load I Area (ft2) Load number (Btuh/ft;'F (Btuh/ft') or perimeter (fl) (Btuh) I or perimeter (ft) I (Btuh) Heat Cool Gross N/P/S Heat Cool Grass N/P/S Heat Cool 6 15819-0wc-8 0.069 n 2.83 0.00. 0 0 0 0 192 176 487 0 61 C 0.330 n 24.42 9.46 0 0 0 0 16 0 391 151 W .Frm wall vnl ext, 3 0.065 n 0.00 0.00 0 0 0 0 0 0 0 0 I --G 61C 0.330 n 0.00 0.00 0 0 0 0 0 0 0 0 11 Vy Frm wall, vnl. ext, 3 ,:0.065 re 0.00 : 0.00 0 - 0 0. 0 0 0 0 :0 �G 61C 0.330 ne 0.00. 0.00 0 0 :..0 0 0 0 A 0. W 151319-0wc-8 0.069 a 2.71 0.00 0 0 0 0 216 200 558 0 L -G 61C 0.330 a 24.42 30.27 0 0 0 0 16 0 391 484 Frm wall vnl ext, 3 Y- 0.065 a 0.00 0.00 0 0 0 0 0 0- 0 '0 :61C .0.330 ' a 0.00 0.00 0 0 0 '0 0 0 0 '.0 61C 0.330 a : 0.00 0.00 0 0 0 0 0 ,. 0 ' 0 0 61C 0.330 a -. 0.00 0.00 0' 0 0 0 0 ` 0 0 0 61C : 0.330 a : 0.00 0.00 ' 0 0 0 0 0 0 .: 0 0 61C 0.330 a 0.00 0.00 0 0 0 0 0 0 0 '0 61C ..0.330 a 0.00 0.00 0 0 - 0 0 0 0 0 0 W Frm wall, vnl ext, 3 0.065 se 0.00 0.00 0 0 0 0 0 0 0 0 I --G -61C 0,330 se 0.00 0.00 0 0 0 0 _.. 0 0 0 0 W 151319-0wc-8 0.069 a 2.96. 0.00 48 48 ,142 0 64 64 0 VAI Frm wall, vni ext, 3 0.065 s 0.00 0.00 0 0 0 0 0 0 .189 0 0 �-G 61C 0.330 s 0.00 0.00 0 0 0 0 0 0 0 :0 W 15819-0wc-8 0,069 '0.065 w 2.96 0,00 88 88 260 0 104 904 308 0 WWW Frm wall, vni ext, 3 w 0.00 0.00 0 0 0 0 0 0 0 0 61C 0.330 w 0.00 0.00 0 0 0 0 0 0 0 0 61C 0.330 w 0.00 0.00 0 0 0 0 0 0 0 0 metal 0.170. w 0.00 0.00 0 0 0 0 0 0 0 a C 16950ad .0.020 - 0,00 0.00 0 0 0 0 '0 0 0 0 F 21A -32c 0.020 - 1.48 0.00 66 66 98 0 544 544 805 0 F 21A -32c.. .0.020 ..0.00 0.00 0 0 I 0 0 0 0 0: 0 F 21A -32c 0.020 - 0.00 0.00 0 0 0 0 0 0 0 0 61 c) AED excursion 0 -7 Envelope loss/gain 500 0 3128 629 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal: gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 500 0 3128 629 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 500 0 3128 629 15 ..Duct loads -0% 0% 0 0 -0% o% 0 :0 Total room load I 5381 32451 An regmred (cfm) I I OI I I 2091 J�'� Calculations approved by ACCA to meet all requirements of Manual J 8th Ed 'Pwrightsoft, Right-Sulte@ Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:330::58 ...ER\Documents\wrightsoflware\Kadchner\FS2B5.rup Calc=MJ8 Front Door faces: NW 9 Right,& Worksheet Basement Katchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Job: FS2B5 Date: By: Vince 1LRoe Room4 238.0 ft 3 8.0 ft heat/cool 4ions 14.0 x 12.0 ft5 168.0 ft' Ty Construction U -value Or HTM I Area (f t') I Load I Area Load number (Btuh/ft'--'F (Bt uh/ft') or perimeter (ft) (Bt h) I or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 15B190wc-8 0,069 n .2.83 0.00. 96 96 284 0 �. G61C 0.330 n 24.42 9.46 0 0 -. 0 0 VL Frm wall, vni ext, 3 0.065 n 0.00 0.00 0 0 0 0 �G 61C 0.330 n 0.00 0.00 0 0 0 0 11 4}t Frm wall, vnl ext, 3 0.065 ne 0.00 0.00 0 0 0 0 I -f' fi1C. :0.330 ne 0.00 0.00 0 0. :0 0 4y 15819-0wo8 0.069 a 2.71 0.00 0 0 0 0 I -G 61C 0.330 a 24.42 30.27 0 0 0 0 Frm wall, vni ext, 3 0.065 ; e 0.00 0.00 0 0 0 '0 :61C 0.330 a 0A0 0.00 0 0 0 0 610 0.330 e 0.00 .0.00. 0 0 0 0 61C 0.330 a 0.00 0.00 0 0 0 0 61C 0.330 a -0.00 0.00 0 0 :0 0 61C - 0.330 a 10100 0.00 0 0 - '0 0 61C 0.330 a 0.00 0.00 0 0 -'0 0 W Frm wall, vni ext, 3 : 0.065 se 0.00 0.00 0 0 0 0 �-f 61C 0.330 se 0.00 0.00 0 0 0 0 W 151319-0wo-8 0.069 s ' 2.96 0.00 96 96 284 0 4y 1-G Frm wall, vni ext, 3 0.065 s 0.00 0.00 0 0 0 0 61C 0.330 s 0.00 0.00 0 0 :0 0 W 151319-0wc-8 0.069 w 2.96 0,00 112 112 ` - 332 : 0 Frm wall, vni ext, 3 0.065 w 0.00 0.00 0 0 0 0 61C 0.330 w 0.00 0.00 0 0 0 0 61C 0.330 w 0.00 0.00 0 0 0 0 �p metal 0.170 w 0.00 0.00 0 0 0 0 C 16B.50ed 0.020 0,00 0.00 0 0 -0 0 _ F 21A -32c 0.020 1.48 0.00 168 168 249 0 F. 21A -32c .'0.020 0.00. 0.00 0 0 : 0 -0 F 21A -32c 0.020 - 0.00 0.00 0 0 0 0 6 c) AED excursion 0 Envelope loss/gain 1146 0 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants@ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 1148 0 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 1148 0 15. Duct loads -0% 0% 0 0 Tatalq em Iasd Airwired(ad ) I I I 901 OI I ..�,{, Calculations aooroved by ACCA to meet all reauirements of Manual J 8th Ed. 9 wrigh�o� Right -Suite® Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:30:58 ...ER\Documents\wrightso([ware\Kartchner\FS285.rup Calc=MJ8 Front Door faces: NW Page Right -M Worksheet o Main And Up Katchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Job: FS2B5 Date: By: Vince Calculations aoaroved by ACCA to meet all reauirements of Manual J 8th Ed wrilghts@ft° Rig ht -Su ite® U niversal 2017 17.0.03 RSU20477 2016 -Sep -1710:330::58 ...ER\Documents\wrightsoftware\Kartchner\FS2B5.rup CaIc=MJS Front Door faces: NW 9 om name Main And Up Room9 posed wall 315.2 ft 27.0 ft om height j4Roonn 8.0 ft d 8.0 It heat/cool dimensions 16.0 x 11.0 ft om area 2597.0 ft° 176.0 ft° Ty Construction U -value Or HTM/fN) I Area (ft') I Load I Area (f t') Load number (Bt uh/ft'---171 (Btuh or perimeter (ft) (Btuh) I or perimeter (ft) I atuh) Heat Cool Gross N/P/S j Heat Cool Gross I N/P/S j Heat Cool 615B19-0wc-8 0.069 n 0.00 0.00 0 0 0 0 0 0 0 I--(' 61C 0.330 n 0.00 0.00 0 0 0 0 0 0 0 0 0 4} � Frm wall, vni ext, 3 0.065 n 4.81 0.47 616 556 2674 264 0 0 0 0 t--I--C 61C 0.330 n 24.42 9.46 60 0 1465 567 0 0 0 O 11 V wall, vni ext; 3 0.065 ne .4.81 0.47 29 14 67 7 0 0 0 0 t-G61C .Frm '0.330 ne 24.42 21.10 15 _ 0 .366 316 0 0 0 0 W L 15B79-ftB 0.069 a 0.00 0.00 0 0 0 0 0 0 0 0 61C 0.330 a 0.00 0.00 0 0 0 0 0 0 0 0 -G Frm wall vnl ext, 3 -.0.065 a 4.81 0,47 .592 454 2182 P 215 .128 112 539 53 61C :0.330 a 24.42 30.27 - 3 0 - 73 91 r. 0 0 0 0 -61C - '0.330 a 24.42 '30.27 9 0 220 272 0 0 0 0 61C 0.330 e 24.42 30.27 16 0 .391 484 16 0 391 484 61C 0.330 a 24.42 30.27 :. 30 0 .733 .908 0 0 O ,0 61C 0.330 a 24.42 30.27 40 0 987 1223 0 0 0 0 61C .0.330 a 24.42 30.27 40 - 0 977. 1211 0 - 0 0 '-0 Vy .Frm wall, vnl ext, 3 0.065 as 4.81 0.47 29 14 67 7 0 0 0 0 `moi 61C 0.330 as 24.42 26.75 15 0 366 401 0 0 0 0 W 15B19-0wo-8 0.069 a ,:: 0.00 0,00 O 0 O 0 0 0 0 0 VAI Frm wall, vni ext, 3 0.065 s 4.81 0.47 616 610 2934 289 88 88 423 42 I -G 61C 0.330 a 24.42 9.46 6 6 147 57 0 0 0 0 W 15B19 Owc 8 0,069 w 0.00 0,00 0 0 0 0 0 0 0 0 WAG Frm wall vni ext, 3 0.065 w 4.81 0.47 640 512 2464 243 0 0 0 0 61C 0.330 w 24.42 30.27 7 0 164 203 0 0 0 0 �G 61C 0.330 w 24.42 30.27 100 0 2442 3027 0 0 0 0 �p metal 0.170 w 12.58 3.14 21 21 264 66 0 0 0 0 G 16B-50ad _ 0.020 1.48 0.84 1557 1557 2304 :. 1308 176 176 Y 260 148 F 21 A -32c 0.020 - 0.00 0.00 0 0 0 0 0 0 0 _ 0 F 21A -32c ::'0.020 1.48 0.00 .176 176 260 0 0 -0 0. 0 F 21 A32c 0.020 1.48 0.00 493 493 730 0 0 0 O 0 61 c) AED excursion g -1 Envelope loss/gain 22277 1116 1613 726 12 a) Infiltration 6631 672 568 58 b) Room ventilation 0 D 0 0 13 Internal gains: Occupants @ 230 3 690 0 0 Appliances/other 2400 0 Subtotal (lines6 to 13) 28907 14922 2181 783 Less external load 0 0 0 0 Less transfer 0 0 0 a Redistribution 0 0 0 0 14 Subtotal 28907 14922 2181 783 15 1 Duct loads 0% 0% 0 0 -0% 0% 0 0 Total room load 1 28907 148501 2181 7451 Air required (cfm) 1 1 1 1 Calculations aoaroved by ACCA to meet all reauirements of Manual J 8th Ed wrilghts@ft° Rig ht -Su ite® U niversal 2017 17.0.03 RSU20477 2016 -Sep -1710:330::58 ...ER\Documents\wrightsoftware\Kartchner\FS2B5.rup CaIc=MJS Front Door faces: NW 9 Right -M Worksheet Main And Up Katchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Job: FS2B5 Date: By: Vince 1. Room name Room11 Room12 2 Exposed wall 9.0 It 33.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/ocol 4 5 Room dimensions Room area 9.0 x 18.0 ft 162.0 ft- 15.0 x 18.0 ft 270.0 ft' Ty Constmction number U -value (Btuh/ft2-'F� Or HTM I (13tuh/ft2) Area (f t2) I or perimeter (ft) Load ( (Btuh) Area (W) I or perimeter (ft) Load I (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/ /S Heat Cool 6 11 W L -G W -G VL 4y t --G 15B19 0wc-8 61C Frm wall, vnl ext, 3 61C Frm wall vnl ext, 3 61C 151319-0wo8 61C Frm wall, vnl ext, 3 :61C 0.069 0.330 0.065 0.330 0.065 0.330 0.069 0.330 0.065 0.330 -'0.330 n.... n n n ne ne a a e a-.24.42 0.00 0.00 4.81 24.42 4.81 24.42...: 0.00 .0.00 ` 4.81 0.00 0.00 0.47 9.46 0.47 -. 21.10 0.00 0.00 0.47 30.27 0 0 0 0 0 0 0 0 - 72 3 0 0 0 0 - 0 '.. 0 0 0 69 0" 0 0 0 0 0 _ 0 0 0 332 73 0 0 0 0 0 '.0 0 0 33 91 0 0 144 30 0 0 0 0 120 0 0 0 114 0 0 0 0 0 90 0 0' 0 548 733 0 0 0 0 433 0 0 '0 54 284 - 0 0 0 0 43 0 61C 61C 61C - 61C 61C Frm wall, vnl ext, 3 81C 151319-owc-8 -. 0.330 0.330 0.330 .0.330 0.065 0,330 0969. a a e - e` e as as a -24.42 24.42 24.42 24.42 24.42 4.81 24.42 0.00 30.27 30.27 30.27 30.27' 30.27 0.47 26.75 0.00 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 0 a 0 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 '. 0 0 30 0 0 0 0 ': 0 0 0 0 0 0 0 0 '0 0 0 733 0 0 0 0 0 '0 0 908 0 0. 0 0 ° 0 Vy 1-G W' Vy 1-G Frm wall, vnl ext, 3 61C 15B19 0wc-8 0.065 0.330 .0.069 s s w 4.81 24.42 0.00 0.47 9.46 '. 0.00 0 0 0 0 0 :. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ". 0 0 0 0 W Frm wall, vnl ext, 3 61C 0.065 0.330 w w 4.81 24.42 0.47 30.27 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1� 61C metal : 16B-50ad : 0.330 0.170 0.020 w w 24.42 12.58 1.48 30.27 3.14 0.84 0 0 162 0 0 162 0 0 240 0 0 136 0 0 270 0 0 270 0 0 '. 400 0 0 227 C F F 21A -32c 21A -32c 0.020 :0.020 - 0.00 1.48 0.00 0.00 0 0 0 0 0 : 0 0 0 0 ` 0 0 0 0 0 0 0 F 21A -32c 0.020 - 1.48 0.00 0 0 0 0 0 0 0 0 61 0)AED excursion 1 1 -12 -157 Envelope loss/gain 645 248 2846 1358 12 a) Infiltration b) Room ventilation 189 0 19 0 694 0 70 0 13 Internal gains: Occupants @ 230 0 0 1 230 Appliances/other 0 g Subtotal (lines 6 to 13) 834 267 3540 1659 14 15 Less external load Less transfer Redistribution Subtotal Duct loads -0% 0% 0 0 0 834 0 0 0 0 : 267 0 -0% 0% 0 0 0 3540 0 0 0 0 1659 0 Total rcom load Air required (cfm) 834 25 267 15 3104 69 1894 y Calculations aDoroved by ACCA to meet all reauirements of Manual J 8th Ed "r wrig~ksQft' Right -Suite® Universal 2017 17.0.03 RSU20477 2016 -Sep -17 10:30-58 '1`` ...ER\Documents\wrightsaftware\Kartchner\FS2B5.rup Calc= MJ8 Front Door faces: NW Page 5 Right -J® Worksheet Job: FS2B5 0 Main And Up Date: Katchner By: Vince 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room13 Room14 2 Exposed wall 7.0 ft 5.0 ft 3 15 Room height 8.0 ft heat/coal 8.0 ft heat/cool 4 Room dimensions 12.0 x 7.0 ft 12.0 x 5.0 ft Room area 84.0 ft' 60.0 ft2 Ty Construction U -value Or H I Area (ft.). I Load Area (ft') Load number (Btuh/ft'-'F (Btuh/ft') or perimeter (ft) (Btuh) I or perimeter (ft) I (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 615B190wo8 0.069 n 0.00 0.00. 0 0 0 0 0 0 0 �!- 61C' : 0.330 n 0.00 0.00 0 0 0 0 0 0 0 i0 :0 V� Fran wall, vnl ext, 3 0.065 n 4.81 0.47 0 0 0 0 0 0 0 `f 61C 0.330 n 24.42 9.46 0 0 0 0 0 0 0 0 0 11 V� Fran wall, vnl ext, 3 0.065 ne 4.81 0.47 0 0 : 0 0 0 0 0 0 `G 61C , 0.330 re. 24.42 21.10 - 0 0 `. 0 0 0 a 0 0 W I 15619-0wo-e 0.069 a 0.00 0.00 0 0 0 0 0 0 0 0 61C 0.330 a 0.00 0.00 0 0 0 0 0 0 0 0 -G Frm wall vnl ext, 3 0.065 a 4.81 0.47 0 -. 0 0 0 0 0 0 0 61C 0.330 a 24.42: 30.27. 0 0 0 0 _ 0 - 0 0 0 61C - 0.330 a 24.42 30.27 0 0 0 0 0 0 0 0 Bic 0.330 a 24.42:. 30.27 '0 0 0 0 '.0 0 0 0 Bic 0.330 a 24.42 30.27 0 0 0 0 0 0 '' 0 0 61C : 0.330 a 24.42 30.27 0 0 0 0 0 0 0 )0 61Cf:: ,0.330 a 24.42 30.27 0 0 0 0 0 0 0 0 W .Frm wall, vnl ext, 3 0.065 se 4.81 0.47 0 0 0 0 0 0 0 0 `C -61C 0.330 as 24.42 26.75 0 0 0 0 0 0 0 0 W 151319-0wc-8 0.069 s 0.00 , 0.00 0 0 0- 0 0 0 0 0 Vy Fran wall, vnl ext, 3 0.065 s 4.81 0.47 56 53 255 25 40 37 178 18 `G 61C 0.330 s 24.42 9.46 3 3 73 28 3 3 73 28 W 15619-0wc-8 0.069 w 0.00 0,00 ( 0 0 : 0 0 0 0- 0 0 VVIIII Frm wall, vni ext, 3 0.065 w 4.81 0.47 0 0 0 0 0 0 I -G 61C 0.330 w 24.42 30.27 0 0 0 0 0 0 0 0 0 0 61C 0.330 w 24.42 30.27 0 0 0 0 0 0 0 0 L�pC metal 0.170 w 12.58 3.14 0 0 0 0 0 0 0 0 C 1613-50ad 0.020 - 1.48 0.84 84 84 '124 71 60 60 89 50 F 21A -32c 0.020 - 0.00 0.00 0 0 0 0 0 0 0 0 F. 21A -32c 0.020 - 1.48 0.00 0 0 - 0 :.0 f.0 0 0 : 0 F 21A -32c .0.020 -. 1.48 0.00 0 0 0 _0 60 60 89 0 61 c) AED excursion 1-102 5 Envelope loss/gain 453 23 429 101 12 a) Infiltration 147 15 1 105 11 b) Room ventilation 0 0 0 0 13 Internet gains: Occupants @ 230 0 0 0 1 0 Appliances/other 1200 0 Subtotal (lines 6 to 13) 600 1237 534 112 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 14 Subtotal 600 0 1237 534 112 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 1 I Total room load I I 8081 12701 134 1161 Air regwmd (cfm) 1 1 1 Calculations aunroved by ACCA to meet all requirements of Manual J 8th Ed wrigh"oft, Rig htSuile® Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:330::58 ...ER\Documents\wrightsoftware\KartchneAF82B5.rup Calc =MJ8 Front Door faces: NW Page 6 Right -J® Worksheet A Main And Up Katchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Job: FS2B5 Date: By: Vince 1 Room name Room15 Rcoml8 2 Exposed wall 27.0 It 35.0 ft 3 Room height 8.0 it heaticool 8.0 it heat/cool 4 Room dimensions 12.0 x 15.0 ft 1.0 x 391.0 it 5 Room area 180.0 ft' 391.0 fP Ty Construction U -value Or HTM I Area (ft') I Load I Area (ft') I Load number (Bluh/ft''F (Btuh/f t') or perimeter (ft) (Btuh) or perimeter (ft) I (Blob) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6. W 15B19-0wc-8 0.069 n 0.00 0.00 0 0 0 0 0 0 0 !0 61 C ' 0.330 n 0.00 0.00 0 0 0 0 0 0 0 0 VL wall, vni ext, 3 0.065 n 4.81 0.47 0 0 0 0 160 130 625 62 __G �G 61C 0.330 n 24.42 9.46 0 0 0 0 30 0 733 284 11 Vy Frm wall vni ext, 3 0.065 ne 4.81 0.47 0 0 0 0 0 0 0 '.0 �G 61C 0.330 ne 24.42 21.10 0 0 'a 0 0 0 0 0 '0 W 15879-0wc-8 0.069 a 0.00 0.00 0 0 0 0 0 0 0 0 �G 61C 0.330 a 0.00 0.00 0 0 0 0 0 0 0 0 r'. Frm wall, vni ext, 3 0.065 a 4.81 0.47 0 0 0 0 0 0 0 0 :sic 0.330 a 24.42. 30.27 0 0 : 0 '0 : 0 0 0 1. '0 a1C '0.330 a -24.42 30.27 0 0 0 '0 0 0 0 0 61C 0.330 a 24.42 30.27 0 0 0 0 0 0 0 0 61C 0.330 a 24.42 30.27 0 0 0 - 0 0 0' 0 0 61C 0.330 a 2442 .30.27 0 0 0 : 0 0 0 0 - 0 61C .0.330 a 24.42 30.27 0 0 0 0 0 0 0 0 W Frm wall, vni ext, 3 0.065 as 4.81 0.47 0 0 0 0 0 0 0: 0 `G 61C -- -0.330 as 24.42 26.75 0 0 0 0 0 0 0 0 W 15131Mwc-8 0.069 s 0.00 0.00 0 0 0 0 0 0 0 0 Vy Frm wall, vni ext; 3 0.065 s 4.81 0.47 120 120 577 57 0 0 0 0 1-G 61C 0.330 s 24.42 9.46. 0 0 0 0 0 0 0 0 W. 15B19-0wo8 .0.069 w ` 0.00 0.00 0 0 -' 0 0 0 0 '.0 '0 Frm wall, vni ext, 3 0.065 w 4.81 0.47 96 71 342 34 120 88 425 42 61C 0.330 w 24.42 30.27 0 0 0 0 7 0 164 203 61C 0.330 w 24.42 30.27 25 0 611 757 25 0 611 757 metal 0.170. w 12.58 3.14 0 0 0 0 0 0 0 0 C 1613-50ad 0.020 - 1.48 0,84 - 180 180 : _266 151 391 391 579 328 F 21A -32c 0.020 - 0.00 0.00 0 0 0 0 0 0 0 0 F 21A -32c : ;0.020 - 1.48 0100 0 0 0 0 ' 0 0 0 0 F 21A -32c, . 0.020 - 1.48 0.00 180 180 266 0 60 60 89 0 61 c)AED excursion 263 1 284 Envelope loss/gain 2062 1261 3225 1959 12 a) Infiltration 568 58 736 75 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants Q 230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2630 1549 3961 2034 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2630 1549 3961 2034 15 Duct loads -0% 0% _0 0 -0% 0% 0 0 Total room load 2630 1549 3961 2034 Air required (cfm) 77 88 116 116 Calculations aoproved by ACCA to meet all requirements of Manual J 8th Ed 1ulsright--ii Right -Suite® Universal 2017 17.0.03 RSU20477 2018 -Sep -1710:30:58 ...ER\Documents\wrightsofKvare\Kartchner\FS2B5.rup Calc= MJ8 Front Door faces: NW Page 7 Right,J® Worksheet Main And Up Katchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Job: FS2B5 Date: By: Vince 1 Room name Room5 Room16 2 Exposed wall 157.2 ft 15.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 1064.0 ft 1.0 5 Room area 1064.0 fl' x 210.0 ft. 210.0 ft' Ty Construction U -value Or HTM I Area (ft2) I Load I Area (fe) Load number I (Btuh/ftR*F� (Btuh/ft2) or perimeter (ft) (Stuh) I or perimeter (ft) I (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat C 6. 47/ 15619-0wc-8 0.069 n 0.00 0.00 0 0 0 I-(' 61C 0.330 0 0.00 0.00 0 0 0 0 0 0 0 0 0 W Fon wall, vnl ext, 3 0.065 n 4.81 OA7 304 304 1462 144 0 8 0 0 0 `-G 61C 0.330 n 24.42 946 0 0 0 0 8 38 4 11 V� Frm wall, vnl ext, 3. 0.065 ne 4.81 0.47 -. 29 14 67 0 0 0 0 �-C 61C:.. 0.330 no 24.42 21.10 15 0 366 7 316 : 0 0 0 0 0 0 0 0 W 151319-0Wc-8 0.069 a 0.00 0.00 0 0 0 0 �-G 61C 0.330 a .0.00 0.00 0 0 0 0 0 0 0 0 Frm wall, vnl ext, 3 0.065 a 4.81 0.47 272 183 878 87 0 0 0 0 61C 0.330 a 24.42 30.27 0 0 0 0 0 -'. 0 0 0 : 0 61C 0.330 e - 24.42 30.27 - 9 : 0 : 220 - 272 0 0 0 0< 0 0 '.0 61C 0.330 a 24.42 30.27 0 0 0 0 0 "0 61C 0.330. a 24.42 30.27 0 0 0 a 0- 0-< 0 0 `':0 61C' 0.330 a 24.42 30.27 40 0 ' 987 :1223 0 - 0 0 0 "0 61C:. _.'.0.330 a 24.42 :30.27 40 ` 0 ..977 1211 0 0 0 Vy .Frm wall, vnl ext, 3 0.065 se 4.81 0.47 29 14 67 7 0 : 0 0 `G 61C _ 0.330 se 24.42 26.75 15 0 366 401 0 0 - -0 0 0 W - 1513790wo-.8 0.069 s c 0.00. ..0.00 0 0 0 0 0 0 0 Vy Frm wall, vnl ext, 3 0.065 a 4.81 0.47 304 304 1462 144 8 0 0 L -G 610. 0.330 s 24142 9.46 0 0 0 0 0 8 0 38 4 W 15819-0wc-8 0.069 w 0.00 0.00 0 0 0 0 0 0 wI'--� Frm wall vnl ext, 3 0.065 w 4.81 0.47 320 274 1318 130 :0 104 0 79 0 380 : 0 37 61C 0.330 w 24.42 30.27 0 0 0 0 0 0 0 I ---G ��EDDD 61C 0.330 w 24.42 30.27 25 0 611 757 25 0 611 0 757 metal 0.170 w 12.58 3.14 21 21 264 66 0 0 0 C 1613-50ad 0.020 - 1.48 084 - 24 24 36 -20 210 210 311 0 176 F 21A -32c 0.020 - 0.00 0.00 0 0 0 0 0 0 F 21A -32c.. 0.020 - 1.48 0.00 176 176 260 0 0 0 0 0 0 F 21A -32c 0.020 - 1.48 0.00 0 0 0 0 193 193 286 0 0 61 c) AED excursion -546 267 Envelope loss/gain 9341 4239 1664 1245 12 a) Infiltration 3307 335 376 2 32 b) Room ventilation -0 0 0 O 13 Internal gains: Occupants @ 230 0 0 1 Appliances/other. 230 1200 0 Subtotal (lines 6 to 13) 12648 5774 19791 1507 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 012648 15 Duct loads 5774 1979 1507 -0% 0% 0 0 -0% 0%1 0 0 1 1 Total room load 11 Air required (cfm) 1 1237 1 532 I 1 19 15861 2 91 581 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed wright.so t- Right -Suite® Universal 2017 17.0.03 RSU20477 2016-Sep-1710:30:58 ...ER1DocumentslwrightsoftwarelKartchner\FS2B5.rup Calc =MJ8 Front Door faces: NW Page basement Job M FS2B5 Performed by Vince for: Katchner 601 West 1700 South Logan, Utah 64321 Phone: 435-755-7080 Scale: 1 : 67 Page 1 RightSui te® Univerml 2017 17.0.03 RSU20477 2016 -Sep -17 10:31:19 ... ig htsoftware\Kartchner\FS2B5.ru p Main Job #: FS285 Performed by Vince for: Katchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 67 Page 2 Right -Sul te® Universal 2017 17.0.03 RSU20477 2016 -Sep -17 10:31:19 ... ightsoflware\Kartch ner\FS2 B5.rup 2nd floor Job M FS2135 Performed by Vince for: Katchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 67 Page 3 Right -Sul te® Universal 2017 17.0.03 RSU20477 2016 -Sep -17 10:31:20 ... ig htsoftware\Kartchner\FS2B5.rup Duct System Summary Job: FSI Date: Basement By: Vince ' Katchner Hevr n4 it on fllan3vp 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 For: Name Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0.30 in H2O 0.30 in H2O Available static pressure 0.40 in H2O 0.40 in H2O Supply/ return available pressure 0.303 / 0.097 in H2O 0.303 / 0.097 in H2O Lowest friction rate 0.106 in/100ft 0.106 in/100ft Actual air flow 450 cfm 450 cfm Total effective length (TEL) Roon-I 377 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Rooms c 389 38 124 0.106 8.0 0x0 ShMt 36.0 250.0 SO Roon-I c 389 38. 1.24 0.106 8.0 0x0 ShMt .36.0 250.0 st1 Roomz h 500 39 0 0.106 6.0 Ox 0 ShMt 36.0 250.0 st1 Room3 h 1043 82 67 0.106 6.0 0X0 ShMt 36.0 250.0 st2 RoonI In 1043 82 67 0.106 6.0 0x0 ShMt 36.0 250.0 st2 Room3-B h 1043 82 67 0.106 6.0 Oxo ShMt 36.0 250.0 st2 Room4 h 1148 90 0 0.106 6.0 0x0 ShMt 36.0 250.0 s12 + WrightsOW Right -Suite® Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:30:59 Am ... ERsDocuments\wrightsoftware\Kartchn.6FS2B5.rup Calc=MJ8 Front Door faces: NW Pagel Trunk Htg ClgDesign TEL Veloc Diam H x W Duct Stud/Joist Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st1 Peak AVF 115 249 0.106 373 8.1 8 x 12 FShtMetlst2, 0.106 530 Peak AVF 335 201 0.106 502 9.0 8 x 12 htMetl 249 + WrightsOW Right -Suite® Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:30:59 Am ... ERsDocuments\wrightsoftware\Kartchn.6FS2B5.rup Calc=MJ8 Front Door faces: NW Pagel Grill Htg I TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm (ft) FR (fpm) (in) (in) Opening (in) Mall Trunk rb10 0x0 335 201 91.0 0.106 530 9.0 2-3.25x14 2-10x18 SJSp rt1 rb11 0x0 115 249 91.0 0.106 394 8.1 2-3.25x14 2-10x18 SJSp rt2 + WrightsOW Right -Suite® Universal 2017 17.0.03 RSU20477 2016 -Sep -1710:30:59 Am ... ERsDocuments\wrightsoftware\Kartchn.6FS2B5.rup Calc=MJ8 Front Door faces: NW Pagel Return Trunk Detail Table 2016 -Sep -17 10:30:59 - wrightsoft° Right -Suite® Universal 2017 17.0.03 RSU20477 Page XM ...ER\Documents\wrighL oftware\Kartchner\FS2B5.rup Calc= MJ8 Front Door faces: NW Trunk HtgClg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt1 Peak AVF 335 201 0.106 377 9.0 8 x 16 ShtMetl rt2 Peak AVF 115 249 0.106 280 8.1 8 x 16 ShtMetl 2016 -Sep -17 10:30:59 - wrightsoft° Right -Suite® Universal 2017 17.0.03 RSU20477 Page XM ...ER\Documents\wrighL oftware\Kartchner\FS2B5.rup Calc= MJ8 Front Door faces: NW Duct System Summary Job: FS2B5 Date: Main And Up By: Vince 711a9i9p Katchner .Heel np ll. 9n 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project• • For: External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.70 in H2O 0.30 in H2O 0.40 in H2O 0.200 / 0.200 in H2O 0.075 in/100ft 850 cfm 534 ft Cooling 0.70 in H2O 0.30 in H2O 0.40 in H2O 0.200 10.200 in H2O 0.075 in/100ft 850 cfm Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Roomll h 834 25 15 0.075 6.0 Oz0 ShMt 39.0 495.0 st3 Room12 h 1770 52 47 0.075 6.0 Oxo ShMt .39.0 495.0 st3 Room12-A h 1770 52 47 0.075 6.0 Oxo ShMt 39.0 495.0 st3 Room13 c 1237 18 70 0.075 6.0 Oxo ShMt 39.0 495.0 st3 Room14 h 534 16 6 0.075 6.0 0x0 ShMt 39.0 495.0 st3 Room15 C 1549 77 88 0.075 6.0 0x0 ShMt 39.0 495.0 st4 Room16 c 1507 58 86 0.075 6.0 0x0 ShMt 39.0 495.0 st3 Room18 h 1980 58 58 0.075 6.0 0x0 ShMt 39.0 495.0 st3 Room18-A h 1980 58 58 0.075 6.0 0x0 ShMt 39.0 495.0 st3 Rooms h 1807 53 47 0.075 6.0 0x0 ShMt 39.0 495.0 st3 Rooms -A h 1807 53 47 0.075 6.0 0x0 ShMt 39.0 495.0 st3 Rooms -e h 1807 53 47 0.075 6.0 0x0 ShMt 39.0 495.0 SO Rooms -C h 1807 53 47 0.075 6.0 Oxo ShMt 39.0 495.0 st3 Room5-D h 1807 53 47 0.075 6.0 Oz0 ShMt 39.0 495.0 st3 Rooms -E h 1807 53 47 0.075 6.0 Oxo ShMt 39.0 495.0 st3 Rooms -F h 1807 53 47 0.075 6.0 Oxo ShMt 39.0 495.0 st3 Rooms h 2181 64 45 0.075 5.2 8x6 ShMt 39.0 495.0 Supply Trunk Detail Table wrightsnft' Right -Suite® Universal 2017 17.0.03 RSU20477 2016-sep-1710:30:50 Page 3 ADM- ... ER\Documents\wrightsoftware\Kartchner\FS2B5.rup Cate =MJB Front Door faces: NW Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (Cfm) (cfm) FR (fpm) (in) (in) Material Trunk st3 Peak AVF 655 670 0.075 603 12.6 8 x 20 ShtMetl st4 Peak AVF 130 135 0.075 203 6.9 8 x 12 ShtMetl wrightsnft' Right -Suite® Universal 2017 17.0.03 RSU20477 2016-sep-1710:30:50 Page 3 ADM- ... ER\Documents\wrightsoftware\Kartchner\FS2B5.rup Cate =MJB Front Door faces: NW Return Branch Detail Table Name Grill Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb15 0x0 150 193 0 0.075 305 7.9 2-3.25x14 2-10x18 SJSp rb16 0x0 129 110 0 0.075 407 6.8 3.25x14 10x9 SJSp rb8 0x0 372 329 0 0.075 392 10.1 3-3.25x14 3-10x27 SJSp rb14 0x0 58 86 0 0.075 272 5.8 3.25x14 10x9 SJSp rb13 0x0 77 88 0 0.075 279 5.9 3.25x14 10x9 SJSp rb12 0x0 64 45 0 0.075 203 5.2 3.25x14 10x9 SJSp 59 wrightsaft' Right -Suite® Page Universal 201717.0.03 RSU20477 2016 -Sep -17 4 .-ER\Documents\wrlgh[software\Kartchner\FS265.rup Cole =MJB Front Door fares- NW