HomeMy WebLinkAboutRESCHECK - 17-00105 - 675 Canyon Springs - SFRCREScheck Software Version 4.6.3
�(J Compliance Certificate
Project 675 canyon springs
Energy Code:
2012 IECC
Location:
Idaho Falls, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Conditioned Floor Area:
3,017 ft2
Glazing Area
18%
Climate Zone:
6 (7918 HDD)
Permit Date:
2/23/17
Permit Number:
0.0
Construction Site: Owner/Agent:
Designer/Contractor:
1340 Indian Hollow Fall Creek Homes
High Country Heating
Ammon, Id 83406 1340 Indian Hollow
High Country Heating
Ammon, Id 83406
P.O. Box 627
0.150
Rigby, Id 83442
139
208-745-8056
highcountryph@yahoo.com
Compliance: Passes using UA trade-off
Compliance: 3.2% Better Than Code Maximum UA: 315 Your UA: 305
The % Better or Worse Than Cade Index reflects how close to compliance the house Is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Wall 1: Wood Frame, 16" D.C.
Door 1: Solid
Window 1: Other:Double Pane with Low -E
Wall 2: Wood Frame, 16" o.c.
Window 1: Other:Double Pane with Low -E
Wall 3: Wood Frame, 16" o.c.
Door 1: Solid
Window 1: Other:Double Pane with Low -E
Wall 4: Wood Frame, 16" D.C.
Window 1: Other:Double Pane with Low -E
Basement Wall 1: Solid Concrete or Masonry
Wall height: 9.0'
Depth below grade: 8.0'
Insulation depth: 9.0'
Window 1: Other:Double Pane with Low -E
525
21.0
0.0
0.057
21
21
0.150
3
139
0.300
42
415
21.0
0.0
0.057
22
32
0.300
10
525
21.0
0.0
0.057
25
42
0.150
6
47
0.300
14
415
21.0
0.0
0.057
23
15
0.300
5
472
19.0
0.0
0.044
20
20 0.300 6
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Hngela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 1 of 9
Basement Wall 2: Solid Concrete or Masonry 310 19.0 0.0
0.044 12
Wall height: 9.0'
Depth below grade: 8.0'
Insulation depth: 9.0'
Window 1: Other:Double Pane with Low -E 40
0.300 12
Basement Wall 3: Solid Concrete or Masonry 410 19.0 0.0
0.044 17
Wall height: 9.0'
Depth below grade: 8.0'
Insulation depth: 9.0'
Window 1: Other:Double Pane with Low -E 20
0.300 6
Basement Wall 4: Solid Concrete or Masonry 310 19.0 0.0
0.044 13
Wall height: 9.0'
Depth below grade: 8.0'
Insulation depth: 9.0'
Window 1: Other:Double Pane with Low -E 20
0.300 6
Ceiling 1: Flat Ceiling or Scissor Truss 1,601 50.0 0.0
0.026 42
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in
REScheck Version 4.6.3 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name - Title Signature Date
Project Notes:
job Number: 675 canyon springs
M
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 2 of 9
CREScheck Software Version 4.6.3
�(J Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
103.1,
;Construction drawings and-
.;documentation
❑Complies
103.2
demonstrate
❑Does Not
[PR1]1
:energy code compliance for the
:building envelope.
[]Not Observable
❑Not Applicable
103.1,
'Construction drawings and
❑Complies
103.2,
documentation demonstrate
❑Does Not
403.7
[PR3]1
;energy code compliance for
:lighting and mechanical systems.
❑Not Observable
a
:Systems serving multiple
❑Not Applicable
;dwelling units must demonstrate
:compliance with the IECC
:Commercial Provisions.
302.1,
- Heating and cooling equipment is:
Heating:
Heating:
:❑Complies
.'. sized per ACCA Manual S based
Btu/hr_
Btu/hr_
;❑Does Not
[PR2]?
„on loads calculated per ACCA
Cooling:
Cooling:
:❑Not Observable
-:
Manual J or other methods
.,approved by the code official.
Btu/hr
Btu/hr
;❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1—)7 2'1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 3 of 9
Additional Comments/Assumptions:
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: 675 canyon springs Reportdate: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 4 of 9
402.1.1,
;Door U -factor. U-_
U- ;❑Complies ;See the Envelope Assemblies
402.3.4
:U -factors of fenestration products❑Complies
;❑Does Not table for values.
[FRl]1
:are determined in accordance
;❑Not Observable
1400 that do not exceed code
:with the NFRC test procedure or
❑Not Applicable
402.1.1,
:Glazing U-factor(area-weighted U-
U -_❑Complies ;See the Envelope Assemblies
El
402.3.1,
average).
Not table for values.
402.3.3,
402.3.6,
❑Complies
;❑Nat Observable
402.5
❑Does Not
❑Not Applicable
[FR211
:
V
;Fenestration that is not site built
[FR20]1
303.1.3
:U -factors of fenestration products❑Complies
AAMA /WDMA/CSA 101/1.5.2/A440
[FR4]1
:are determined in accordance
El Not
1400 that do not exceed code
:with the NFRC test procedure or
limits.
402.4,4
;taken from the default table.❑Not
Observable
:sealed at housing/interior finish
,and
Applicable
402.4.1.1 ,Air barrier and thermal barrier
❑Complies
[FR23]1
:installed per manufacturer's
❑Does Not
:insulated to aR-8. All other ducts R-
j instructions.
❑Nat Observable
402.4.3
;Fenestration that is not site built
[FR20]1
:is listed and labeled as meeting
Q)
AAMA /WDMA/CSA 101/1.5.2/A440
for has infiltration rates per NFRC
1400 that do not exceed code
limits.
402.4,4
1IC-rated recessed lighting fixtures
[FRl6�2
:sealed at housing/interior finish
,and
labeled to indicate 252.0 cfm
:leakage at 75 Pa.
403.2.1
;Supply ducts in attics are R--
[FR1211
:insulated to aR-8. All other ducts R-
in unconditioned spaces or —
:outside
the building envelope are
:insulated to 2:11-6.
403.2.2
:All joints
and seams of air ducts,]
[FR13]1
lair
handlers, and filter boxes are
]sealed.
403.2.3 1Building cavities are not used as
[FR1513.:; ;ducts or plenums.
HVAC piping conveying fluids R --
above 105 4F or chilled fluids
below 55 4F are Insulated to a -R-
3.
Protection of insulation on HVAC `
piping. i
Hot water pipes are insulated to R -
z R-3.
s Not
Observable
Applicable
R --
s Not
Observable
s Not
Observable
111 High Impact (Tier 1) 1--2 Medium Impact (Tier 2) 13;1 Low Impact (Tier 3)
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 5 of 9
Additional Comments/Assumptions:
I I High Impact (Tier 1) 1,2IMedium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 6 of 9
'=Ski lon
' # Insulation Inspection
Plans Yeirffed
Velue
Pteld;Yefhed Complles� , Cot ments/AssI mr lopsj
�
!`
\lelue
--,; ,.,
3031
All installed insulation is labeled
❑Complies
[IN13)z -nor the installed R -values
❑Does Not
` :]provided.
.`
❑Not Observable
R -
I R -❑Complies
❑Not Applicable
;See the Envelope Assemblies
402.1.1, :Wall insulation R -value. If this is a:
402.2.5,
:mass wall with at least 'A of the
EJ—Wood
El -Wood
0Does Not ;table for values.
402.2.6
:wall insulation on the wall
:exterior,
: ❑ Mass
j ❑ Mass
❑Not Observable
[IN3)1
the exterior insulation
:requirement applies (FR10).
❑ Steel
❑ Steel❑Not
Applicable
303.2
,Wall insulation is installed per
❑Complies
[IN4)1
(:manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 1 High Impact (Tier 1) 12 `..1 Medium Impact (Tier 2) 1 3>1 Low Impact (Tier 3)
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 7 of 9
402.1.1,
;Ceiling insulation R -value.
R-
; R-_ ;❑Complies ;See the Envelope Assemblies
402.2.1,
i
❑ Wood
; ❑ Wood :❑Does Not table for values.
402.2.2,
402.2.6
i
l
❑ Steel
❑ Steel bNot Observable ;
[Fill'
'
i
;❑Not Applicable
r}�+irs'ot
servable
303.1.1.1, '.Ceiling insulation installed per
!vs.
❑Complies
303.2
;manufacturer's instructions.
❑Does Not
[FI211
:Blown insulation marked every
LJNot Observablet
(j
:300 ft'.
�
❑Not Observable
t -
•
❑Not Applicable
A02.2.3
?Vented attics with air permeable
u 3
❑Complies
(F(2_)z
':'insulation include baffle adjacent
❑Does Not
ElNot Applicable
to soffit and eave vents that
!extends over insulation.
❑Not Observable
❑Not Applicable j
402.2.4
(Attic access hatch and door
R-
; R- I❑Complies '
[FI311
I i insulation aR-value of the
;❑Does Not
adjacent assembly.
❑Not Observable
❑Not Applicable
402.4.1.2 Blower door test @ 50 Pa. <=5
ACH 50 =_
; ACH 50 = ;❑Complies
[FI17)1
iach in Climate Zones 1-2, and
;❑Does Not
<=3 ach in Climate Zones 3-8.❑Not
Observable
❑Nat Applicable
403.2.2
;Duct tightness test result of <=4
cfm/100
cfm/100 '.❑Complies
[FI411
'.cfm/100 ft2 across the system or
ft2
ft'❑Does Not
<=3 cfm/100 ft2 without air❑Not
Observable
,handler @ 25 Pa. For rough -in
:tests, verification may need to❑Not
Applicable
;occur during Framing Inspection.
403.2.2.1 '.Air handler leakage designated❑Complies
[FI24]1
:by manufacturer at <=2% of
❑Does Not
;design air flow.
❑Nat Observable
❑Not Applicable
403.1:1:
Programmable thermostats
❑Complies
I[Fl9f
.: installed on forced air furnaces.
❑Does Not
❑Not Observable
40%14�0-1 Heat pump thermostat Installed
es
otservable
licable■
JCIrculating service hot water a3�`-nr-^"—Cr
_,�Isystems
r G _
have automatic or
r}�+irs'ot
servable
!vs.
licable
_ 1 �
_
i
Does Not
k h .
__ efficacy *> .
HVAC equipment
��l and air flow limits.
LJNot Observablet
,Ii
Not Applicable
5' iG"f.�'�.A.� � +=:�Y�Y ■
�
t -
•
� �a�it2`att.Yrv„3`Y
��K'�fay��b { "n oes Not
!,fixtures have high efficacy lamps W%`�J%ff �Egt$.AF! ee 5
u 3
Does not apply to low -voltage
ONot Observable
!lighting. ;
ElNot Applicable
1 I High Impact (Tier 1) 1, 2 '1 Medium Impact (Tier 2) 3`1 Low Impact (Tier 3)
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 8 of 9
Additional Comments/Assumptions:
1 1 High Impact (Tier 1) 12,-.1 Medium Impact (Tier 2) 13'.1 Low Impact (Tier 3)
Project Title: 675 canyon springs Report date: 02/23/17
Data filename: C:\Users\Angela Byram\AppData\Local\Check\REScheck\675 canyon springs.rck Page 9 of 9
0 2012 IECC Energy
�( Efficiency Certificate
Above -Grade Wall 21.00
Below -Grade Wall 19.00
Floor 0.00
Ceiling / Roof 50.00
Ductwork (unconditioned spaces):
Window 0.30
Door 0.15
Heating System:
Cooling System:,
Water Heater:
Name: Date:
Comments