LOAD SHORT FORM - 17-00105 - 675 Canyon Springs - SFR
wrightsoft' Load Short Form High Country Heating P.O. Box 627, Rigby, I6 83442 Phone: 208-7454056 Fax: 208-745-0817 Email: highcountryph®yahoo.cum Project Information For: Fall Creek Homes 1340 Indian Hollow, Ammon, Id 83406 Job: 675 canyon springs Date: 2123117 By: Vince Plan: Timpanogas ROOM NAME Area (ft') Design Information Htg AVF (cfm) Clg AVF (cfm) Htg CIg Infiltration 1828 Outside db(°F) -6 89 Method Simplified Inside db (°F) 70 75 Construction quality Semi -tight Design TD (°F) 76 14 Fireplaces 0 Daily range - H 41 67 Inside humidity (°/a) 50 50 1254 73 Moisture difference (gr/Ib) 62 -31 819 685 HEATING EQUIPMENT 40 COOLING EQUIPMENT Make Goodman Mfg. 7867 5344 Make Goodman Mfg. 314 Trade GOODMAN 223 1634 Trade GOODMAN, JAN ITROL, AMANA DISTI... Model GMH950703BX 37 Room9 Cond GSX130241D* 1419 AHRI ref 2002183 42 46 Coil CA*F1824*6D* 86 420 6 12 AHRI ref 4700003 Room12 Efficiency 95 AFUE 626 Efficiency 11.0 EER, 13 SEER Heating input 69000 Btuh Sensible cooling 16100 Btuh Heating output 54460 Btuh Latent cooling 6900 Btuh Temperature rise 69 OF Total cooling 23000 Btuh Actual air flow 859 cfm Actual air flow 859 cfm Air flow factor 0.029 cfm/Btuh Air flow factor 0.059 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area (ft') Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (cfm) Room1 335 4255 1828 125 107 Room2 159 2245 726 66 43 Room3 69 852 608 25 36 Room4 118 1387 1142 41 67 Rooms 147 2479 1254 73 74 Room6 58 819 685 24 40 Room7 687 7867 5344 232 314 Room8 223 1634 624 48 37 Room9 201 1419 785 42 46 Room10 86 420 6 12 0 Room12 291 2294 626 68 37 C)... 4m CAL 7All A/, A V+r .11, ,VV+ IVL UV Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. - wrightsoff:• RightSulte® Universal 2017 17.0.10 RBU20477 2D17 -Feb -2316:39:20 Page 1 ...re\FellCreek\Timpanogee\875 canyon eprings.,up Calc=MJe House faces: SW Entire House d 3017 29149 14633 859 859 Other equip loads 5024 925 Equip. @ 0.94 RSM 14625 Latent cooling 0 T Al Q I QA41 I O1990 I .IAC I .cn I nen Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2017 -Feb -2916:99:20 wrightSOM RightSuite® Universal 2017 17.0.10 RSU20477 Page ...reTall Creek\Timpenoges\675 canyon springs.rup Cole =MJ8 House feces: SW wriightsoft Building Analysis High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-7455056 Fax: 20&745,0817 Email: hlghwunlryph@yahoo.wm For: Fall Creek Homes 1340 Indian Hollow, Ammon, Id 83406 Job: 675 canyon springs Date: 2123/17 By: Vince Plan: Timpanogas Component Design Btuh % of load Walls Location: 12234 Indoor: Heating Cooling Idaho Falls, ID, US 22.3 Indoor temperature (°F) 70 75 Elevation: 4741 ft Ceilings Design TD (°F) 76 14 Latitude: 440N 1.5 Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Drybulb(°F) -6 89 Infiltration: 0 Dailyrange °F) - 34 (H ) Method Simplified 0 Wet bulb (° - 60 Construction quality Semi -tight Adjustments Wind speed (mph) 15.0 7.5 Fireplaces 0 34173 100.0 Component Btuh/ft' Btuh % of load Walls 4.1 12234 35.8 Glazing 22.8 7608 22.3 Doors 11.4 718 2.1 Ceilings 1.5 2433 7.1 Floors 1.5 2337 6.8 Infiltration 1.9 3818 11.2 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 5024 14.7 Adjustments 0 Z000 Total 34173 100.0 Cooling Component BtuhA2 Btuh %of load Walls 0.3 766 4.9 Glazing 25.6 8558 55.0 Doors 2.8 175 1.1 Ceilings 0.8 1345 8.6 Floors 0 0 0 Infiltration 0.2 370 2.4 Ducts 0 0 Ventilation 925 5.9 Internal gains 3420 Blower 0 Adjustments 0 Z000 Total 15559 Latent Cooling Load = 0 Btuh Overall U -value =0.051 Btuh/ft'-°F Data entries checked. @ Wrl htsOfL' 2017 -Feb -23 16:39:20 RlghtSulte® Universal 201717.0.10 RSU20477 Page i re\Fall Creek\Timpenagas\675 canyon springs.rup Cala=MJ8 House favus: SW a Component Constructions Job: 675 canyon springs Vlfrlq�ltSflsal ` Date: 2/23117 By: Vince High Country Heating Plan: Timpanogos P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountryph®yahoo.mm Project Information For: Fall Creek Homes 1340 Indian Hollow, Ammon, Id 83406 ]ecinn Cnndifir Location: Indoor: Heating Cooling Idaho Falls, ID, US Indoor temperature (°F) 70 75 Elevation: 4741 ft Area Design TD (°F) 76 14 Latitude: 44°N Clg HTM Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Drybulb(°F) -6 89 Infiltration: Dailyrange (°F) - 34 (H ) Method Simplified Wet bulb(°F) - 60 Construction quality Semi -tight 0.065 Wind speed (mph) 15.0 7.5 Fireplaces 0 173 Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 cell ins, 1/2" 1601 0.020 50.0 1.52 2433 0.84 1345 gypsum board Int finish 2017 -Feb -2316:39:20 wrightSOft' Right -suites Universal 201717.0.10RSU20477 Page ACM reTall Cre9MTlmpanogaM675 canyon springs.rup Cato =MJ8 House faces: SW Construction descriptions Or Area U -value Insul R Htg HTM Loss Clg HTM Gain W BMM'-°F W.'F� BtuhW Btuh Bluhhr Btuh Walls 12F-Osw: Frm wall, wit ext, 3/8" woad shth, r-21 cav ins, 1/2" gypsum ne 365 0.065 21.0 4.94 1802 0.47 173 board int Trish, 2"x6" wood fnn, 16" o.c, stud se 383 0.065 21.0 4.94 1890 0.47 181 Buy 436 0.065 21.0 4.94 2154 0.47 207 nw 400 0.065 21.0 4.94 1976 0.47 190 all 1583 0.065 21.0 4.94 7822 0.47 751 15819-Owc-8: Bg wall, heavy dry or light damp soil, 2"x4" wood int frm, ne 453 0.040 19.0 3.20 1447 0.01 6 concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board Int fnsh se 271 0.040 19.0 3.00 810 0 0 sw 390 0.040 19.0 3.18 1240 0.01 6 nw 291 0.040 19.0 3.15 915 0.01 3 all 1403 0.040 19.0 3.15 4413 0.01 14 Partitions (none) Windows 61C: 61C; 6.67 ft head ht no 139 0.300 0 22.8 3173 23.0 3204 ne 20 0.300 0 22.8 456 23.0 460 as 33 0.300 0 22.8 741 29.3 952 as 40 0.300 0 22.8 912 29.3 1172 sw 47 0.300 0 22.8 1072 29.3 1377 sw 20 0.300 0 22.8 456 29.3 586 nw 15 0.300 0 22.8 342 23.0 345 nw 20 0.300 0 22.8 456 23.0 460 all 334 0.300 0 22.8 7608 25.6 8558 Doors metal: Door, mtl pur core type ne 21 0.150 6.0 11.4 239 2.78 58 sw 42 0.150 6.0 11.4 479 2.78 117 all 63 0.150 6.0 11.4 718 2.78 175 Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 cell ins, 1/2" 1601 0.020 50.0 1.52 2433 0.84 1345 gypsum board Int finish 2017 -Feb -2316:39:20 wrightSOft' Right -suites Universal 201717.0.10RSU20477 Page ACM reTall Cre9MTlmpanogaM675 canyon springs.rup Cato =MJ8 House faces: SW Floors 21A -32c: Bg floor, heavy dry or light damp soil, 8' depth, carpet fir fnsh 1445 0.020 0 1.52 2196 0 0 93 0.020 0 1.52 141 0 0 all 1538 0.020 0 1.52 2337 0 0 2017 -Feb -2316:39:20 WrightSOW RlghtSuite®Universa1201717.0.10RSU20477 Page ...mXFall Creak\Timpenogee\675canyonspdngs.mp Calc=MJ8 Housefeces:SW + w ightsoft• Project Summary High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-7458056 Fax: 208-7450817 Email: highwunbyph@yahoo.mm Promect Information For: Fall Creek Homes 1340 Indian Hollow, Ammon, Id 83406 Notes: Design Information Job: 675 canyon springs Date: 2123/17 By: Vince Plan: Tlmpanogas Weather: Idaho Falls, ID, US Winter Design Conditions Summer Design Conditions Outside db -6 OF Outside db 89 OF Inside db 70 OF Inside db 75 OF Design TO 76 OF Design TD 14 OF Coil CA*F1824*6D* Daily range H Relative humidity 50 % 95 Moisture difference -31 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 29149 Btuh Structure 14633 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent (72 cfm) 5024 Btuh Central vent (72 cfm) 925 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Air flow factor 0.029 cfm/Btuh Equipment load 34173 Btuh Use manufacturer's data n 0.70 in H2O Rate/swing multiplier 0.94 Space thermostat Infiltration Equipment sensible load 14625 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Semi -tight Fireplaces 0 Structure 285 Btuh Ducts 0 Btuh Heating Cooling Area Central vent 72 cfm) -1286 Btuh (fl') 3017 301T Equipment latent load 0 Btuh Volume (4') 17167 17167 Air changes/hour 0.19 0.10 Equipment total load 14625 Btuh Equiv. AVF (cfm) 54 29 Req. total capacity at 0.70 SHR 1.7 ton Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DIST[... Model GMH950703BX Cond GSX130241D* AHRI ref 2002183 Coil CA*F1824*6D* AHRI ref 4700003 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input 69000 Btuh Sensible cooling 16100 Btuh Heating output 54460 Btuh Latent cooling 6900 Btuh Temperature rise 69 OF Total cooling 23000 Btuh Actual air flow 859 cfm Actual air flow 859 cfm Air flow factor 0.029 cfm/Btuh Air flow factor 0.059 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2017-Feb-2316:3920wri 7tOrt` RigMSulte® Universal 201717.0.10 RSU20477 Pagel AM re\Fall CreeklTlmpanogaM675 canyon springs.rup Ceic=MJ8 House faces: SW wrightsoft° AED Assessment High Country Heating P.O. Box 627, Rigby, ld 83442 Phone: 208445-8056 Fax: 208-745-0817 Email: highwuntryph@yahoo.wm For: Location: Idaho Falls, ID, US Elevation: 4741 ft Latitude: 440N Outdoor: Drybulb(°F) Dailyrange (°F) Wet bulb (OF) Wind speed (mph) Fall Creek Homes 1340 Indian Hollow, Ammon, Id 83406 Heating -6 15.0 Cooling 89 34 (H ) 60 7.5 Job: 675 canyon springs Date: 2123/17 By: Vince Plan: Timpanogas Indoor: Heating Ind oortemperature (°F) 70 Design TD (°F) 76 Relative humidity (%) 50 Moisture difference (gr/Ib) 61.5 Infiltration: ♦ � � aw i uormn Maximum hourly glazing load exceeds average by 15.2%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Cooling 75 14 50 -31.5 2017 -Feb -2318:39: Wrlght'o� Rig ht -Su U niversal 201717.0.10 RSU20477 Pagee1 1 ...re\FallCreeklTlmpanogas\875 canyon apnng%.rup Calc=MJB House faces: SW +wrightsoft• Right -A Worksheet High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 20&7458056 Fax: 208-7450817 Email: highccunlryph@yahoo.mm Job: 675 canyon springs Date: 2123117 B : Vince Plan: Timpanogas 1 Room name Entire House Rooml 2 Exposed wall 355.0 8 43.0 8 3 Room height 9.5 it d 10.0 it heal/cool 4 5 Room dimensions Room area 3017.0 ft' 1.0 x 335.0 it 335.0 ft' Ty Construction U -value Or I HTM I Area (ft') I Load I Area (ft-) I Load number (Stuh/ft'--'F � (Btuh/fl') or perimeter r (8) (Btuh) or perimeter (ft) (Btuh) Heat Caol Gross N/P/S Heat Ccol Grass N/P/S Heat Cool 6 4jl 0.085 ne 2 0.47 525 385 1802 235 193 951 FI 61C 0.300 no 2.94 22.80 23.02 139 3173 204 .3204 43 0 989 791 8 978 --DG met metal 0.150 ne ' 11.40 2.78 21 1 21 .238 58 0 0 0 0 Yy 15B19-0wr.-8 0.069 ne 3.20 0.01 473 453 1447 6 0 0 0 0 11 I -G 61C 0.300 ne 22.80 23.02 20 0 456 460 0 0 0 0 W 12F-0aw 0.065 se 4.94 0.47 - .415 383 :1890 .181. 30 30 148 14 L -G 61C 0.300 se 22.80 29.30 33 0 741 952 0 0 0 0 t 15619-0wo-8 0.069 Be 3.00 0.00 311 271 810 0 0 0 0 0 -G 61C 0.300 Be 22.80 29.30 40 0 912 1172 0 0 0 0 12F-0aw 0.065 sw 4.94 0.47 525 436 2154 207. 0 0 0 0 61C 0.300 sw 22.80 28.30 47 0 1072 1377 0 0 0 0 metal. 0.150 sw - 11.40 2.78 42 42 479 117 0 0 0 0 V� 15819-0wo8 0.069 sw 3.18 0.01 410 390 1240 6 0 0 0 0 �f 61C 0.300 sw 22.80 29.30 20 0 456 586 0 0 0 0 t 12F-0sw 0.065 my 4.94 0.47 415 400 .`1876 190 165 165 815 78 -G 61C 0.300 nw 22.80 23.02 75 0 342 345 0 0 0 0 Vy 15B19-owo80.069 nw 3.15 0.01 311 291 915 3 0 0 0 0 �G 61C 0.300 nw 22.80 23.02 20 0 456 460 0 0 0 0 C 16B40ed 0.020 - 1.52 0.84 1801 1601 2433 1345 335. 335 509 281 F 21A -32c 0.020 - 1.52 0.00 1445 1445 2196 0 0 0 0 0 F`.. 21A42c :0.020 - 1.52 0.00 93 93 141 : 0 40 40 61 0 61 c) AED excursion 0-153 Envelope loss/galn 25330 10843 3453 1290 12 a) Infiltration 3818 370 802 78 b) Room ventilation 0 0 0 0 13 Internal gains: Oaupants @ 230 4 920 2 460 Appliances/other 2500 0 Subtotal (lines 6 to 13) 29149 14633 4255 1828 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 14 :0/. 0 0 14 Subtotal 29149 14633 4255 1828 1151 Duct loads 0% 0% 0 0 0 0 mom load298591 148591 41251 182071 Air relquired (dm)1 1 1 1 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -- WrjgIlY947if' 2017 -Feb -2316:38:20 Rig yon apdn U nivera lc= MJ 17Hous RSUs: SW Page 1 ... re\Fall CreeklTimpanogas\675 canyon apnngs.mp Calc=MJB House faoes:SW +wrightsoft Right -M Worksheet High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-7455056 Fax: 208-7450817 Email: highwuntryph@yahoo.mm Job: 675 canyon springs Date: 2123/17 BY: Vince Plan: Timpanogas 1 Roam name Room2 Room3 2 Exposed wall 25.5 it 9.0 6 3 Room height 10.0 n heat/cool 10.0 it heal/cool 4 Room dimensions 1.0 x 159.0 it 1.0 x 68.5 it 5 Room area 159.0 ft' 66.5 fl' Ty Construction U -value OrHTM Area 02) Load I Area (fl') I Load number (Blah/fP--°F (Btuh/fl') or perimeter (it) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool 6 Vy. 12F -0w` 0.065 ne 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 11---00 metal 0.150 ne 11.40 2.78 0 0 0 0 0 0 0 0 W IIBI9-0wcb 0.069 ne 3.20 0.01 0 0 0 0 0 0 0 0 11 L -G 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 Vy 12F-0sw 0.065 $e 4.94 OA7 0 0 0 0 0 0 0 0 I -G 61C 0.300 as 22.80 29.30 0 0 0 0 0 0 0 0 t 15B194wo8 0.069 as 3.00 0.00 0 0 0 0 0 0 0 0 -G 61C 0.300 $a 22.80 29.30 0 0 0 0 0 0 0 0 0.065 sw 4.94 OA7 165 .165 815 78 90 69 341 33 L12F-0sw 61C 0.300 sw 22.80 29.30 0 0 0 0 0 0 0 a metal .0.150 sw 11:40 2.78 0 0 0 0 21 21 239 Be 4jl 15819-0wcb 0.069 sw 3.18 0.01 0 0 0 0 0 0 0 0 -C 81C 0.300 aw 22.80 29.30 0 0 0 0 0 0 0 0 vy 12F-0sw 0.065 nw - 4.94 0.47 90 75 370 36 0 0 0 0 ---G 61C 0.300 nw 22.80. 23.02 15 0 342 345 0 0 0 0 15B19-0wo-8 0.069 nw 3.15 0.01 0 0 0 0 0 0 0 0 BIC 0.300 nw 22.80 23.02 0 0 0 0 0 0 0 0 C 16B50ed 0.020 - 1.52 0.84 159 159 242 134 69 69 104 Be F 21A52c 0.020 - 1.52 0.00 0 0 0 0 0 0 0 0 F 21A -32c 0.020 ':1.52 0.00 0 0 ' 0 0 0 0 0 0 61 c) AED excursion87 57 Envelope loss/gain 1769 680 6 92 12 a) Infiltration 476 46 168 16 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13) 2245 726 852 608 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2245 726 852 608 16 Ductloads -0% 0% 0 0 -0% 0% 0 0 mom load '43I 8251 6361 Air relquired(cfm) I I I 61 I I JCalculations approved by ACCA to meet all reouirements of Manual J 8th Ed. g -Fk- wright9ofY 2017 -Feb -2316:39:20 J&k Rig ht -Su ite® U niv areal 2017 17.0.10 RSU20477 Page ...reTall CreeMTimpenogas1675 canyon spings.mp Calc =We House faces: SW + wrightsofC Right -M Worksheet High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highwuntryph@yahoo.com Job: 675 canyon springs Date: 2123117 By: Vince Plan: Timpanogas 1 Room name Rwm4 RwmS 2 Exposed wall 12.5 It 27.5 It 3 Room height 10.0 It heancool 10.0 8 heattwol 4 5 Room dimensions Room area 1.0 x 118.0 it 118.0 fl' 1.0 x 146.7 0 146.7 ft' Ty Construction U -value Or HTM Area (ft') Load I Area (ft') Load I number (8tuh/ft'-°F (Stuh/ft') or perimeter (6) (Bt h) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Co.[ Gross N/P/S Heat Cool 6 Vy 12F-0sw 0.065 ne 4.94 0.47 0 0 0 0 0 0 0a FL -DG 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 a metal 0.150 no 11.40 2.78 0 0 0 0 0 0 0 0 W 15BI"W" 0.088 no 3.20 0.01 0 0 0 0 0 0 0 0 11 I -G 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 W 12F-0ew . 0.065 so - 4.94 0.47 g . 0 0 0 135 .135 667 64 �G 61C. 0.300 se 22.80 29.30 0 0 0 0 0 0 0 0 t 15B19-0wc-8 0.069 as 3.00 0.00 0 0 0 0 0 0 0 0 -C 61C 0.300 as 22.80 29.30 0 0 0 0 0 0 0 0 Yy 12F-0aw 0.065 sw 4.84 0.47 100 80 395 38 120 100 494 47 61C 0.300 ew 22.80 29.30 20 0 456 586 20 a 456 .586 11 ----DG metal 0.150 sw 11.40 2.78. 0 0 0 0 0 0 0 0 It 15B19-0ow-B 0.069 sw 3.18 0.01 0 0 0 0 0 0 0 0 ---G 61C 0.300 sw 22.80 29.30 0 0 0 0 0 0 0 0 t 12F-Om0.065 nw 4.94 0.47 25 25 123 12 20 20 99 9 -G 61C .0.300. nw 22.80 23.02 0 0 .. 0 0 0 0 0 0 Vy 15B18-0wc8 0.069 nw 3.15 0.01 0 0 0 0 0 0 0 0 �G 61C 0.300 nw 22.80 23.02 0 0 0 0 0 0 0 0 C 16B50ed 0.020 1.52 0.84 118 118 179 99 147 147 223. 123 F 21A -32c 0.020 1.52 0.00 0 0 0 0 0 0 0 0 F 21A -32C , 0,020 - 1.52 .0.00 e 0 0 ' 0 18 18 27 0 61 c) AED excursion i 11!5 144 Envelope loss/gain 1154 680 1986 874 12 a) Infiltration 233 23 513 5D b) Rwmventilation 0 0 0 0 13 Internal gains: Occupants 230 1 230 1230 Appliances/other 0 0 Subtotal (lines 6 to 13) 1387 1142 2479 1254 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1387 1142 2479 1254 1s Ductloads -0% 0% 0 0 -0% 0% 0 0 13411 11671 24731 12541 Air rral equired (dm)I I I I I Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed. g� -Of- wrtghtwaft' Right-Sufted2017-Feb-2316:39:20 .1CGA mnyonspNn Universalalo=201717Hous R8Us:SW Page ...relFall Creek\Timpanogea\675 canyon spdn8s.rup Calc=MJe Housa facea:SW + wrightsoft Right -M Worksheet High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-7464056 Fax: 208-745-0817 Emall: highccuntryph(a)yehco.com Job: 675 canyon springs Date: 2123117 Byy: Vince Ptan: Timpanogos 1 Room name Room6 Room? 2 Exposed wall 5.5 ft 65.0 R 3 Room height 10.0 ft heat/cool 10.0 R heat/coal 4 Room dimensions 1.0 x 57.8 R 1.0 x 687.3 R 5 Room area 57.8 ft' 687.3 ft' Ty Construction U -value Or HTM Area (f t')Load 1 1 Area (f t') 1 Load number j (Btuh/ftLT (Btuh/fl') or perimeter (R) (Btuh) or perimeter (ft) 1 (Btuh) 1 Heat Cool Gross N/P/S Heal Cool Gross N/P/S He Cool 6 4j/ 12F -Om 0.065 ne 4.94. OA7 0 0 0 0 290 172. 851 82 I --G. 61C 0.300 ne 22.80 23.02 0 0 .- 0 0 97 0 2204 2226 I --O metal .0.150 ne 11.40 2.78 0 0 0 0 21 21 239 58 W 15B19-0wc8 0.069 ne 3.20 0.01 0 0 0 0 0 0 0 0 11 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 W 12F-0sw 0.065 as 4.94 OA7 55 ` 35 173 17. .195 : 183 902 87 I -G 61C - 0.300 as 22.80 .29.30 20 0 458 586 13 0 285 368 t 101"W"0.069 as 3.00 0.00 0 0 0 0 0 0 0 0 -G 61C 0,300 as 22.80 29.30 0 0 0 0 0 0 0 0 w 12F-0sw 0.065 sw 4.94 0.47 0 0 0 0 50 22 109 10 1-G 61C 0.300 sw 22.80 29.30 0 0 0 0 7 0 160 205 ll--:::D metal. .0.150 m..11.40 2.78 0 0 0 0 21 21 239 58 Vy 15B19-0wc8 0.069 sw 3.18 0.01 0 0 0 0 0 0 0 0 V --G 61C 0.300 sw 22.80 29.30 0 0 0 0 0 0 0 0 t 12F-0ew 0.065 nw 4.94 0.47 0 0 0 0 115 .115. 568 55 --G 61C .0.300 my 22.80 23.02 0 0 0 0 0 0 0 0 W 15B1g-0wc-8 0.069 nw 3.15 0.01 0 0 0 0 0 0 0 0 �G 61C 0.300 nw 22.80 23.02 0 0 0 0 0 0 0 0 C 16MOad 0.020. 1.52 0.84 58 58 88 49 687 687 1045 577 F 21A -32c 0.020 1.52 0.00 0 0 0 0 0 0 0 0 F 21A -32c '. 0.020 - 1.52 0.00 0 0 0 0 35 _35 53 0 61 c) AED excursion?A 388 Envelope loss/gain 717 675 6655 3227 12 j a) Infiltration 103 10 1212 118 b) Room ventilation 0 0 0 0 19 Internal gains: Occupants @ 230 0 0 0 0 Appllances/other 0 2000 Subtotal (lines 6 to 13) 819 fi85 7867 5344 Less external load a 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 819 685 7867 5344 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 1 ToI mom1 load 1 8241 6401 1 72321 531144] Fur�e9uired (cfm) I 1 1 J . Calculations awroved by ACCA to meet all reauirements of Manual J 8th Ed. g T11- Wrilghtwort' 2017-Feb-23 �ICCA ... R Universal 17RSU2017-Fah-2316:39:20 re\FaIlCresklTimpanogas\675crayonspdnga.rup CalcmMJB Housefaces:SW Page 4 +wrightsoft, Right -M Worksheet High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-746-0817 Email: highwuntryph@yahoo.wm Job: 675 canyon springs Date: 2123117 By:n: Vince Plan: 1 Room name Rooms Rwm9 2 Exposed wall 30.0 0 24.0 it 3 Room height 9.0 it heat/cool 9.0 It heat/cool 4 5 Room dimensions Room area 13.5 x 16.5 It 222.8 fl2 1.0 x 200.5 It 200.5 ft' Ty Construction U -value Or I HTM/ft') I Area (f N) I Lo ed I Area (ft2) Load number (Btuh/ft%*F (Btuh or perimeter (6) (at h) or perimeter (8) 1 (Btuh) 1 Heat Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool 6 Vy 12F-0sw.0.065 ne 4.94 0.47 0 0 0 0 0" 0 0 0 IL -DC 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 metal 0.150 ne 11.40 2.78 0 0 0 0 0 0 0 0 W 1019-0wo-B 0.069 ne 3.20 0.01 0 0 0 0 0 0 0 0 N L -G 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 W 12F-0sw - 0.065 se 4.04 0.47 - 0 0 0 0 0 0 0 0 �O 61C 0.300 as 22.80 29.30 0 0 0 0 0 0 0 0 yy 15B19-0wo8 0.069 as 3.00 0.00 149 129 383 0 0 0 0 0 �-G 61C 0.300 $e 22.80 29.30 20 0 456 586 0 0 0 0 Vy 12F-0sw 0.065 sw .4.94 0.47 0 0 0 0 0 0 0 0 81C 0.300 sw 22.80 29.30 0 0 0 0 0 0 0 0 II ----DG metal 0.150 sw. 11.40 2.78 0 0 0 0 0 0 0 0. VL 15B19-0wc-B 0.069 sw 3.18 0.01 122 122 399 2 117 97 279 0 -G 61C 0.300 sw 22.80 29.30 0 0 0 0 20 0 456 586 t 12F-0sw 0.065 my .4.94 0.47 a 0 0 0 0 0 0 0 -G 61C 0.300 my 22.80. 23.02 0 0 0 0 0 0 0 0 W 15B19-0wa80.069 nw 3.15 0.01 0 0 0 0 99 99 325 2 1--G 61C 0.300 nw 22.80 23.02 0 0 0 0 0 0 0 0 C 16B50ad 0.020 1.52 0.84 1 1 1 1 6 6 9 5 F 21A -32c 0.020 - 1.52 0.00 223 223 339 0 201 201 305 0 IF 21A -32c . 0.020 1.52 0.00. 0 0 0 0 0 0 0 0 61 c) AED excursion 29 188 Envelope loss/gain 1578 618 1374 781 12 a) Intimation 56 5 45 4 b) Rwm ventilation 0 01 10 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1634 624 1419 78s Less external load 0 01 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Su6totel 1634 624 1419 785 1s Ouct loads -0% 0% 0 0 -0% 0% 0 0 1 1 mom load 648 6371 4421 7461 Airrelquird(cfm) 1 1 1 1 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. w,'Ightxs*tt• 2017 -Fal, -z316:39: RightSuite®Unlversa1201717.0.10 RSU20477 Page ...re\Fall Creek\Timpano8as\675 canyon spdngs.rup Calc w Wit House faces: SW Wrlghtsoft' Right -M Worksheet Job: 675 canyon springs Date: 2123117 B: Vince High Country Heating pian: Timpanogas P.O. Box 627, Rigby, Id 83442 Phone: 208-7455056 Fax: 208-745-0817 Email: highwuntryph@yahoo.wm 1 Room name Room10 Rcom12 2 Exposed wall 9.0 8 47.5 8 3 Room height 9.0 6 heaUwol 9.0 R heat/cool 4 Room dimensions 9.0 x 9.5 It 1.0 x 291.0 it 5 Room area 85.5 fP 291.0 ft' Ty Construction U -value Or I H I Area (ft') I Load I Area (ft') I Load number (Btuh/fN-°F (Btuh/ft.) or perimeter (6) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heal Cool 6 Vy 12FSsw - 0.065 ne -4.94 0.47. 0 0 -0 0 0 0 0 0 ` 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 metal 0.150 ne 11.40 2.78 0 0 0 0 0 0. 0 - 0 W i5B195w" 0.069 ne 3.20 0.01 0 0 0 _. 0 126 126 414 3 11 L -G 61C 0.300 ne 22.80 23.02 0 0 0 0 0 0 0 0 V" W 12FSsw - 0.065 se 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.300 ee 22.80 20.30 0 0 0 0 0 0 0 0 t i5B19-0wo-8 0.069 se 3.00 0.00 0 0 0 0 0 0 0 0 -G 61C 0.300 as 22.80 29.30 0 0 0 0 0 0 0 0 12F -Ow 0.065 aw 4.94 0.47 0 0 0 0- 0 0 0 0 6 610 .0.300 ew 22.80 29.30 0 0 - 0 0 0 0 0 0 metal 0.150 sw 11.40 2.78 0 0 0 0 0 0 0 0 y/ 10195wco 0.069 sw 3.18 0.01 81 81 266 2 90 90 296 2 �C 61C 0.300 sw 22.80 29.30 0 0 0 0 0 0 0 0 4y 12FSsw 0.065 my 4.94 0.47 0' 0 0 0: 0 0 0 0 L -C 61C 0.300 my 22.80 23.02 0 0 0 0 0 0 0 0 W 15B195wc5 0.069 nw 3.15 0.01 0 0 0 0 212 192 590 1 61C 0.300 nw 22.80 23.02 0 0 0 0 20 0 456 460 C 16B50ad 1 .0.020 1.52 0.84 5. 5 7 4- 5 5 8 4 F 21A -32c _ 0.020 - 1.52 0.00 86 86 130 0 291 291 442 0 F 21A52c 0.020 - r 1.52 0.00 .. 0 b 0 0 0 0 _ 0 0 8 s).D excursion -1 148 Env elope loss/gain 403 5 2205 617 12 a) Infihreeon 17 2 1 89 9 b) Rwmven81aton 0 0 0 0 13 Internal gains: Occupants @} 230 0 00 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 420 61 1 2294 626 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 SUMotel 420 6 22&F 626 15 DUG loads -0% 0% 0 0 5% 0% 0 0 Are I I I 41 22 6371 qir( uddm) 12 01 I I BI JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. Aft'*0- wrightsofb` 2017 -Feb -2316:39:20 RightSuiteO Universal 2017 17.0.10 RSU20477 Page ...re\Fall CreelATimpanogas1675wnyonspdn9s.mp Calc=MJ8 Housefews:SW +wrlghtsoft• Right@ Worksheet High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highwuntryph@}yahoo.wm Job: 675 canyon springs Date: 2123117 By: Vince Pian: Tlmpanogas 1 Room name Room13 2 Exposed well 56.5 ft 3 Room height 9.0 it heat/cool 4 Rcom dimensions 1.0 x 645.0 ft 5 Raom area 645.0 fP Ty Construction U-valueOr I HTM I Area (fl') I Load I Area I Load number I (Btuh/ft'-°F (Btuh/f P) or perimeter (ft) (Btuh) or perimeter Heat Ccol Gross N/P/S Heat Cool Gross N/P/S Hast Cool 6 Vy 12F-0sw- 0.065 ne 4.94 0.47 0 0 0 0 ~I Bic 0.300 ne 22.80 23.02 0 0 0 ` 0 metal 0.150 no 11:40 2.78 0 0 0 0 -1D3 Vy 15B19-0wc-8 0.069 ne 3.20 0.01 347 327 1033 3 11 L -G at 0.300 ne 22.80 23.02 20 0 456 460 W 12F-0sw 0.065 as 4:94 9.47 0 0 0 0 t -G 61C. 0.300 ae. 22.80 29.30 0 0 0 0 Yy 15B19-0wc-8 0.069 se 3.00 0.00 162 142 427 0 t -G 61C 0.300 as 22.80 29.30 20 0 456 586 yl 12F -Ow 0.065 aw 4.94 0:47 0 0 0 0 IL -DG 61C 0.300 sw 22.80 29.30 0 0 0 0 metal 0.150 sw 11.40 2.78 0 0 0 0 ly 15619-0wc8 0.069 sw 3.18 0.01 0 0 0 0 �C 61C 0.300 sw 22.80 29.30 0 0 0 0 Vy 12F-0sw 0.065 my 4.94 0A7 0 0 0 0 t -C 61C ' 0.300 nw 22.80 23.02 0 0 0 0 W 15B19-0wc-8 0.069 nw 3.15 0.01 0 0 0 0 �G 61C 0.300 nw 22.80 23.02 0 0 0 0 C 16B-50ad 0.020 - 1.52 0.84 13 13 19 10 F 21A -32c 0.020 1.52 0.00 645 645 980 0 F> 21A -32c 0.020 1.52 0.00 0 0 0 "0 61 c)AED excursion -66 Envelope loss/gam 3372 994 12 a) Infiltration 105 10 b) Roomventilation 0 0 13 Internal gains: Occupants@ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 3477 1004 Less external load 0 0 Less transfer 0 0 Rest hibutlon 0 0 14 Sublotal 3477 1004 15 Duct loads -0% 0% 0 0 load 31077 1004 1 I A%l Qulreed 1 1 1 21 91 1 1 Calculations approved by ACOA to meet all reauirements of Manual J 8th Ed. g� � wrighteort' 2017 -Feb -2316:39:20 ,IC:CSA canyon uite®U Universal 2017 17Hous RSUs: SW Page 7 ...re\Fall Creek\Timpanogos\675 canyon springs.mp Calc=MJe House faces: SW main Job M 675 canyon springs Performed by Vince for: Fall Creek Homes 1340 Indian Hollow Ammon, Id 83406 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 highcountryph@yahoo.com Scale: 1 :90 Page 1 RUhtSuite® Universal 2017 17.0.10 RSU20477 2017 -Feb -23 16:39:49 panogas\675 canyon springs.... Basement Job M 675 canyon springs Performed by Vince for: Fall Creek Homes 1340 Indian Hallow Ammon, Id 83406 High Country Heating P.O. Bax 627 Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745.0817 highcountryph@yahoo.com Scale: 1 : 90 Page 2 RightSufte® Universal 2017 17.0.10 RSU20477 2017 -Feb -23 16:39:48 panogas\675 canyon springs.... + wrightsflftDuct System Summary High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208.7450817 Email: highcounlryph@yahoo.com Project For: Fall Creek Homes 1340 Indian Hollow, Ammon, Id 83406 External static pressure Pressurelosses Available static pressure Supply/ return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.70 in H2O 0.35 in H2O 0.35 in H2O 0.172 / 0.178 in H2O 0.070 in/100ft 859 cfm 499 ft Job: 675 canyon springs Date: 2/23117 By: Vince Plan: Timpanogas Cooling 0.70 in H2O 0.35 in H2O 0.35 in H2O 0.172 / 0.178 in H2O 0.070 in/100ft 859 cfm Supply Branch Detail Table Name Design (Btuh) Htg (Cfm) Clg (Cfm) Design FR Diam (in) H x W (in) Duct Mail Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Rooms h 2128 63 54 0.097 6.0 0x0 ShMt 36.0 140.0 st2 Rooms -A h 2128 63 54 0.102 6.0 0x0 ShMt 44.0 125.0 st2B Room10 h 420 12 0 0.106 6.0 0x0 ShMt 12.5 150.0 st2 Room12 h 2294 68 37 0.101 6.0 0x0 ShMt 30.0 140.0 st2A Room13 h 1739 51 29 0.093 6.0 0x0 ShMt 20.0 165.0 all Room13-A h 1739 51 29 0.070 6.0 0x0 ShMt 39.7 205.0 stlB Room2 h 2245 66 43 0.114 6.0 0X0 ShMt 20.5 130.0 st2 Room3 c 608 25 36 0.105 6.0 0X0 ShMt 3.0 160.0 st2 Room4 c 1142 41 67 0.086 6.0 0x0 ShMt 23.5 175.0 stl Rooms c 1254 73 74 0.071 6.0 0x0 ShMt 36.0 205.0 st1A Rooms C 685 24 40 0.072 6.0 0x0 ShMt 23.0 215.0 st1A Room7 C 1336 58 78 0.071 6.0 0x0 ShMt 45.2 195.0 st1A Room7-A C 1336 58 78 0.094 6.0 0x0 ShMt 22.0 160.0 stl Room7-B C 1336 58 78 0.104 6.0 0x0 ShMt 14.5 150.0 stl Room7-C c 1336 58 78 0.101 6.0 0x0 ShMt 30.0 140.0 stl Rooms h 1634 48 37 0.073 6.0 0x0 ShMt 31.5 205.0 stlB Rooms c 785 42 46 0.106 6.0 0X0 ShMt 22.5 140.0 st1 2017 -Feb -2316:39:21 WrightSOW RightSuite® Universal 2017 17.0.10 RSU20477 Pagel ...re\Fall CreeKTimpanogas\675canyonspdngs.mp Calc=MJ8 Houssfaces:SW Supply Trunk Detail Table Name Trunk Type Htg (Cfm) Clg (Cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1B Peak AVF 99 66 0.070 149 6.2 8 x 12 ShtMetl st1A st1A Peak AVF 255 258 0.070 388 8.9 8 x 12 ShtMetl st1 st1 Peak AVF 562 636 0.070 716 12.5 8 x 16 ShtMetl 74 st2 PeakAVF 297 223 0.097 445 8.8 8 x 12 ShtMetl 0x0 st2A PeakAVF 130 90 0.101 195 6.4 8 x 12 ShtMetl st2 st2B Peak AVF 63 54 0.102 94 4.9 8 x 12 ShtMetl st2A Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (dm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 0x0 107 154 146.0 0.122 488 6.6 3.25x14 10x9 SJSp rt1 rb2 0x0 41 67 140.0 0.127 212 4.8 3.25x14 10x9 SJSp rt1A rb3 0x0 73 74 142.5 0.125 233 5.0 3.25x14 10x9 SJSp rt1A rb4 0x0 192 150 254.5 0.070 303 8.0 2-3.25x14 2-10x18 SJSp rt2A rb5 0x0 42 46 85.0 0.210 146 3.8 3.25x14 10x9 SJSp rt1 rb6 Ox 0 289 295 133.0 0.1341 466 8.2 2-3.25x14 2-10x18 SJSp rt2 rb7 0x0 48 37 164.5 0.108 152 4.4 3.25x14 10x9 SJSp rt18 rb8 Ox 0 68 37 179.5 0.099 214 5.0 3.25x14 10x9 SJSp rt26 Return Trunk Detail Table Name Trunk Type Htg (Cfm) Clg (Cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt1B Peak AVF 48 37 0.108 72 4.4 8 x 12 ShtMetl rt1A rt1A Peak AVF 162 177 0.108 266 7.1 8 x 12 ShtMetl rt1 rt1 Peak AVF 311 378 0.108 567 9.4 8 x 12 ShtMetl rt2 Peak AVF 548 481 0.070 616 11.8 8 x 16 ShtMetl rt2A Peak AVF 259 187 0.070 389 8.9 8 x 12 ShtMetl rt2 rt2l3 Peak AVF 68 37 0.099 101 5.0 8 x 12 ShtMetl rt2A 2017 -Feb -23 16:39:21 wrightSOW RigMSuile@ U niversal 2017 17.0.10 RSU20477 Page ... Weal[ CreekRimpanogas\676 canyon springs.mp Cale =MJ8 House faces: SW