LOAD SHORT FORM - 17-00181 - 826 S 2275 W - SFR
+g Load Short Form Job: SF2B8 wri htsoft Date: 3/7/17 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, IG 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcauntryph@yahoo.mm Project Information For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 ROOM NAME Area (ft2) Htg load (Btuh) InformationDesign Htg AVF (cfm) Clg AVF (Cfm) Htg Clg Infiltration 135 Outside db (°F) -6 89 Method Simplified Inside db (°F) 70 75 Construction quality Semi -tight Design TD (°F) 76 14 Fireplaces 0 Daily range - H 83 111 Inside humidity (%) 50 50 1225 52 Moisture difference (gr/Ib) 62 -31 2190 1928 HEATING EQUIPMENT 119 COOLING EQUIPMENT Make Goodman Mfg. 2290 373 Make Goodman Mfg. 23 Trade GOODMAN 23 627 Trade GOODMAN; JANITROL; AMANA DIST[... Model GMSS920603BN 3 Room8 Cond GSX130301B 18316 AHRI ref 7367472 470 384 Coil CAPF3030N6D AHRI ref 6497552 Efficiency 92.1 AFUE Efficiency 11.3 EER, 13.5 SEER Heating input 60000 Btuh Sensible cooling 19600 Btuh Heating output 55000 Btuh Latent cooling 8400 Btuh Temperature rise 64 °F Total cooling 28000 Btuh Actual air flow 933 cfm Actual air flow 933 cfm Air flow factor 0.026 cfm/Btuh Air flow factor 0.062 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heal ratio 1.00 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (Cfm) Room10 50 912 135 23 8 Roomll 50 98 55 3 3 Room9 121 2857 1589 73 98 Rooni 245 3252 1802 83 111 Room15 42 2025 1225 52 75 Rooml4 138 2190 1928 56 119 Rooml3 96 2290 373 59 23 Room7 23 627 45 16 3 Room8 709 18316 6238 470 384 ,wv,,, 1r_ GGJ .1 .V I/IJ Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. WrightsOft' Rig ht -Su ite® U niversal 2017 17.0.10 RSU20477 ...Angela Byram\Documents\wrightsoftware\SF2BB.mp Calc =10,18 House Front faces: NW 09 2017 -Mar -07 07:52:12 Page 1 Entire House d 1697 36352 15165 933 933 Other equip loads 10132 768 Equip. @ 0.94 RSM 14977 Latent cooling 0 TnTAI A I 4907 I eceoe Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft' Right -Suite® Universal 201Paage717.0.10 RSU20477 2017 -Mar -07 2 ...Angela Byram\Documents\wrighlsoflware\SF2B0.mp Calc = MJB House Front faces: NW - wrlghtsoft° Building Analysis De r7117 zes Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 2087458056 Fax: 208-7450817 Email: highceuntryph@yahoo.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Heating Component Design Conditions % of load Walls Location: 11073 Indoor: Heating Cooling Idaho Falls, ID, US 12.9 Indoor temperature (°F) 70 75 Elevation: 4741 ft Ceilings Design TD (T) 76 14 Latitude: 44°N 3.9 Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Dry bulb (T) -6 89 Infiltration: 0 Dailyrange (°F) - 34 (H ) Method Simplified 12.8 Mtbulb(°F) - 60 Construction quality Semi -tight Adjustments Wind speed (mph) 15.0 7.5 Fireplaces 0 Heating Component Btu N1112 Btuh % of load Walls 4.9 11073 23.8 Glazing 24.3 5993 12.9 Doors 12.9 543 1.2 Ceilings 1.5 1468 3.2 Floors 3.9 3808 8.2 Infiltration 2.0 5164 11.1 Ducts 8303 17.9 Piping 0 0 Humidification 5961 12.8 Ventilation 4171 9.0 Adjustments 0 Total 46484 100.0 Cooling Component Btuh/ft2 Btuh % of load Walls 0.5 1064 6.7 Glazing 31.1 7654 48.0 Doors 3.1 132 0.8 Ceilings 0.8 811 5.1 Floors 0.1 83 0.5 Infiltration 0.2 512 3.2 Ducts 4909 30.8 Ventilation 768 4.8 Internal gains 0 0 Blower 0 0 Adjustments 0 Total 15933 100.0 Latent Cooling Load = 0 Btuh Overall U -value =0.068 Btuh/ft' °F Data entries checked. wri htsof , 2017 -Mar -0707:52:12 g Right -Suite® U nlversal 201717.0.10 RSU20477 Pagel ...Angela Byram\Documents\wdghtsoftware\SF2B8.mp Calc= MJ8 House Front faces: NW Component Constructions Job: SF2B8 wrightsoft p Date: 3/7/17 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, Io 83442 Phone: 2M7458056 Fax: 208-745-0817 Email: highwunlryph@yahoo.com Project For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 7)esinn Conditir Location: 0.065 Indoor: Heating Cooling Idaho Falls, ID, US 266 Indoor temperature (°F) 70 75 Elevation: 4741 ft 2747 Design TD (°F) 76 14 Latitude: 44°N 22.0 Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Dry bulb (T) -6 89 Infiltration: all 2242 0.065 Dailyrange (°F) - 34 ( H ) Method Simplified 1064 V�ktbulb(T) - 60 Construction quality Semi -tight 543 Wind speed (mph) 15.0 7.5 Fireplaces 0 50.0 Construction descriptions Or Area U -value Insult R Htg HTM Loss Cig HTM Gain M ahhR'--°F W- Fiats B4hN Btuh Bul„W etuh Walls Fran wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 7k6" wood firm, 16" o.c. stud: Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 61 C: 61 C; 6.67 ft head ht Doors metal: Door, mill pur core type Ceilings 168-50ad: Attic ceiling, asphalt shingles roof mat, r-50 cell ins, 1/2" gypsum board Int fnsh Floors 19A-30bscp: Pan floor, carpet flr fnsh, r-30 ins, firm fir, 12" thkns, 1/2" gypsum board int fnsh 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge Ins, carpet flr fnsh n 561 0.065 22.0 4.94 2771 0.47 266 e 556 0.065 22.0 4.94 2747 0.47 264 s 531 0.065 22.0 4.94 2625 0.47 252 w 593 0.065 22.0 4.94 2930 0.47 281 all 2242 0.065 22.0 4.94 11073 0.47 1064 n 4 0.320 0 24.3 97 10.4 41 e 144 0.320 0 24.3 3502 33.5 4822 s 34 0.320 0 24.3 817 18.4 619 w 65 0.320 0 24.3 1577 33.5 2171 all 246 0.320 0 24.3 5993 31.1 7654 w 42 0.170 10.5 12.9 543 3.14 132 966 0.020 50.0 1.52 1468 0.84 811 208 0.034 30.0 2.17 451 0.40 83 122 0.355 10.0 27.0 3292 0 0 2 0.355 10.0 27.0 66 0 0 all 124 0.355 10.0 27.0 3357 0 0 2017 -Mar -0707:52:12 4 - WrightsOft' Rig ht-SuiteOUniversal201717.0.10RSU20477 Page l ... Angela Byram\Documenls\wdghtsoftware\SF288.mp Calc=MJ8 House Front faces: NW wrightsoft Project Summary Date: 31727178 Entire House ey: Vinceeyrom High Country Heating P.O. Box 627, Rigby, ld 83442 Phone: 208-745-8056 Fax: 208-7450617 Email: highcounlryph@yahoo.com Promect Information For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Desim Information Make Goodman Mfg. Trade GOODMAN Idaho Falls, ID, US Trade GOODMAN; JANITROL; AMANA DISTI... Winter Design Conditions Summer Design Conditions Outside db -6 OF Outside db 89 OF Inside db 70 OF Inside db 75 OF Design TD 76 OF Design TD 14 OF Efficiency 92.1 Daily range H Heating input 60000 Relative humidity 50 % Btuh Heating output Moisture difference -31 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 28049 Btuh Structure 10256 Btuh Ducts 8303 Btuh Ducts 4909 Btuh Central vent (59 cfm) 4171 Stuh Central vent (59 cfm) 768 Btuh Humidification 5961 Btuh Blower 0 Btuh Piping 0 Btuh in H2O Space thermostat Equipment load 46484 Btuh Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load 14977 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Semi -tight Fireplaces 0 Structure -712 Btuh Ducts -108 Btuh Heating Cooling Central vent (59 cfm) -1068 Btuh Area (fts) 1697 1697 Equipment latent load 0 Btuh Volume (ftp 16968 16968 Air changes/hour 0.26 0.14 Equipment total load 14977 Btuh Equiv. AVF (cfm) 74 40 Req. total capacity at 0.70 SHR 1.8 ton Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS920603BN Cord GSX130301B AHRI ref 7367472 Coil CAPF3030N6D AHRI ref 6497552 Efficiency 92.1 AFUE Efficiency 11.3 EER, 13.5 SEER Heating input 60000 Btuh Sensible cooling 19600 Btuh Heating output 55000 Btuh Latent cooling 8400 Btuh Temperature rise 64 OF Total cooling 28000 Btuh Actual air flow 933 cfm Actual air flow 933 cfm Air flow factor 0.026 cfm/Btuh Air flow factor 0.062 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Wrl htsoft 2017 -Mar -0707:52:12 9 Right -Suite® Universal 201717.0.10 RSU20477 Page 7 +� ...Angela Byram\Documentslwrightsoftware\SF2B8.mp Calc = MJ8 House Front faces: NW [•. AED Assessment Job: SF2B8 Wilg�lt$Q1 ` Date: 3/7/17 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, ld 83442 Phone: 208-7468056 Fax: 208-745-0817 Email highcounlryph@yahoo com Project Information For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 ••..0 l+,x a M. w o0 i neo ems Maximum hourly glazing load exceeds average by 9.6%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh 2017 -Mar -07 07:52:12 (C Wr'IghtSOft Right-Suite®Umversal20171Z0.10RSU20477 Page Ha l ...Angela Byram\Documents\wrightsonwame SF2B8.rup Calc = MJ8 House Front (acesNW Design Location: Indoor: Heating Cooling Idaho Falls, ID, US Indoor temperature (°F) 70 75 Elevation: 4741 ft Design TD (T) 76 14 Latitude: 44'N Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Dry bulb (T) -6 89 Infiltration: Dailyrange (T) - 34 (H ) Wet bulb (T) - 60 Wind speed (mph) 15.0 7.5 ••..0 l+,x a M. w o0 i neo ems Maximum hourly glazing load exceeds average by 9.6%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh 2017 -Mar -07 07:52:12 (C Wr'IghtSOft Right-Suite®Umversal20171Z0.10RSU20477 Page Ha l ...Angela Byram\Documents\wrightsonwame SF2B8.rup Calc = MJ8 House Front (acesNW wrightsoft, Right -M Worksheet Job: SF288 Entire House Date: 317/17 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 83442 Phone: 208-7458056 Fax: 208-745.0817 Email: highcountryph@Jyahoo.com 1 Room name Entire House Room10 2 Exposed wall 253.0 ft 9.0 It 3 Room height 10.0 It d 10.0 it heat/cool 4 5 Room dimensions Room area 1696.8 fP 9.0 x 5.5 It 49.5 fP Ty Construction U -value Or HrM Area (it-) Load Area (f P) I Load I number (Btuh/fl'-°F (Btuh/fly or pedmeter (ft) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross WP/S Heal Cool 6 lq! Fmi wall, vnl ext, 3 0.065 n 4.94 0.47 565 561 2771 266 0 0 0 0 L -G 61C 0.320 n 24.32 10.37 4 0 97 41 0 0 0 0 IN Fr n wall, vnl end, 3 0.065 a 4.94 0.47 700 556 2747 264 90 90 445 43 L -G 81C 0.320 a 24.32 33.49 144 0 3502 4822 0 0 0 0 11 IN Frm wall, vnl ext, 3 0.065 s 4.94 0.47 565 531 2625 252 0 0 0 0 �G 61C 0.320 s 24.32 18.43 34 0 817 619 0 0 0 0 Franwall, vnl ext, 3 0.065 w 4.94 0.47 700 593 2930 281 0 0 0 0 61C 0.320 w 24.32 33.49 65 0 1577 2171 0 0 0 0 metal 0.170 w 12.92 3.14 42 42 543 132 0 0 0 0 C 16B-50ad 0.020 - 1.52 0.84 966 966 1468 811 50 50 75 42 F 19A-30bscp 0.034 - 2.17 0.40 208 208 451 83 0 0 0 0 F 228-10cpm 0.355 26.98 0.00 731 122 3292 0 0 0 0 0 F 228.10cpm 0.355 - 26.98 0.00 27 2 66 0 0 0 0 0 61 c)AED excursion 0 -01 Envelope losstgain 22884 9744 520 73 12 a) Infiltration 5164 512 184 18 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants 230 0 0 0 0 Appliances/olher 0 0 Subtotal (lines 6 to 13) 28049 10256 704 91 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 28049 10256 704 91 15 Duct loads 30% 48% 8303 4909 30% 48% 208 44 Total room load 36352 15165 912 135 Airrequired(cfm) 933 933 23 6 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. $. � wrightsoft' 2017 -Mar -0707:52:12 Rig ht -Suite® U niversal 2017 17.0.10 RSU20477 Page 1 ...Angela Byram\Documents\wdghtsofWare\SF2BB.mp Calc=MJB House Front faces: NW ++ Wrightsof , Right -M Worksheet Job: SF2B8 Entire House Date: 3/7/17 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcounuyph@yahoo.mm 1 Room name Roomll Room9 2 Exposed wall 0 ft 22.0 ft 3 Room height 10.0 ft heal/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 9.0 x 5.5 ft 49.5 ft' 11.0 x 11.0 ft Ty Construction LLvalue Or HTM I Area (W) I Load Area (W) I Load number (Btuh/fl;°F (Bluh/ftp or perimeter (ft) (Bum) or perimeter (ft) (Btuh) Heal Cool Gross WP/S Heat Cool Groes WP/S Heal Cool 6 Yr/ Frm wall, vnl ext, 3 0.065 n 4.94 0.47 0 0 0 0 0 0 0 0 elC 0.320 n 24.32 10.37 0 0 0 0 0 0 0 0 V Frm wall, vnl ext, 3 0.065 a 4.94 0.47 0 0 0 0 11 65 420 40 �G61C 0.320 a 24.32 33.49 0 0 0 0 25 0 608 837 11 Yt/ Frm wall, vnl ext, 3 0.065 s 4.94 0.47 0 0 0 0 11 11 543 52 �G 61C 0.320 a 24.32 18.43 0 0 0 0 0 0 0 0 Fran wall, vni ext, 3 0.065 w 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.320 w 24.32 33.49 0 0 0 0 0 0 0 0 metal 0.170 w 12.92 3.14 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 50 50 75 42 121 121 184 102 F 19A.30bsco 0.034 - 2.17 0.40 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 - 26.98 0.00 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 26.98 0.00 0 0 0 0 0 0 0 0 6c)AED excursion -4 -p Envelope loss/gain 75 37 1755 1030 12 a) Infiltration 0 0 449 45 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants C 230 0 0 0 1 0 Appliances/other 0 0 Subtotal (lines 61013) 75 37 1 2204 1074 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 75 37 2204 1074 15 Duct loads 30% 48% 22 18 30% 48% 653 514 Tolal oad 98 55 2857 1589 Air re=(dM) 3 3 73 98 Calculations aooroved by ACCA to meet all reauirements of Manual J 8th Ed. Wright®oft- Right -Suite® U niversal 2017 17.0A0 RSU20477 2017 -Mar -0707:52:12 ...Angela Byram\Documents\wdghtsoftware\SF268.mp Calc =MJ8 House Front faces: NW Paget +wrightsoft• Right -M Worksheet Job: SF2B8 Entire House Data: 317/17 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 83442 Phone: 208-7458056 Fax: 208-745-0817 Email: highcauntryph@yahoo.com 1 Room name Room17 Roam15 2 Exposed wall 22.5 ft 16.0 fl 3 Room height 10.0 it heat/cool 10.0 tt heaVcool 4 Room dimensions 1.0 x 244.5 it 1.0 x 42.0 it 5 Room area 244.5 ft2 42.0 f2 Ty Construction U -value Or HTM Area (f t2) Load Area (W) I Load number (Btuh/ft%'F j (Btuh/ft� or perimeter (tt) (Bluh) or perimeter (n) (Btuh) Heal Cool Gross WP/S Heat Cool Grass WP/S Heal Cool 6 YtJ Fria wall, vnl ext, 3 0.065 n 4.94 0.47 0 0 0 0 35 35 173 17 I -G 61C 0.320 n 24.32 10.37 0 0 0 0 0 0 0 0 Fnn wall, vnl ext, 3 0.065 a 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.320 a 24.32 33.49 0 0 0 0 0 0 0 0 11 Vrl Film wall. vnl ext, 3 0.065 s 4.94 0.47 150 142 703 67 45 45 222 21 �C 61C 0.320 s 24.32 18.43 8 0 188 143 0 0 0 0 Film wall, vnl ext, 3 0.065 w 4.94 0.47 75 57 281 27 80 65 321 31 F --G 81C 0.320 w 24.32 33.49 18 0 440 606 15 0 365 502 �D metal 0.170 w 12.92 3.14 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 - 1.52 0.84 245 245 372 205 42 42 64 35 F 19A-30bscp 0.034 2.17 0.40 0 0 0 0 42 42 91 17 F 22B-10cpm 0.355 26.98 0.00 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 - 26.98 0.00 27 2 66 0 0 0 0 0 fi c)AED excursion 125 173 Envelope loss/gain 2050 117 1236 798 12 a) Infiltration 459 46 327 32 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2509 1218 1563 828 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2509 1218 1563 828 15 Duct loads 30% 48% 743 583 30% 48% 463 396 mom load 32831 1801 20521 12751 Airtrequlred (dm)I I II I I Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed. WrlghteoR' Right -Suite® U niversal 2017 17.0.10 RSU20477 2017 -Mar -07 07:52 Aft -pkPa3 ...Angela Byram\Documents\wdghlsoftwamkSF2BB,wp Cale =MJ8 House Front faces: NW Page +{+wrightsoft, Right -JO Worksheet Job: SF268 Entire House Date: 3/7/17 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 83442 Phone: 20&745-8056 Fax: 208-745-0817 Email: highcountryph@yahoo.com 1 Room name Rooml4 Room13 2 Exposed wall 11.5 It 20.0 fl 3 Room height 10.0 It heat/cool 10.0 It heaVcool 4 Room dimensions 11.5 x 12.0 It 8.0 x 12.0 it 5 Room area 138.0 fP 96.0 ft2 Ty Construction U -value Or HTM I Area (fl2) Load I Area (f12) Load number (Bt uh/ft2-°F (Blah/fly or perimeter (8) (Blah) or perimeter (R) (Btuh) Heat Cool Grass WP/S HealCool Gross WP/S Heal Cool 6 l5J I'm wall, vnl ext, 3 0.065 n 4.94 0.47 0 0 0 0 120 11 573 55 L -G 61C 0.320 n 24.32 10.37 0 0 0 0 4 0 97 41 I'm wall, vnl ext, 3 0.065 a 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.320 a 24.32 33.49 0 0 0 0 0 0 0 0 11 IN Fnn wall, vnl ext, 3 0.065 s 4.94 0.47 0 0 0 0 0 0 0 0 �G 61 C 0.320 a 24.32 18.43 0 0 0 0 0 0 0 0 Fan wall, vnl ext, 3 0.065 w 4.94 0.47 115 91 450 43 80 80 395 38 61C 0.320 w 24.32 33.49 24 0 584 804 0 0 0 0 metal 0.170 w 12.92 3.14 0 0 0 0 0 0 0 0 C 1615-50ad 0.020 - 1.52 0.84 138 138 210 116 98 96 146 81 F 19A-30bscp 0.034 2.17 0.40 98 98 212 39 68 68 147 27 F 22B-10cpm 0.355 26.98 0.00 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 26.98 0.00 0 0 0 0 0 0 0 0 61 c)AED excursion 219-301 Envelope loss/gain 1455 1281 1359 212 12 a) Infiltration 235 23 408 40 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6/013) 1690 1304 1787 252 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1690 1304 1767 252 15 Duct loads 30% 48% 500 624 30% 48% 523 121 oad 27561 1928 22591 373 Ax�equued (cfin) I I 1191 I I 231 Calculations aooroved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft Right -Suite® Universal 2017 17.0.10 RSU20477 2017 -Mar -0707:52:12 ...Angela Byram\Documents\wdghlsoflware\SF2BB.mp Cale =MJB House Front faces: NW Page4 wrightsoft, Right -JO Worksheet Jeb: SF2B8 Entire House Date: 3/7/17 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 63442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcountfyph@yahoo.com 1 Room name Room7 RoomB 2 Exposed wall 5.0 ft 117.0 It 3 Room height 10.0 ft heal/cool 10.0 It heat/cool 4 5 Room dimensions Room area 5.0 x 4.5 ft 22.5 ft' 1.0 x 708.8 It 708.8 ft' Ty Construction U -value Or HTM Area (f P) Load Area (it-) Load number (Btuh/ft;°F (Bt uh/f t) or perimeter (ft) (Btuh) or perimeter (ft) (Stuh) Heel C001 Gross WP/S Heal Cool Gross WP/S Heal Cool 6 Yt/ Fml wall, vat ext, 3 0.065 n 4.94 0.47 0 0 0 0 260 260 1284 123 �-G 61C 0.320 n 24.32 10.37 0 0 0 0 0 0 0 0 t Fan wall, vn1 ext, 3 0.065 a 4.94 0.47 0 0 0 0 350 256 1265 121 --G 61C 0.320 a 24.32 33.49 0 0 0 0 94 0 2286 3148 11 YN Frm wall, vnl ext, 3 0.065 s 4.94 0.47 0 0 0 0 260 234 1157 111 �G 61C 0.320 s 24.32 18.43 0 0 0 0 26 0 628 476 Frm wall, vn1 eat, 3 0.065 w 4.94 0.47 50 50 247 24 300 250 1236 119 61C 0.320 w 24.32 33.49 0 0 0 0 8 0 188 260 metal 0.170 w 12.92 3.14 0 0 0 0 42 42 543 132 C 16MOad 0.020 - 1.52 0.84 0 0 0 0 0 0 0 0 F 19A-30bsco 0.034 2.17 0.40 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 26.98 0.00 23 5 135 0 709 117 3157 0 F 22B-10cpm 0.355 - 26.98 0.00 0 0 0 0 0 0 0 0 6i c)AED excursion -4 -508 Envelope loss/gain 382 20 11744 3982 12 a) Infiltration 102 10 2388 237 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants a 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 484 30 14132 4219 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 484 30 14132 4219 15 Duct loads 30% 48% 143 14 30% 48% 4184 2019 Toul1 oad6161 1 1 431 784701 23 63841 Air requiretll(cfm) 1 Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed. Aft, r' wriahtsaft' 2017 -Mar -0707:52:12 AGCA Rig hl-Suite®Universal 201717.0.10 RSU20477 Page 5 ...Angela Byram\Documents\wdghtsoftware\SF2BB.mp Cale =MJ8 House Front faces: NW wrightsoR° Right -J® Worksheet Job: SF2B8 Entire House Date: 3/7117 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highmuntryph@yahoo.com 1 Room name Rooml2 2 Exposed wall 30.0 ft 3 Room height 10.0 ft heat/coot 4 5 Room dimensions Room area 15.0 x 15.0 ft 225.0 fl° Ty Construction U -value Or HTM Area (fl') Load I Area I Load number (Btuh/fl;°F (Btuh/ftp or perimeter (ft) (Bluh) or perimeter Heat Cool Gross W Heat Cool Gross NIP/5 Heat Caol 6 y/ �G Fm wall, vnl ext, 3 0.065 n 4.94 0.47 150 150 741 71 61C 0.320 n 24.32 10.37 0 0 0 0 Fnn wall, vni ext, 3 0.065 a 4.94 0.47 150 125 617 59 67C 0.320 a 24.32 33.49 25 0 608 837 17 IN Firm wall, vnl ext, 3 0.065 a 4.94 0.47 0 0 0 0 t -G 61C 0.320 3 24.32 18.43 0 0 0 0 Firm wall, vni ext, 3 0.065 w 4.94 0.47 0 0 0 0 61C 0.320 w 24.32 33.49 0 0 0 0 metal 0.170 w 12.92 3.14 0 0 0 0 C 1613-50ad 0.020 - 1.52 0.84 225 225 342 189 F 19A,30bsco 0.034 - 2.17 0.40 0 0 0 0 F 22EW0cpm 0.355 26.98 0.00 0 0 0 0 F 22B-10cpm 0.355 - 26.98 0.00 0 0 0 0 a! c)AED excursion.77 Envelope loss/gain 2308 1140 12 a) Infiltration 612 61 b) Room ventilation 0 0 13 Internal gains: Occupants® 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 2921 1201 external load 0 0 Less transfer 0 0 [Less Redistribution 0 0 14 Subtotal 2921 1201 Duct loads 30% 48% 865 575 Total room load 37861775 Air required (cfm) 97 109 Calculations aooroved by ACCA to meet all reauirements of Manual J 8th Ed. -rk- wrigM1teoR' ...Rightl 171RSU20477 2017 -Mar -0707:52:12 Angela Byram\Documents\wrightsoftware\SF2B8.mp Cale =Me House Front faces :NW Page Main Job #: SF2138 Performed by Vince Byram for: Cady Puiey 3758 Yelloweenes Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 highcou ntryph@yahoo. oom Scale: 1 : 58 Page 1 Right-SuiteO Universal 2017 17.0.10 RSU20477 2017 -Mar -07 07:52:45 .cu ments\wrightsoftware\S F2 Be. ru p 55 cfm 0 Room12 179 cfm K 55 cfm RoomU 11 cfm 0\ 59 cfm Job M SF2138 Performed by Vince Byram for: Cody Pozey 3758 Vellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 2nd Story K\ 23 cfm Room10 ff— 3 fm Room14 I; Room11 I173 cfm X14 cfm 111 cfm C?MM 15 cm High Country Heating P.O. Box 627 Rigby, Id 83442 Phone'. 208-745-8056 Fax 208-745-0817 highcountryph@yahoo.com 1\ 98 cfm Room9 OTOM I Scale: 1 :58 Page 2 Right -Su iba Universa 12017 17.0.10 RSU20477 2017 -Mar -07 07:52:45 .. cuments\wrig htsoftware\S F2B8. rup +I+ wrightsoft Duct System Summary Entire House High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highwuntryph@yahoo.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.70 in H2O 0.36 in H2O 0.34 in H2O 0.178 / 0.162 in H2O 0.078 in/100ft 933 cfm 438 Job: SF2B8 Date: 3/7/17 By: Vince Byram Cooling 0.70 in H2O 0.36 in H2O 0.34 in H2O 0.178 / 0.162 in H2O 0.078 in/100ft 933 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Room10 h 912 23 8 0.099 6.0 0x0 ShMt 20.0 160.0 st2 Room11 c 55 3 3 0.099 6.0 0x0 ShMt 14.0 165.0 st2 Room12 c 888 49 55 0.084 6.0 0x0 ShMt 21.0 190.0 stl Room12-A c 888 49 55 0.078 6.0 0x0 ShMt 28.5 200.0 stl Room13 h 2290 59 23 0.082 6.0 0x0 ShMt 26.0 190.0 stl Room14 C 1928 56 119 0.095 6.0 0x0 ShMt 12.0 175.0 stl Room15 C 1225 52 75 0.093 6.0 0x0 ShMt 15.0 175.0 st2 Room17 C 1802 83 111 0.094 6.0 0x0 ShMt 9.0 180.0 st2 Room7 h 627 16 3 0.106 6.0 0x0 ShMt 7.5 160.0 stl Room8 h 3053 78 64 0.113 6.0 0x0 ShMt 21.5 135.0 st2 Room8-A h 3053 78 64 0.095 6.0 0x0 ShMt 7.5 180.0 st2 Room8-B h 3053 78 64 0.099 6.0 0x0 ShMt 24.5 155.0 st2 Room8-C h 3053 78 64 0.098 6.0 0X0 ShMt 27.0 155.0 stl RoomsD h 3053 78 64 0.105 6.0 0x0 ShMt 14.0 155.0 sill Room8-E h 3053 78 64 0.094 6.0 0x0 ShMt 18.5 170.0 st1 Rooms c 1589 73 98 0.107 6.0 0x0 ShMt 25.5 140.0 st2 wrightSOft' Right -Suite® Unhiersal 2017 17.0.10 RSU20477 ..Angela Byram\Documentsk dghtsoftware\SF2BB.mp Calc=MJ8 House Front faces: NW 2017 -Mar -07 07:52:12 Page 1 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk W Peak AVF 470 488 0.093 732 10.7 8 x 12 ShtMetl stl Peak AVF 463 446 0.078 695 10.9 8 x 12 ShtMetl wrightSOft' Right -Suite® Unhiersal 2017 17.0.10 RSU20477 ..Angela Byram\Documentsk dghtsoftware\SF2BB.mp Calc=MJ8 House Front faces: NW 2017 -Mar -07 07:52:12 Page 1 Return Branch Detail Table Return Trunk Detail Table Grille Htg CIg TEL Design Veloc Diam H x W Stud/Joist Duct Type Name Size (in) (dm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Mall Trunk rb13 0x0 125 173 192.0 0.085 274 7.4 2-3.25x14 2-10x18 SJSp rt1 rb12 0x0 86 114 87.5 0.186 362 5.4 3.25x14 10x9 SJSp PH rb10 Ox 0 486 387 62.5 0.260 770 8.7 2-3.25x14 2-10x18 SJSp rb14 0x0 179 141 133.5 0.122 568 7.0 3.25x14 10x9 SJSp rt2 rbll 0x0 56 119 209.0 0.078 376 6.5 3.25x14 10x9 SJSp rt2 Return Trunk Detail Table 2017 -Mar -0707:52:12 wrightsoft Right -Suite® Universal 2017 17.0.10 RSU20477 Paget ...Angela Byram\Documents\wrighlsoflware\SF288.mp Calc=MJB House Front faces: NW Trunk Htg CIg Design Veloc Diam H x W Duct Name Type (cfm) (Cfm) FR (fpm) (in) (in) Material Trunk PH Peak AVF 211 287 0.085 739 8.9 8 x 7 ShlMetl rt2 Peak AVF 236 259 0.078 778 8.7 8 x 6 ShtMetl 2017 -Mar -0707:52:12 wrightsoft Right -Suite® Universal 2017 17.0.10 RSU20477 Paget ...Angela Byram\Documents\wrighlsoflware\SF288.mp Calc=MJB House Front faces: NW