07/14/2017N/ADon AllenMechanical Inspector Consultation
Building Inspection Type
Plastic pipe penetrations into rated walls must maintain fire rating. Some have
fire stop wrap without collars nor is it in the annular space.
Inspector Comments:
1/2" drywall appears to be on separation wall between upper floor bathrooms
(removed electrical cover to check thickness). Other separation walls are 5/8"
thick but could not verify type x.
Inspector Comments:
Metal pipe penetrating separation wall in basement needs to be fire caulked to
maintain rating.
Inspector Comments:
Dropped soffit in south basement unit needs to be fire rated.Inspector Comments:
No fire rating done under bathroom sink in basement.Inspector Comments:
Fire separation is not completed on ceiling or wall in furnace closet of main level
south unit.
Inspector Comments:
Sprinkler system is required in a 6-plex.Inspector Comments:
South unit bedroom in basement must have an emergency egress window (or
door) to the outside.
Inspector Comments:
Last approval was a remodel into a 3-plex (basement, main, & upper level units).
Converted at some point to a 6-plex without permit. Division of the upstairs into
two units would require ceilings to be 1 hour rated. How many layers of 5/8" type
x drywall is on ceiling of upper units? (2 required)
Inspector Comments:
12/15/2016NONCOMPLYQuinton OwensBuilding Inspector Consultation
This review is for building code only (not reviewed here for other codes or P&Z
requirements).
Inspector Comments:
Electrical Inspection Type
07/14/2017N/ABret StoddardElectrical Inspector Consultation
Plumbing Inspection Type
07/14/2017N/ADon AllenPlumbing Inspector Consultation