HomeMy WebLinkAboutRESCHECK - 16-00552 - 1071 Washington Blvd - New SFRfZREScheck Software Version 4.6.2
Compliance Certificate
Project F52B3 - Charlotte
Energy Lode:
20121ECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Orientation:
Bldg. faces 270 deg. from North
Conditioned Floor Area:
3,045 ft2
Glazing Area
19%
Climate Zone:
6 (8693 HDD)
Permit Date:
Permit Number:
Construction Site:
Owner/Agent:
Rexburg, ID 83440
Designer/Contractor:
Kartchner Homes
84321
435-755-7080
john@kartchnerhomes.com
Compliance: Passes using UA trade-off
Compliance: 2.3% Better Than Code Maximum UA: 259 Your UA: 253
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Ceiling 1: Flat Ceiling or Scissor Truss
Main Wall Front: Wood Frame, 16" o.c.
Orientation: Front
Window 4: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Front
Door 1: Solid
Orientation: Front
Main Wall Right: Wood Frame, 16" D.C.
Orientation: Right side
Main Wall Rear: Wood Frame, 16" o.c.
Orientation: Back
Window 5: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Back
Main Wall Left: Wood Frame, 16" o.c.
Orientation: Left side
Basement Wall Front: Solid Concrete or Masonry
Orientation: Front
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 6: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Front
Project Title: FS283 -Charlotte
Data filename: C:\Users\jhoel lei n\Documents\REScheck\FS2B3.rck
1,536 50.0
504 21.0
50
40
0.0 0.026
40
0.0 0.057
24
0.320
16
0.010
0
252 21.0 0.0
432 21.0 0.0
Rom
0.057 14
0.057 18
0.320 36
212 21.0 0.0 0.057 12
504 0.0 13.0 0.047 23
25 0.320 8
Report date: 07/20/16
Page 1 of 9
Basement Wall Right: Solid Concrete or Masonry 252 0.0 13.0 0.047 12
Orientation: Right side
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Basement Wall Rear: Solid Concrete or Masonry 416 0.0 13.0 0.047 17
Orientation: Back
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 7: Vinyl/Fiberglass Frame:Triple Pane 60 0.320 19
Orientation: Back
Basement Wall Left: Solid Concrete or Masonry 196 0.0 13.0 0,047 8
Orientation: Left side
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 8: Vinyl/Fiberglass Frame:Double Pane with Low -E 20 0.320 6
Orientation: Left side
Compliance Statement., The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in
REScheck Version 4.6.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
-Title Signature Date.
Project Notes:
Founder Square Subd
Block: 3, Lot: 2
Rexburg, ID 83440
Project Title: FS283 - Charlotte Report date: 07/20/16
Data filename: C:\UsersUhoe] lein\Documents\REScheck\FS2B3.rck Page 2 of 9
CREScheck Software Version 4.6.2
ID( Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
& Req;ID
Pre-inspection/Plan
-
Verified Field Verified
Valde' � Value
Complies? Comments/Assumptions
103.1,
(Construction drawings and
❑Complies
103.2
(documentation demonstrate.
k,Jr :�=
❑Does Not I
[PRI]'
:energy code compliance for the&-
+
J= 'i,
I
❑Not Observable
011
;building envelope.-
,,;'
❑Not Applicable
103.1.
;Construction drawings and
]''�
❑Complies
103 2,
'documentation demonstrate
lenergy
❑Does Not
403.7
code compliance for
/
"t "�,: '.
❑Not Observable
[PR311
lighting and mechanical systems
r s
�i, a¢
g
:Systems serving multiple
.'
' "i<
<
❑Not Applicable j
;dwelling units must demonstrate
I compliance with the IECC
Y
(Commercial Provisions.
3023,
-.,Heating and cooling equipment is!
Heating:
Heating:
❑Complies
403.6
i sized per ACCA Manual S based
Btu/hr
Btu/hr_❑Does
Not
[PR2]2
:on loads calculated per ACCA
Cooling:
Cooling:
Observable
q
Manual J or other methods❑Not
;approved by
Btu/hr
Btu/hr_❑Not
'cable
Applicable
the code official.
r
pp
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: FS283 - Charlotte Report date: 07/20/16
Data filename: C:\Users\ hoellei n\Documents\REScheck\FS2B3.rck Page 3 of 9
Section
#
Foundation inspection
Plans Verified Field Verified
Value-
Complies? Comments/Assumptions.
& Req.ID
.Value
402.1.1
Conditioned basement wall
R- R-
;❑Complies ; See the envelope Assemblies
[F0411
:insulation R-value. Where interior;
R R_
!❑Does Not ;table for values.
'1
insulation is used, verification
;❑Not Observable
;may need to occur during
Insulation Inspection. Not❑Not
Applicable
:required in warm-humid locations!
:in Climate Zone 3.
3032
[F0511
;Conditioned basement wall`"'�rN
l insulation installed pers�
< +° ,.
� �, , , �
Us .'�+
❑Complies
❑Does Not
instructions.
y
manufacturer's
�' tt
❑Not Observable '
❑Not Applicable
402.2.8.
;Conditioned basement wall
I ft I ft❑Complies
I See the Envelope Assemblies
[FO611
!insulation depth of burial or
I
❑Does Not ;table for values.
;distance from top of wall.
❑Not Observable;
,
❑Not Applicable
303 2.1
'A protective covering is installed
,<1' F"
" []Complies
[FO1112
Ito protect exposed exterior,vr
;insulation and extends a
3'AMVu "+ {
'��
❑Does Not
.minimum of 6 in. below rade.
g
a f ° r +�"
❑Not Observable
-�
❑Nat Applicable j
403.$
[F012p
;Snow- and ice-melting system
;controls installed.
A zw'y"' ; ;r ;t
❑Complies
❑Does Not
y��r w
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 JHlgh Impact (Tier 1) 1,2 1 Medium Impact (Tier 2) ::3 ILow Impact (Tier 3)
Project Title: FS2B3 - Charlotte Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2B3.rck Page 4 of 9
Section
#
Framing /Rough -In Inspection
Plans Verified Field Verified
Value .Value Complies? Comments/Assumptions
402.1.1,
'Door U -factor.
j U-_ U -_❑Complies See the Envelope Assemblies
402.3.4❑Does
Not table for values.
[FRl]1
;❑Not Observable
❑Not Applicable
402.1.1,
;Glazing U-factor(area-weighted
; U-_ U- ;❑Complies ;See the Envelope Assemblies
402.3.1,
laverage).❑Does
Not table for values.
402.3.3,
402.3.6,❑Not
Observable
402.5
;❑Not Applicable
[FR2]1
303.1.3
U -factors of fenestration products
�t,'��>,r� z`' kin❑Complies
[FR4]1
:are determined in accordance
❑Does Not
,J
:with the NFRC test procedure or
taken from the default table
. ❑Not Observable
❑Not Applicable
402.4.1.1
'Air barrier and thermal barrier❑Complies
[FR23]1
:installed per manufacturers
❑Does Not
;instructions.
„
❑Not Observable
i
❑Not Applicable
402.4.3.
Fenestration that is not site built
f �
T��rw°'�C ❑Complies
[FR20]
is listed and labeled as meeting
❑Does Not
V
AAMA /WDMA/CSA 101/I.S 2/A440
2 ' °*_
fir^„'
;or has infiltration rates per NFRC
❑Not Observable
F +
{rF;; ❑Not Applicable
,400 that do not exceedode
limits..
4024.4
{ IC -rated recessed lighting fixtures
° ''`{ z jasy ,A �" t ❑Complies
[FR16]1
aealed at housing/interior finish
;and labeled indicate
f„,"-`rn x a :Sr ❑Does Not
to
❑Not Observable
leakage at 75 Pa.
h�� 7-'�' , _ , a
❑Not Applicable
1rg1:,./r,]'7a;`,�kti
403.2.1
;Supply ducts in attics are
R-_ R -❑Complies
[FR12]1
; insulated to >_R-8. All other ducts
R_ R,❑Does Not
U
inunconditioned spaces or
,'outside the building envelope are
;❑Not Observable
❑Not Applicable
insulated to aR-6.
403.2.2
[FR1311
IAII joints and seams of air ducts,
'air handlers, and filter boxes are
sealed.
t,f} »� t� s °�'',/FKI`` • . ❑Complies
, ° ❑
aap,t {'� ' "rye Does Not
d;
lif rr� f e + []Not Observable;
❑Not Applicable
'4Q3.2.3
[FR15]a
!Building cavities are not used as
{ ducts
t,'' ti�r�1 a ❑Complies
� ❑Does
or plenums.
ak �, �'� yr s''; Not
y,w
❑Not Observable ;
❑Not Applicable
4033
a HVAC piping conveying fluids
; R- R -_❑Complies
[FR1712
!above 105 QF or chilled fluids
❑Does Not
below 55 QF are insulated to aR-
i
I❑Not Observable
I3
❑Not Applicable
403.3.1
[FR2411
:Protection of insulation on HVAC
piping.
.,r,,py ' ❑Complies
" , ❑Does Not
❑Not Observable
a f' ❑Not Applicable
403.42 ,
!Hot water pipes are insulated to
1 R-_ R- ;❑Complies
[FR18]2
II>_R-3.❑Does
Not
❑Not Observable
;❑Not Applicable
111 High Impact (Tier 1) 12`J Medium Impact (Tier 2) 1 1 3'I Low Impact (Tier 3)
Project Title: FS2B3 - Charlotte Report dater 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2B3.rck Page 5 of 9
'Section IPlans
#
Framing /Rough -In Inspection
Verified
Value,.
Field -Verified
.:Value
Complies? Com::�nts/Assumptlonr
& Req ID
403.5Automatic
or gravity dampers are
, "� „ "
; . +m ""`' +'
❑Complies
[FRlgj2
installed on all outdoor
intakes and exhausts.
*
[]Does Not
v,
�)
❑NotObservable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 12`1 Medium Impact (Tier 2) 13 Low Impact (Tier 3)
Project Title: FS2B3 - Charlotte Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2B3.rck Page 6 of 9
Section
#
'&
-
Insulation Inspection
Plans Verified Field Verified
Value Value
Complies? Comments/Assumptions'.
RegAD
303.1
'All installed insulation is labeled
f ' �` " , �, ? '[?j;
❑Complies
[1N131�
:orthe installed R -values
t
❑Does Not
u
provided.
a i'
❑Not Observable
❑Not Applicable
402.1.1,
Wall insulation R -value. If this is a R-_ R -_❑Complies
;See the envelope Assemblies
402.2.5,
; mass wall with at least 'A of the
❑Wood ; E]Wood
:❑Does Not ;table for values.
402.2.6
;wall insulation on the wall
:exterior,
❑ Mass ❑ mass❑Not
Observable
[IN311
the exterior insulation
i requirement applies (FR10).
❑ Steel E] Steel❑Not
Applicable
303.2
I Wall insulation is installed per'��i'(❑Complies
[IN411
;manufacturer's instructions.
t1' d a
❑Does Not
❑Not Observable
❑Not Applicable j
Additional Comments/Assumptions:
111 High Impact (Tier 1) :2 Medium Impact (Tier 2) 1. 3'1 Low Impact (Tier 3)
Project Title: FS2B3 - Charlotte Report date: 07/20/16
Data filename: C:\Users\jhoe] lei n\Documents\REScheck\FS2B3.rck Page 7 of 9
Section
#
-
Final Inspection Provisions
Plans Verified Field Verified
Value - Value Complies? Comments/Assumptions'
&,Req.ID
402.1.1,
1 Ceiling insulation R -value.
R- R -❑Complies ; See the Envelope Assemblies
402.2.1,
j ❑ Wood ; ❑ Wood❑Does Not I table for values.
402.2.2•
402.2.6❑Not
El Steel ❑ Steel ;❑Not Observable
[Fill'
I
Applicable
303.1.1.1,
303 2
Ceiling insulation installed per
imanufacturer's instructions❑Does
�ra ; " . ❑Complies
Not
�n�'�,.yf
[FI2]1
j Blown insulation marked every
!300
t. e M x
wv`�'"' Observable;
ft'.
ti❑Not
'r.,.. f'L Applicable
„.,la<.�'u; ^j ,-�¢sad�❑Not
402.2.3
fj Vented attics with air permeable
❑Complies
[F1221x`
=insulation include baffle adjacent
: ' i sj' • �`” 4 ",❑Does Not
'
jto soffit and eave vents that
insulation.*=❑Not
r' . r`extends Observable
IE]Not
over
Applicable
402.2.4
;,Attic access hatch and door
R-_ R -_❑Complies
[FI311
:insulation >_R -value of the❑Does
Not
adjacent assembly.
❑Not Observable
❑Not Applicable
402.4.1.2
'Blower door test @ 50 Pa. <=5
ACH 50 =_ 1 ACH 50 =_❑Complies
[FI17]1
ach in Climate Zones 1-2, and❑Does
Not
J
<=3 ach in Climate Zones 3-8.
;❑Not Observable
❑Not Applicable
403.2.2
Duct tightness test result of <-4
; cfm/100 cfm/100 ;❑Complies
[FI411
cfm/100 ft2 across the system or
1 ft' ; ft2 ❑Does Not
<=3 cfm/100 ft2 without air
j❑Not Observable
1 handler @ 25 Pa. For rough -in
!tests, verification may need to
;❑Not Applicable
occur during Framing Inspection.
403.2.2.1
;Air handler leakage designated
4; 'd't` 1;❑Complies
[F12411
1 by manufacturer at <=2% of
ht t11%
`= i ❑Does Not
;design air flow.
,
F '° !U ❑Not Observable
�_; n+t, ❑Not Applicable
403.1..1
[FI9]2
]Programmable thermostats
installed on forced air furnaces.
a;x r'=£ ❑Complies
, ` ' ��,, ❑Does Not
❑Not Observable
r. • € ❑Not Applicable
403:1,2
Heat pump thermostat installed
c �t• ❑Complies
P�si
[FI10]2
on heat pumps.
" " `="1 ��;f`¢= a ❑Does Not
l�
z
MUM111 `1 "' s `4, ❑Not Observable
,,„p.,, ,],tkF •- e „ ❑Not Applicable
403.44
j Circulating service hot water
[systems have
�'_`��`�TU�i.,2' .,`'`-�' ❑Complies
r=`t. El
[FI11]2.
automatic or
accessible manual controls
r ;µ1K+,r`=e'+''sr Not
ff
#)
., �� [ - , ti =❑Not Observable
❑Not Applicable
403.5.1
t.,h,
; All mechanical ventilation system
its r fes,... = sz❑Complies
r
T ,'a ,,, � `��k
[FI25]3
fans not part of tested and listed
€'tl ,❑Does Not
HVAC equipment meet efficacy;,,h
p Observable
;and air flow limits.
h,c ,; : 1❑Not
Applicable
„z, ?❑Not
]
175% of lamps in permanent
fixtures or 75 /a of permanent
0fixtures
]"�s" ; '❑Complies
s„ ,' ° ❑Does Not1
[01"4.1
have high efficacy lamps.
; .1
Does to low
' �.# 4 c, ❑Not Observable
not apply -voltage
1
Applicable
alighting.
`��"t<:,, ''[ ,,..=❑Not
111 High Impact (Tier 1) 12::1 Medium Impact (Tier 2) [l3-:1 Low Impact (Tier 3)
Project Title: FS2B3 - Charlotte Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2B3.rck Page 8 of 9
Section
#
Final Inspection Provisions,
Plans Verified Field Verified
Value Value ' Compiles? Comments/Assumpt]ons
.Re .ID
404.,1 -
iFuel gas lighting systems have
NOW ° �, ❑Complies
[FI237a
a no continuous pilot light.
�,.. [�� ' 4 ° ;-r,(`w �;.rir ❑Does Not
rk x ❑NotObservable
❑Not Applicable
401.3
Compliance certificate posted.
" ❑Complies ,
`
[FI7]�
d, ❑Does Not
❑Not Observable
licable
❑Not Applicable
3'03 3
Manufacturer manuals for
�"'� yig'r"�r� "�"" p ❑Complies
�'".�
[FIlf3)a `
mechanical and water heating
,� ti� tir a ` y�?.fi'w ,p'f''ry` w [--]Does Not
.11EINot
.:systems
have been provided°r
�p�,T'eas ;[
❑Not Observable
:Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2d Medium Impact (Tier 2): 3.[1 Low Impact (Tier 3)
Project Title: FS2133 - Charlotte Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2 B3.rck Page 9 of 9
2012 IECC Energy
Efficiency Certificate
Above -Grade Wall
Below -Grade Wall
Floor
Ceiling / Roof
Ductwork (unconditioned spaces):
13.00
0.00
50.00
Window 0.32
Door 0.01
CoolingHeating &
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments