Project Number: U2001-0643-171
February 14, 2017
Blue Raven Solar, LLC
1220 S. 630 E., Suite 430
American Fork, UT 84003
ATTENTION: Scott Gurney
REFERENCE: David Peck Residence: 323 South 3rd East, Rexburg, ID 83440
Solar Panel Installation
Dear Mr. Gurney:
Per your request, we have reviewed the attached layout relating to the installation of solar panels at the above-
referenced site. The following materials and components are proposed in the installation of the solar panels.
Roof Structure: 2x4 Manufactured trusses @ 18 in O.C.
Roof Material: Composite/Asphalt Shingles
Based upon our review, it is our conclusion that the installation of solar panels on th e existing roof will not adversely
affect the structure of this house. The design of supporting members and connections is by the manufacturer and/or
installer. The adopted building code in this jurisdiction is the 2012 International Building Code and ASCE 7-10.
Appropriate design parameters which must be used in the design of the supporting members and connections are listed
below:
Ground snow load: 50 psf per Utah amendments to the IBC (verify with local building department)
Design wind speed for risk category II structures: 115 mph (3-sec gust)
Wind exposure: Category C
Our conclusion regarding the adequacy of the existing roof is based on the fact that the additional weight of the solar
panels is less than 3 pounds per square foot. In the area of the solar panels, no 20 psf live loads will be present .
Regarding snow loads, it is our conclusion that since the panels are slippery and dark, effective snow loads will likely
be reduced in the areas of the panels. Regarding wind loads, we conclude that any additional forces will be negligible
due to the low profile of the flush-mounted panel system. Regarding seismic loads, we conclude that any additional
forces will be small. With an assumed roof dead load of 15 psf, solar panel dead load of 3 psf, and affected roof area of
40% (maximum), the additional dead load (and consequential seismic load) will be 9.4%. This calculation
conservatively neglects the weight of wall dead load. Because the increase is less than 10%, this alteration meets the
requirements of the exception in Section 3403.4 of the 2012 International Existing Building Code. Thus the existing
structure is permitted to remain unaltered.
During design and installation, particular attention must be paid to the maximum allowable spacing of attachments and
the location of solar panels relative to roof edges. The use of solar panel support span tables provided by the
manufacturer is allowed only where the building type, site conditions, and solar panel configuration match the
description of the span tables. Attachments to existing roof trusses or rafters must be staggered so as not to overload
any existing structural member. Waterproofing around the roof penetrations is the responsibility of others. Electrical
engineering is beyond our scope. All work performed must be in accordance with accepted industry-wide methods and
applicable safety standards. Vector Structural Engineering assumes no responsibility for improper installation of the
solar panels.
Please note that a representative of Vector Structural Engineering has not physically observed the roof framing of this
home. Our conclusions are based upon the assumption that all structural roof components and other supporting
elements are in good condition and are sized and spaced such that they can resist standard roof loads.
Very truly yours,
VECTOR STRUCTURAL ENGINEERING, LLC
Wells L. Holmes, P.E.
Project Manager
Firm License No.: C2269
WLH/wsp Enclosures 02/14/2017
JOB NO.:U2001-0643-171
PROJECT:DAVID PECK (28071144) RESIDENCE SUBJECT:WIND PRESSURE
Label:Note: Calculations per ASCE 7-10
SITE-SPECIFIC WIND PARAMETERS:
Basic Wind Speed [mph]:115 Notes:
Exposure Category:C
Risk Category:II
Importance Factor, I:
ADDITIONAL INPUT & CALCULATIONS:
Height of roof, h [ft]:15 (Approximate)
Comp/Cladding Location:
Enclosure Classification:
Zone 1 GCp:0.9 Figure 30.4-2B (enter largest abs. value)
Zone 2 GCp:1.7 (enter largest abs. value)
Zone 3 GCp:2.6 (enter largest abs. value)
α:9.5 Table 26.9-1
zg [ft]:900 Table 26.9-1
Kh:0.849 Table 30.3-1
Kzt:1 Equation 26.8-1
Kd:0.85 Table 26.6-1
Velocity Pressure, qh [psf]:24.4 Equation 30.3-1
GCpi:0 Table 26.11-1 (largest abs. value)
OUTPUT:
Zone 1 Pressure, p [psf]:21.99 psf (1.0W, Interior Zones*)
Zone 2 Pressure, p [psf]:41.53 psf (1.0W, End Zones*)
Zone 3 Pressure, p [psf]:63.52 psf (1.0W, Corner Zones* within a)
(*a=assumed=3')
Solar Panel Array
Gable/Hip Roofs 7° < θ ≤ 27°
Enclosed Buildings
Components and Cladding Wind Calculations
piphGCGCqp
VECTOR STRUCTURAL ENGINEERS
JOB NO.:U2001-0643-171
PROJECT:DAVID PECK (28071144) RESIDENCE SUBJECT:CONNECTION CAPACITY
Lag Screw Connection
Capacity:Demand:
Lag Screw Size:5/16
Cd:1.6
Embedment:2.5 in
Grade:
Capacity:205 lbs/in. emb.Zone 1:13.2 4 12 158
Number of Screws:1 Zone 2:24.9 4 12 299
Total Capacity:820 lbs Zone 3:38.1 4 12 457
Demand< Capacity:CONNECTION OKAY
SPF (G = 0.42)
Pressure
(0.6 Wind)
(psf)
Max
Spacing
(ft)
Max. Trib.
Area
(ft2)
Max. Uplift
Force (lbs)
VECTOR STRUCTURAL ENGINEERS
JOB NO.:U2001-0643-171
PROJECT:DAVID PECK (28071144) RESIDENCE SUBJECT:GRAVITY LOADS
CALCULATE ESTIMATED GRAVITY LOADS
DEAD LOAD (D)
Increase due to
pitch
Original
loading
Roof Pitch/12 3.9
Composite/Asphalt Shingles 4.2 1.05 4.00 psf
1/2" Plywood 1.1 1.05 1.00 psf
Framing 3.0 psf
Insulation 0.8 psf
1/2" Gypsum Clg.2.2 psf
M, E & Misc 1.5 psf
DL 12.8 psf
PV Array DL 3.0 psf
ROOF LIVE LOAD (Lr)
Existing Design Roof Live Load [psf]20 ASCE 7-10, Table 4-1
Roof Live Load With PV Array [psf]0 2015 IBC, Section 1607.12.5
SNOW LOAD (S):Existing With PV Array
Roof Slope (:12):3.9
Roof Slope [°]:18
Snow Ground Load, pg [psf]:50 ASCE 7-10, Section 7.2
Terrain Category:C ASCE 7-10, Table 7-2
Exposure of Roof:Fully Exposed ASCE 7-10, Table 7-2
Exposure Factor, Ce:0.9 ASCE 7-10, Table 7-2
Thermal Factor, Ct:1.1 ASCE 7-10, Table 7-3
Risk Category:II ASCE 7-10, Table 1.5-1
Importance Factor, IS:1.0 ASCE 7-10, Table 1.5-2
Flat Roof Snow Load, pf [psf]:35 ASCE 7-10, Equation 7.3-1
Minimum Roof Snow Load, pm [psf]:0 ASCE 7-10, Section 7.3.4
Unobstructed Slippery Surface?Yes ASCE 7-10, Section 7.4
Slope Factor Figure:Figure 7-2b ASCE 7-10, Section 7.4
Roof Slope Factor, Cs:0.867 ASCE 7-10, Figure 7-2
Sloped Roof Snow Load, ps [psf]:30 ASCE 7-10, Equation 7.4-1
Design Snow Load, S [psf]:30
1.000
35
35
3.9
18
50
C
Fully Exposed
0.9
1.1
II
1.0
35
0
No
Figure 7-2b
JOB NO.:U2001-0643-171
PROJECT:DAVID PECK (28071144) RESIDENCE SUBJECT:LOAD COMPARISON
Summary of Loads
Existing With PV Array
D [psf]13 16
Lr [psf]20 0
S [psf]35 30
Maximum Gravity Loads:
Existing With PV Array
D + Lr [psf]33 16 ASCE 7-10, Section 2.4.1
D + S [psf]47 46 ASCE 7-10, Section 2.4.1
Maximum Gravity Load [psf]:47 46
Ratio Proposed Loading to Current Loading:96.6%OK
The gravity loads in the area of the solar panels are decreased; thus, the stresses
of the structural elements are decreased. Therefore, the requirements of Section
3403.3 of the 2012 IBC are met and the structure is permitted to remain
unaltered.