HomeMy WebLinkAboutINSPECTION SUMMARY - 14-00532 - 621 Eaglewood Dr - SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 06/30/2017 11:23 am
Permit Details Permit Number: 14-00532
621 Eaglewood Dr. - SFR
621 Eaglewood Dr.
Building - Single Family Residence
Permit Issued Date: 12/04/2014
Permit Inspection Statistics
23Total Inspections Completed:
17Total Inspections Passed:
Inspection Pass Rate
73.91%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
12/22/2014FailTed DyeResidential Footing Inspection
complete items then call back for re-inspectInspector Comments:
12/23/2014PassTed DyeCommercial Footing Inspection
01/07/2015PassTed DyeFoundation Inspection
02/26/2015FailTed DyeSheeting
Those area's where the sheeting missed being nailed to the studs is marked with
green paint.
Will check for corrections when the framing inspection is done.
Inspector Comments:
03/10/2015FailTed DyeResidential Framing/Structure Inspection
03/12/2015PassTed DyeResidential Framing/Structure Inspection
03/13/2015PassTed DyeResidential Insulation Inspection
03/26/2015FailTed DyeCommercial Sheetrock/Drywall Inspection
03/27/2015PassTed DyeCommercial Sheetrock/Drywall Inspection
05/07/2015PassTed DyeSidewalk Inspection
05/12/2015PassTed DyeSheeting
Sheeting re-inspection was done with the framing inspection.Inspector Comments:
05/12/2015FailTed DyeResidential Building Final
05/14/2015PassTed DyeResidential Building Final
Electrical Inspection Type
03/10/2015PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/10/2015PassBret StoddardResidential Electrical Service Inspection
05/12/2015PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Page 1 of 2
(Continued)
Permit Details Permit Number: 14-00532
621 Eaglewood Dr. - SFR
621 Eaglewood Dr.
Building - Single Family Residence
Permit Status of (Open) as of Report Date: 06/30/2017 11:23 am
Permit
Inspection
Summary
Mechanical Inspection Type
03/05/2015PassQuinton OwensGas Pressure Test
03/05/2015FailQuinton OwensHVAC Rough-in
Ducts penetrating into garage must be 26 ga. min.Inspector Comments:
03/12/2015PassDon AllenHVAC Rough-in
All good to cover the mechanical roughinInspector Comments:
05/12/2015PassDon AllenHVAC Final Inspection
COOG FOR THE C/O
BASEMENT IS NOT FINISHED
Inspector Comments:
Plumbing Inspection Type
01/21/2015PassDon AllenPlumbing Underground Inspection
plumbing underground is all good to cover.Inspector Comments:
01/22/2015PassDon AllenPlumbing Sewer
All good to cover the sewer line.Inspector Comments:
03/05/2015PassPLL ADMINPlumbing Rough-in
Signed by Brian HillInspector Comments:
05/12/2015PassDon AllenPlumbing Final Inspection