HomeMy WebLinkAboutBUILDING 2 REVIEW - 03-00051 - Teton River Village Building #2 - 3 Units�RFXBUgC edy P.O. Box 280 o 01exI(//l/�/o, Ury 12 North Center Street a - » Rexburg, Idaho 83440 ° e Phone (208) 359-3020 �T9e<ISHEO 1$ STATE OF IDAHO e-mail Fax (208) 3 9-3022g.id.us www.d. rexbu rg. id. us 8/18/2003 Ken Harris 3520 North University Avenue Suite #200 Provo, Utah 84604 Dear Ken, I have reviewed the drawings for building #2 of the Teton River Village and have identified the following deficiencies: 1. Provide a handicap parking space adjacent to building #2. The closest handicap parking spaces are located across a vehicle access aisle. 2. Please provide a Flood Elevation Certificate as required in the 2000 International Building Code (IBC) Section 1612.5. 3. A soil investigation report that was conducted for the Jack -In -The Box restaurant (located on the same piece of property) identified a layer of fill mixed with garbage covering the building lot. Please provide us with a soils report for any areas where new footings are to be placed. Will you be excavating to remove these materials? Where footings are to be placed on structural fill, please provide a report as per the 2000 IBC Section 1803.4. 4. The plans identify that the mechanical, plumbing and electrical shall be "design build". Will the mechanical system require roof top units? If so, the mechanical roof unit weights need to be included in the structural design. Mechanical and electrical component placement must meet the design criteria of the 2000 IBC Section 1621. When components are identified, please supply the necessary information as per the 2000 IBC Section 1621.3.5. 5. The plans and specifications identify special inspections required for masonry, field welding, bolting and structural fill. The concrete is identified as 3000 psi and therefore should also be inspected by special inspectors. We need to meet with the inspection company representative to go over special inspections prior to construction. 6. The energy calculations that have been provided are for the Idaho Falls area. Our climate zone is different than Idaho Falls. The energy calculations should be for climate zone 16 of the 2000 International Energy Conservation Code. When the mechanical and electrical design is complete, another set of calculations will be required for the systems. We need envelope compliance plans a.s.a.p. 7. The Fire Department has reviewed the plans. I have attached a copy of the report. Please provide the necessary information they have requested. These items need to be addressed before issuance of a building permit. Please let me know if you have any questions. I can be reached during the day at 359-3020 Ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson OF UPC �C oQ c`— o Ql�y a A ��T4eUSHE� 1� STATE OF IDAHO REXBURG-MADISON COUNTY EMERGENCY SERVICES 26 NORTH CENTER STREET P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359.3020 Fax(208)359-3022 e-mail rexburg@srv.net REXBURG, IDAHO 83440 208-359-3010 208-359-3006 FAX 2000 International Fire Code Plan Date: 7-8-03 Plan Review Review Date: 8-6-03 Building Name: TETON RIVER VILLAGE, BUILDING #2 Building Address: SECOND EAST, REXBURG, IDAHO Stories: ONE Type of Construction: V-A Occupancy Classification: M Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 4797 TOTAL SQ. FEET 1. Required Fire Flow (Appendix B): 1,500 GPM/TWO HOURS Comments: REQUIRED FIRE FLOW MAY BE REDUCED WHEN BUILDING IS EQUIPPED WITH AUTOMATIC FIRE SPRINKLER SYSTEMS. 2. Water Supply (Section 508, Appendix C) Required: YES Fire Hydrant Location: EXISTING ON 2vn EAST (O"DELL'S) Fire Hydrant Flows: EXISTING OK, PROPOSED UNKNOWN Fire Flow Test Location: SECOND EAST Fire Flow Supplied By: FD 8. Ventilating hood and duct fire extinguisher system (Section 609) required: Type being provided: Automatic fuel shut-off required: Portable fire extinguisher shown: Comments: 9. Fire alarm systems (Section 907) required: YES Type of system required: Manual: Automatic: Both: X Type of system being provided: Manual: Automatic: Both: Components of system shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: 1. NO, PLANS NOT SUBMITTED FOR ALARM SYSTEM. SUBMITTALS SHALL INCLUDE LOCATIONS OF ALARM -INITIATING AND NOTIFICATION APPLIANCES; ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS, MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND MATIERIALS, AND INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. 2. NO PLANS SUBMITTED FOR FIRE SPRINKLER SYSTEM. 3. SITE PLAN FOR THIS PROJECT STILL NOT ADEQUATE, PLEASE SUBMIT A NEW SITE PLAN. 10. Other corrections that are required by special occupancy or conditions: SEE ALL PREVIOUS COMMENTS Plans as submitted are acceptable: NO Plans checked by: CHRIS HUSKINSON Date: 8-6-03 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: X 8. Ventilating hood and duct fire extinguisher system (Section 609) required: Type being provided: Automatic fuel shut-off required: Portable fire extinguisher shown: Comments: 9. Fire alarm systems (Section 907) required: YES Type of system required: Manual: Automatic: Both: X Type of system being provided: Manual: Automatic: Both: Components of system shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: 1. NO, PLANS NOT SUBMITTED FOR ALARM SYSTEM. SUBMITTALS SHALL INCLUDE LOCATIONS OF ALARM -INITIATING AND NOTIFICATION APPLIANCES, ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATIERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS, MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND MATIERIALS, AND INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. 2. NO PLANS SUBMITTED FOR FIRE SPRINKLER SYSTEM. 3. SITE PLAN FOR THIS PROJECT STILL NOT ADEQUATE, PLEASE SUBMIT A NEW SITE PLAN. 10. Other corrections that are required by special occupancy or conditions: SEE ALL PREVIOUS COMMENTS Plans as submitted are acceptable: NO Plans checked by: CHRIS HUSKINSON Date: 8-6-03 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: X FpEXeU/�C // ,�jq ////� ��//pp P.O. Box 280 o Cly O/ iG°A','fdar 12 North Center Street « „ Rexburg, Idaho 83440 F� .y Phone (208) 359-3020 Tq �$ STATE OF IDAHO Fax (208) 359-3022 /SHE www.cLrexburgJd.us e-mail rexburg@d.rexburg.id.us 8/8/2003 Ken Harris 3520 North University Avenue Suite #200 Provo, Utah 84604 Dear Ken, I have reviewed the drawings for building #1 of the Teton River Village and have identified the following deficiencies: UNC 1. Provide a handicap parking space adjacent to building #2. The closest handicap parking spaces are located across a vehicle access aisle. 2. The trash dumpster located on the south side of the parking lot will not be accessible by our trash trucks. Our trucks are side loading and require asphalt on both sides of the dumpster. 3. Please provide a Flood Elevation Certificate as required in the 2000 International Building Code (IBC) Section 1612.5. 4. A soil investigation report that was conducted for the Jack -In -The Box restaurant (located on the same piece of property) identified a layer of fill mixed with garbage covering the building lot. Please provide us with a soils report for any areas where new footings are to be placed. Will you be excavating to remove these materials? Where footings are to be placed on structural fill, please provide a report as per the 2000 IBC Section 1803.4. 5. The plans identify that the mechanical, plumbing and electrical shall be "design build". Will the mechanical system require roof top units? If so, the mechanical roof unit weights need to be included in the structural design. Mechanical and electrical component placement must meet the design criteria of the 2000 IBC Section 1621. When components are identified, please supply the necessary information as per the 2000 IBC Section 1621.3.5. 6. The plans and specifications identify special inspections required for masonry, field welding, bolting and structural fill. The concrete is identified as 3000 psi and therefore should also be inspected by special inspectors. We need to meet with the inspection company representative to go over special inspections prior to construction. 7. The energy calculations that have been provided are for the Idaho Falls area. Our climate zone is different than Idaho Falls. The energy calculations should be for climate zone 16 of the 2000 International Energy Conservation Code. When the mechanical and electrical design is complete, another set of calculations will be required for the systems. 8. The City Engineer is out of town until Monday, August 1 Ph and the P&Z official will not be back until August 15`h. They have not reviewed the finished site plan and may have additional comments. 9. The Fire Department has reviewed the plans. I have attached a copy of the report. Please provide the necessary information they have requested. These items need to be addressed before issuance of a building permit. Please let me know if you have any questions. I can be reached during the day at 359-3020 Ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson Allen Washburn P.O. Box 280 Qny (0/ jfx1m1y 12 North Center S treet Rezhurn Idahn A3ddn STATE OF IDAHO Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@srv.net RE"URG-MADISON COUNTY EMERGENCYSER VICES 26 NORTH CENTER STREET REXB URG, IDAHO 83440 208-359-3010 208-359-3006 FAX 2000 International Fire Code Plan Date: 5-30-03 Plan Review Review Date: 8-6-03 Building Name: TETON RIVER VILLAGE, BUILDING #1 Building Address: SECOND EAST, REXBURG, IDAHO Stories: ONE Type of Construction: V-A Occupancy Classification: M Existing Floor Area: 12,811 SQ. FEET New Construction Floor Area: APPROXIMATELY 19,741 TOTAL SQ. FEET 1. Required Fire Flow (Appendix B): 2,500 GPM/TWO HOURS Comments: REQUIRED FIRE FLOW MAY BE REDUCED WHEN BUILDING IS EQUIPPED WITH AUTOMATIC FIRE SPRINKLER SYSTEMS. 2. Water Supply (Section 508, Appendix C) Required: YES Fire Hydrant Location: EXISTING ON 2" EAST (O"DELL'S), PROPOSED NEAR BUILDING Fire Hydrant Flows: EXISTING OK, PROPOSED UNKNOWN Fire Flow Test Location: SECOND EAST Fire Flow Supplied By: FD Other Approved Water Source: NONE Water Supply Acceptable: NO Fire Hydrant Location Acceptable: SEE COMMENTS Water Supply Comments: FOR BUILDING #1 PROPSED HYDRANT LOCATION ADEQUATE BUT NOT FOR ENTIRE PROJECT. ALL PROPOSED HYDRANTS REQUIRE AN ENGINEERS CALCULATION OF AVAILABLE WATER PRIOR TO APPROVAL. HYDRANTS ADJACENT TO BUILDING #1 MUST BE INSTALLED AND IN OPERATING ORDER PRIOR TO CONSTRUCTION. 3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES Acceptable Width: U/% Length: YES Surface: YES Complete Road Acceptable: NO, SEE COMMENTS Comments: BUILDER HAS NOT SUBMITTED ADEQUATE SITE PLAN FOR REQUIRED ACCESS TO BUILDINGS. 4. Access Roads and Water Supply, including fire hydrants are required to be installed and made serviceable prior to and during time of construction (Section 501): Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED. 5. installation of portable fire extinguishers (Section 906) Required: YES Location shown: NO Type provided acceptable: NOT SHOWN Comments: MINIMUM SIZE OF 2A10BC REQUIRED WITHIN TRAVEL DISTANCES IN ALL SPACES. 6. Automatic fire extinguishing systems (Section 903) Required: YES Type of system being installed: UNKNOWN Sprinkler system monitoring (Section 907) required: YES Comments: SEE SECTION #9 COMMENTS. 7. Standpipes (Section 905) required: NO Type required: Comments: 8. Ventilating hood and duct fire extinguisher system (Section 609) required: Type being provided: Automatic fuel shut-off required: Portable fire extinguisher shown: Comments: 9. Fire alarm systems (Section 907) required: YES Type of system required: Manual: Automatic: Both: X Type of system being provided: Manual: Automatic: Both: Components of system shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: 1. NO, PLANS NOT SUBMITTED FOR ALARM SYSTEM. SUBMITTALS SHALL INCLUDE LOCATIONS OF ALARM -INITIATING AND NOTIFICATION APPLIANCES, ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS, MODEL NUMBERS AND LISTING INFORMATION FOR EQUH'MENT, DEVICES AND MATIERIALS, AND INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. 2. NO PLANS SUBMITTED FOR FIRE SPRINKLER SYSTEM. 3. SITE PLAN FOR THIS PROJECT STILL NOT ADEQUATE, PLEASE SUBMIT A NEW SITE PLAN. 10. Other corrections that are required by special occupancy or conditions: SEE ALL PREVIOUS COMMENTS Plans as submitted are acceptable: NO �uRG P.O. Box 280orth Center Street �� �aQ�l°Q%J 12 N a a o �/ Rexburg, Idaho 83440 Phone (208) 359-3020 STATE OF IDAHO Fax (208) 359-3022 4e�rSHEp e-mail rexburg@srv.net MEMO: TO: TO WHOM IT MAY CONCERN FROM: CHRIS HUSKINSON, FIRE INSPECTOR DATE: JUNE 07, 2003 RE: TETON RIVER VILLAGE TO WHOM IT MAY CONCERN: Upon review of the site plan drawings submitted the following items need to be addressed: 1. WATER SUPPLY: This proposed project shows two large square footage structures spaced approximately 350 feet apart with several smaller buildings on the site. Based on conversations with the developers both of the larger structures are to be sprinklered. Plans do not show what construction type the new building shall be. Please indicate the type of construction for a more accurate review. The number of hydrants required may change depending upon type of construction. Currently, the size of structures and space between buildings require the west building to have a minimum of four hydrants within 300 feet. Currently it has one. The existing building has the correct number of hydrants. -Additionally, a six-inch main line to the hydrants will not be capable of supplying the required amount of water. 2. ACCESS: Areas adjacent to buildings shall have curbs painted red, maintained, and signed "No Parking Fire Lane". Additional plans are required to complete an accurate plan review of this project. If there are an questions please feel free to contact me. r Chris Huskinson Fire Inspector