I have reviewed the plans for Legacy Cove and have identified the following
discrepancies or questions:
1. Please provide storm water calculations and detention facility details.
2. Catch basins for storm water are spaced so that the far edges of the parking lot
are almost 1000' away. Additional catch basins should be provided that are
piped to main basins.
3. Identify Right -Of -Way on site plan. Has a development agreement with the
City of Rexburg been completed?
4. Identify utility easements on site plan.
5. Compact parking spaces are to be signed. Please identify signage on plans.
6. Please provide literature on stucco for 1 -hr rating.
7. Exterior guardrails are identified as 361', please change to 42" as per 1997
Uniform Building Code (UBC) Section 509.2.
8. The shear wall schedule on page A04 identifies construction requirements.
Are all of the walls highlighted on the framing details shear walls?
9. The shear wall schedule identifies MST 60 straps, what is there spacing?
10. Provide details showing requirements of the second paragraph of shear wall
notes from page A04.
11. Where shear walls are sheethed with long side of structural panels in the
horizontal direction (as per shear wall notes on page A04) is blocking required
at the joints that will be created?
12. On page A04, a footing schedule is provided, and then all footings are
identified as one size. Please identify which is valid. If the schedule is to be
used, please identify which footings are which.
13. If footings are place directly on bedrock but are located above the frost line,
the rock surface must be cleaned of any soil or loose surface. Please identify
this on the plans if this construction method is to be used.
14. Please provide truss details as soon as you can.
15. Provide details of transition from parking lot to sidewalk at the handicap
spaces.
16. The upper level managers apartment is not accessible.
17. The large room in the Community Center building requires 2 exits. One exit
must be directly to the outside or to a properly constructed corridor. The exits
should be '/2 the diagonal distance of the area served from each other.
18. Please identify what will be stored in the equipment room of the Community
Center building.
19. Identify shear walls for the Community Center building.
20. What is above the exercise room in the Community Center building?
21. What is the purpose of the shaft that has been created between floors in the
managers unit and the area below?
22. Provide copies of the plan to the State of Idaho Electrical Division for review.
23. I have attached a copy of the Fire Department review top the back of this
document.
Please provide me with 2 new stamped copies of the corrected plans. If you have
any questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 3-01-02
Plan Review Review Date: 4-15-02
Building Name: LEGACY COVE STUDENT HOUSING
Building Address: SEVENTH SOUTH AND SECOND EAST
Stories: 2.5 Type of Construction: V -ONE HOUR
Occupancy Classification: R1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 23,160 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 1,500 GPM/TWO HOURS
Comments: FIRE FLOW REQUIREMENTS BASED ON BUILDINGS BEING FULLY
SPRINRLERED. CLUBHOUSE FIRE FLOW IS 1500 GPM/TWO HOURS.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: B-56
Fire Hydrant Flows: UNKNOWN
Other Approved Water Source: NONE
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLANS SUBMITTED SHOW A HYDRANT ON NORTH SIDE
OF MENS HOUSING ADJACENT TO WOMEN'S HOUSING. THIS HYDRANT COULD BE
ELIMINATED IF EXISTING HYDRANT ON ASPEN VILLAGE PROPERTY IS
UTILIZED. ALL HYDRANTS WITHIN 500 FEET.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES Length: YES Surface: YES
Turning Radius: YES Grade: YES
Clearance: YES Turn Arounds: YES
Complete Road Acceptable: YES
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO
WILL BE ISSUED.
A STOP WORK ORDER
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Comments: MINIMUM OF 2A10BC EXTINGUISHER REQUIRED IN EACH UNIT IN
ADDITION TO COMMON AREAS, LAUNDRIES, COMPUTER ROOMS, ETC.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: TO BE INSTALLED Type Of System Being Installed: 13R
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: TO BE INSTALLED
Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: Both: YES
Type Of System Being Provided: Manual: Automatic: Both: YES
Components Of System Shown: Smoke Detectors: YES Heat Detectors:
Manual Pull Station: YES Sounding Devices: YES Visual Devices:
YES
Door Holders: NO Duct Detectors: NO
Fire Alarm System Acceptable: NO DRAWINGS PROVIDED FOR ALARM
SYSTEM. HANDICAPPED UNITS (TYPE "A") UNITS MUST BE EQUIPPED WITH
HORN/STROBES. PLANS ARE VAGUE IN REGARD TO PULL STATIONS,
MANUAL PULL STATIONS TO BE PROVIDED AT EVERY EXIT FROM EVERY LEVEL.
HEAT AND SMOKE DETECTORS TO BE PROVIDED IN COMMON AREAS. SYSTEM TO
BE SUPERVISED. NEW PLANS NEED TO INCLUDE THE FOLLOWING ITEMS:
LOCATIONS OF ALARM -INITIATING AND NOTIFICATION APPLIANCES, ALARM
CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER
CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE
DROP CALCULATIONS, MANUFACTURERS MODEL NUMBERS AND LISTING
INFORMATION FOR EQUIPMENT, DEVICES AND MATERIALS, ETC. PLEASE
SUBMIT PLANS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions/Comments: Plans As Submitted Are Acceptable: YES
Plans Checked Bv: CHRIS HUSRINSON Date: 4-15-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES