HomeMy WebLinkAboutPLAN REVIEWS - Legacy Cove - 667 S 2nd E4/24/2002 Brent Hilton Hilton Architects 6895 South 900 East Salt Lake City, UT 84047 Dear Brent, STATE OF IDAHO www.drexburo.id.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the plans for Legacy Cove and have identified the following discrepancies or questions: 1. Please provide storm water calculations and detention facility details. 2. Catch basins for storm water are spaced so that the far edges of the parking lot are almost 1000' away. Additional catch basins should be provided that are piped to main basins. 3. Identify Right -Of -Way on site plan. Has a development agreement with the City of Rexburg been completed? 4. Identify utility easements on site plan. 5. Compact parking spaces are to be signed. Please identify signage on plans. 6. Please provide literature on stucco for 1 -hr rating. 7. Exterior guardrails are identified as 361', please change to 42" as per 1997 Uniform Building Code (UBC) Section 509.2. 8. The shear wall schedule on page A04 identifies construction requirements. Are all of the walls highlighted on the framing details shear walls? 9. The shear wall schedule identifies MST 60 straps, what is there spacing? 10. Provide details showing requirements of the second paragraph of shear wall notes from page A04. 11. Where shear walls are sheethed with long side of structural panels in the horizontal direction (as per shear wall notes on page A04) is blocking required at the joints that will be created? 12. On page A04, a footing schedule is provided, and then all footings are identified as one size. Please identify which is valid. If the schedule is to be used, please identify which footings are which. 13. If footings are place directly on bedrock but are located above the frost line, the rock surface must be cleaned of any soil or loose surface. Please identify this on the plans if this construction method is to be used. 14. Please provide truss details as soon as you can. 15. Provide details of transition from parking lot to sidewalk at the handicap spaces. 16. The upper level managers apartment is not accessible. 17. The large room in the Community Center building requires 2 exits. One exit must be directly to the outside or to a properly constructed corridor. The exits should be '/2 the diagonal distance of the area served from each other. 18. Please identify what will be stored in the equipment room of the Community Center building. 19. Identify shear walls for the Community Center building. 20. What is above the exercise room in the Community Center building? 21. What is the purpose of the shaft that has been created between floors in the managers unit and the area below? 22. Provide copies of the plan to the State of Idaho Electrical Division for review. 23. I have attached a copy of the Fire Department review top the back of this document. Please provide me with 2 new stamped copies of the corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 3-01-02 Plan Review Review Date: 4-15-02 Building Name: LEGACY COVE STUDENT HOUSING Building Address: SEVENTH SOUTH AND SECOND EAST Stories: 2.5 Type of Construction: V -ONE HOUR Occupancy Classification: R1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 23,160 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 1,500 GPM/TWO HOURS Comments: FIRE FLOW REQUIREMENTS BASED ON BUILDINGS BEING FULLY SPRINRLERED. CLUBHOUSE FIRE FLOW IS 1500 GPM/TWO HOURS. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: B-56 Fire Hydrant Flows: UNKNOWN Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: PLANS SUBMITTED SHOW A HYDRANT ON NORTH SIDE OF MENS HOUSING ADJACENT TO WOMEN'S HOUSING. THIS HYDRANT COULD BE ELIMINATED IF EXISTING HYDRANT ON ASPEN VILLAGE PROPERTY IS UTILIZED. ALL HYDRANTS WITHIN 500 FEET. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: YES Grade: YES Clearance: YES Turn Arounds: YES Complete Road Acceptable: YES 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO WILL BE ISSUED. A STOP WORK ORDER 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: MINIMUM OF 2A10BC EXTINGUISHER REQUIRED IN EACH UNIT IN ADDITION TO COMMON AREAS, LAUNDRIES, COMPUTER ROOMS, ETC. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: TO BE INSTALLED Type Of System Being Installed: 13R Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: TO BE INSTALLED Comments: 8).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: Both: YES Type Of System Being Provided: Manual: Automatic: Both: YES Components Of System Shown: Smoke Detectors: YES Heat Detectors: Manual Pull Station: YES Sounding Devices: YES Visual Devices: YES Door Holders: NO Duct Detectors: NO Fire Alarm System Acceptable: NO DRAWINGS PROVIDED FOR ALARM SYSTEM. HANDICAPPED UNITS (TYPE "A") UNITS MUST BE EQUIPPED WITH HORN/STROBES. PLANS ARE VAGUE IN REGARD TO PULL STATIONS, MANUAL PULL STATIONS TO BE PROVIDED AT EVERY EXIT FROM EVERY LEVEL. HEAT AND SMOKE DETECTORS TO BE PROVIDED IN COMMON AREAS. SYSTEM TO BE SUPERVISED. NEW PLANS NEED TO INCLUDE THE FOLLOWING ITEMS: LOCATIONS OF ALARM -INITIATING AND NOTIFICATION APPLIANCES, ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND MATERIALS, ETC. PLEASE SUBMIT PLANS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions/Comments: Plans As Submitted Are Acceptable: YES Plans Checked Bv: CHRIS HUSRINSON Date: 4-15-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: YES New Plans: YES