I have reviewed the drawings for the Deseret Industries building and have identified the
following deficiencies:
1. The handicapped parking spaces do not have the 5' aisle as required. Also a van
accessible space with a 9' wide aisle adjacent to it is required.
2. Please provide a Flood Elevation Certificate as required in the 2000 International
Building Code (IBC) Section 1612.5.
3. A soil investigation report must be provided. The structural calculations use the
soil conditions of Site Class "C". Without an engineered site study, the default
Site Classification is "D". Please provide a soil investigation study or revise the
structural calculations using Site Class "D".
4. The structural calculations are not consistent. Part of the document references the
IBC and part the 1997 Uniform Building Code. At the front of the document, the
snow load (live load) is accurately identified as 35 lb/ft, while in the roof
calculations the snow load used is 30 lb/ft. The document identifies the seismic
use group as group I. The IBC Table 1604.5 lists "buildings or structures where
more than 300 people congregate in one area" as seismic use group II. The retail
area of the store has an occupancy of 487.
5. On page 2 of the roof section of the structural calculations, the engineer makes the
statement that the mechanical roof unit weights have not been included in the
structural design and that roof joist manufacturer should provide the design.
Please provide me with the necessary engineering document
6. On page G1.2 an "as is" area is identified at the rear of the building as having an
exit serving 120 occupants. Two exits are required with exit lights. Sheet E1.1
identifies an exit sign in the "as is" area leading back into the building. Please
remove this symbol.
7. The exit signs on page E1.2 are not the same as on page FD1.1. Please add where
missing.
8. The exiting thru the vestibule does not meet the requirements set forth in the IBC
Section 1006.1 and Table 1004.2.1.
9. Submit manufacturer's certificate of compliance for all components as per IBC
Section 1621.3.5. Page 50.1 identifies that equipment seismic bracing will be
provided by the equipment manufacturer. Please supply this information.
10. IBC Table 601 identifies the roof construction of Type II -B buildings as being
required to have a 0 hr. fire -resistance rating. Footnote "c" makes an exception
for F-1 occupancies. Section 302.3.2 of the IBC requires that "the most restrictive
type of construction, so determined, shall apply to the entire building" in order for
Section 302.3.2 - "Non -separated Uses" to apply. The roof construction must be
1 -hr rated.
11. The plans and specifications identify special inspections required for concrete,
masonry, reinforcing steel, steel roof deck and all structural welding. Please
provide us with information and certifications of the people and firm that will be
performing these inspections. We need to meet with the inspection company
representative to go over special inspections prior to construction.
12. Structural observation by the Engineer is a requirement of your Quality Assurance
Program that is detailed on page 50.2. Please provide a list of projected visits.
13. Page S0.2 identifies IBC Sections 1505.2 thru 1505.4 to be followed for concrete
testing. These sections deal with roof assemblies. Please make the necessary
changes.
14. The Fire Department has reviewed the plans. I have attached a copy of the report.
Please provide the necessary information they have requested.
These items need to be addressed before issuance of a building permit. Please let me know
if you have any questions. I can be reached during the day at 359-3020 Ext. 324.
Sincerely
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
Jon Berry
STATE OF IDAHO
P0. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
REXBURG-MADISON COUNTY
EMERGENCYSERVICES
26 NORTH CENTER STREET
REXBURG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code
Plan Review
Plan Date: 4-03
Review Date: 5-29-03
Building Name: DESERET INDUSTRIES AND DISTRIBUTION CENTER
Building Address: NORTH SECOND EAST, REXBURG
Stories: 1 Type of Construction: H -B
Occupancy Classification: M, B, F-1
Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 39,133 SQUARE FEET
1. Required Fire Flow (Appendix B): 4,250 GPM/THREE HOURS
Comments: FIRE FLOW MAY BE REDUCED IF EACH BUILDING HAS A FIRE
SUPPRESSION SYSTEM THROUGHOUT.
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: OKAY
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLEASE PROVIDE AN ENGINEER'S ASSESSMENT
OF WATER FLOWS PRIOR TO CONSTRUCTION.
3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: X Length: X Surface: X
Complete Road Acceptable: YES
Comments: NONE
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required: YES
Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN
Comments: MINIMUM SIZE OF 2A10BC REQUIRED TO BE MOUNTED
THROUGHOUT FACILITY WITHIN TRAVEL DISTANCES.
6. Automatic fire extinguishing systems (Section 903) Required: YES
Type of system being installed: NOT SHOWN
Sprinkler system monitoring (Section 907) required: YES
Comments: PLANS REQUIRED TO BE SUBMITTED TO STATE PRIOR TO
ISSUANCE OF A BUILDING PERMIT.
7. Standpipes (Section 905) required: NO
Type required: Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
Type being provided:
Automatic fuel shut-off required:
Portable fire extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: YES
Type of system required: Manual: Automatic: Both: X
Type of system being provided: Manual: Automatic: Both: X
Components of system shown: Smoke Detectors: X Heat Detectors:
Manual Pull Station: X Sounding Devices: X Visual Devices: X
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: REQUIRED
Fire Alarm System Acceptable: NO, SEE COMMENTS BELOW
10. Other corrections that are required by special occupancy or conditions: FIRE
ALARM SYSTEM: PLEASE SUBMIT PLANS IN ADDITION TO THE
FOLLOWING SUBMITTALS: ALARM CONTROL AND TROUBLE
SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION,
BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE
DROP CALCULATIONS, MANUFACTURERS MODEL NUMBERS, AND
LISTING INFORMATION FOR EQUIPMENT, EVICES AND MATERIALS
AND INTERFACE CONNECTIONS. ADA UNITS SHALL HAVE ALL
HORN/STROBE UNITS. PLEASE INDICATE WHERE FACP WILL BE
LOCATED. PLANS MUST BE SUBMITTED PRIOR TO CONSTRUCTION
OR A STOP WORK ORDER WILL BE ISSUED.
ADDITIONAL ALARM SYSTEM COMMENTS:
DISTRIBUTION CENTER-
1.
ENTER1. ADD PULL STATION TO FRONT VESTIBLE EXIT
2. ADD HORN/STROBE UNIT WITHIN 15 FEET OF FRONT
VESTIBLE EXIT
MAIN COMPLEX -
1. ADD HORN/STROBE UNITS IN HALLWAY LEADING TO
OFFICES ON NORTH SIDE.
2. ADD HORN/STROBE TO MENS BATHROOM
3. ADD HORN/STROBE TO SOUTH END OF HALLWAY 202
4. ADD PULL STATION AT REAR EXIT FROM PROCESSING
5. ADD PULL STATION AT REAR EXIT FROM RETAIL
6. MOVE PULL STATIONS WITHIN FIVE FEET OF EXIT
7. ADD HORN/STROBE UNITS TO WAITING AREA OFFICES
ON NORTH SIDE.
Plans as submitted are acceptable: NO
Plans checked by: CHRIS HUSIONSON Date: 5-29-03
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: X