I have reviewed the drawings for the BYU Idaho Student Health and Counseling Center
and have identified the following discrepancies:
The parking plan includes two handicapped accessible spaces, one with an aisle along
side and one without. The ADA guidelines for Accessible Design requires that a 5
foot aisle be included along side each handicapped accessible space. Additionally, the
amount of required handicapped spaces (by my calculations) should be 3, not 2. If we
identify the number of required parking spaces using the Rexburg Zoning Ordinance
requirement of spaces per 1000 sq. ft. of building space, the result is 61 required
spaces for the 20296 sq. ft. building. The ADA Standard for Accessible design
identifies that 3 handicapped spaces are to be provided. "I feel that these numbers are
conservative for a building that will have an occupancy of over 200 people.
The waiting area is of a size that will require 2 exits as per Table 1004.2.1 of the 2000
International Building Code (IBC). Exit signs will need to be added to the other
entrance(s) that connects to the exit hallway.
Please provide cut sheets for all HVAC Units.
The Fire Department has reviewed the drawings and I have attached a copy of their
report to the back -of this document. Please address their concerns.
Please address the above items and return two copies of any changes to me at City Hall.
Thank you for your cooperation in this matter. If you have any questions please give me a call at
359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
cc: John Millar
Chris Huskinson
Rulon Neilsen
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
2000 INTERNATIONAL FIRE CODE Plan Date: 9-20-02
Plan Review Review Date: 10-6-02
Building Name: BYU-I STUDENT HEALTH CENTER
Building Address: BYU-I CAMPUS, VIKING DRIVE
Stories: TWO Type of Construction: 5-A
Occupancy Classification: B Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 22,472 SQUARE FEET
1).Required Fire Flow (Appendix III -A): 2750 GPM/TWO HOURS
Comments: FIRE FLOW REQUIREMENT SHALL BE 1500 GPM/TWO HOURS AS
BUILDING IS EQUIPPED WITH AN AUTOMATIC FIRE SUPPRESSION SYSTEM.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: CLOSEST IS D-38 CENTRAL HIGH SCHOOL AND BYU-
I CAMPUS (VIKING DRIVE)
Fire Hydrant Flows: OKAY
Fire Flow Test Location: SAME AS ABOVE
Fire Flow Supplied By: FD AND BYU-I
Other Approved Water Source: NONE
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: YES
Water Supply Comments: NONE
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: X Length: X Surface: X
Complete Road Acceptable: YES
Comments: NONE
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO
CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Comments: MINIMUM SIZE OF 2A10BC REQUIRED WITHIN TRAVEL DISTANCES
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: YES Type Of System Being Installed: WET, SUBMIT PLANS TO
STATE FIRE MARSHAL
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: YES
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required: Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: NO
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments:
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: Both: X
Type Of System Being Provided: Manual: Automatic: Both: X
Components Of System Shown: Smoke Detectors: X Heat Detectors: X
Manual Pull Station: X Sounding Devices: X Visual Devices: X
Door Holders: Duct Detectors: Flow Alarm: X
Sprinkler Valve Monitoring: X Fire Alarm System Acceptable: SEE
COMMENTS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: SEE COMMENTS
Comments: PLEASE PROVIDE THE FOLLOWING IN REGARDS TO THE ALARM
SYSTEM: ALARM CONTROL AND SIGNALLING EQUIPMENT, ANNUNCIATION, POWER
CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE
DROP CALCULATIONS, MANUFACTURERS, MODEL NUMBERS AND LISTING
INFORMATION FOR EQUIPMENT, DEVICES AND MATERIALS, AND THE INTERFACE
FOR SAFETY CONTROL FUNCTIONS. SEE BELOW FOR MISSING HORN/STROBES,
PULL STATIONS, ETC. THAT NEED TO BE ADDED TO SYSTEM. ARE MAGNETIC
DOOR HOLDERS GOING TO BE USED THROUGHOUT THE BUILDING? IF S0,
PLEASE ADDRESS.
Plans As Submitted Are Acceptable: NO, PLEASE ADDRESS NOTED ITEMS
Plans Checked By: CHRIS HUSRINSON Date: 10-6-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: X New Plans: X
ALARM SYSTEM ITEMS•
FIRST FLOOR:
1. ADD PULL STATION AT REAR GARAGE DOOR EXIT
2. ADD HORN/STOBE UNIT IN ROOMS 136, 131, 134, 164, 172, AND
116.
3. MOVE HORN/STROBE IN ROOM 179 TO MORE CENTRAL LOCATION.
4. ADD HORN STROBE UNITS IN CORRIDOR 126.
SECOND FLOOR:
1. ADD HORN/STROBE UNIT IN ROOM 282.