I have reviewed the plans for Beehive Phase II located at 408 West Main in
Rexburg and have identified the following discrepancies:
1. The allowable area for an R4 occupancy shall not exceed 3000 sq. ft. as
per 1997 Uniform Building Code (UBC) Section 334.1 from Appendix
Chapter 3. The Section allows increases from UBC Sections 504, 505 and
506. Section 504 does not seem applicable to this building. Section 505
would allow area increase with separation on 2 or more sides of over 20'.
Only one side of the building has over 20' to a property line, assumed
property line (1/2 way between buildings) or public way. The increased
area allowed by providing sprinklers (Section 505.3) are to be identified in
Table 5-B and UBC Section 504.2, neither applies to R-4 occupancies.
Section 506 does not seem to apply either. After discussing the issue with
Reggie Fulmer of the Idaho Falls Building Department, I have decided to
take his recommendation and review the project as an R-1 occupancy.
The City of Idaho Falls has allowed construction of these facilities as R-1
occupancies. I have requested information from the State of Idaho of their
inspections, requirements, etc. of Assisted Living Centers. Any
information I receive back from the State may change some requirements.
2. The Code Analysis on page C-1 of the plans has many wrong listings.
The live roof load is listed at 30 psf when it should be 35 psf The
earthquake zone is listed at 2 when it should be listed at 3. Our wind zone
is 80 mph not 70 mph. The location of the project will be in a category
"C" wind zone. Our frost depth is 36" not 24", Please make the necessary
changes to the plans as well as structural calculations and re -submit. Also
when making the above changes to sheet C-1, please change the R-4
designation to R-1. ,
3. Please provide a site plan that identifies utility service lines with
dimensions, sizes and types. Show parking space sizes, parking aisle
dimensions, handicap space, handicap signs and handicap access from
parking to building.
4. Please show minimum vertical and horizontal reinforcement in foundation
as per UBC Sections 1914.3.3 and 1914.3.5. If the engineer has
performed structural analysis that would allow the rebar configuration as it
is shown on plans, please provide the calculations.
5. Identify the size (btu) of the furnaces and water heaters.
6. Electrical drawings should be provided to Mark with the State of Idaho
Electrical Bureau.
7. The exits do not meet the %z of diagonal length as required by UBC
sectionl004.2.4.
8. The living room and activity areas do not meet the light requirements of
UBC Section 1203.2.
9. Provide an egress window in each bedroom. The scale of the plans is too
small for me to identify the size of the windows. They should meet the
requirements of UBC Section 310.4.
10. Provide Draft Stops as per UBC Section 708.3.
11. Please provide drawings with details for handicap accessible bathrooms.
Include turning space for 60" circle, hand bar location, sink heights, knee
space, fixture heights, etc.
12. All areas customarily occupied by humans shall be provided with natural
ventilation by means of operable exterior openings with an area of not less
than 1/20 of the total floor area or shall be provided with a mechanically
operated ventilation system. Such system shall be capable of supplying a
minimum of 15 cubic feet per minute of outside air per occupant as per
UBC section 1202.2.1.
The Fire Department has not reviewed the plans. They have requested a larger set
be provided for their review and may have additional requirements. Please provide me
with 2 new copies of the corrected plans. If you have any questions, please give me a call
at 359-3020 ext. 324.
Sincerely, D
Val Christensen
Building Official