I have reviewed the Valley Wide Coop drawings that you have provided me and
have identified the following discrepancies:
1. The ADA Standards for Accessible Design require 5 handicapped spaces be
provided for a parking lot with 102 parking spaces. Parking lots with only
100 spaces are only required to have 4 handicapped spaces. One of the
handicapped spaces is required to be a van accessible space with a 9' wide
aisle adjacent to it.
2. The right-of-way for 2000 West is shown out in the street. The right of way
must be located somewhere between the parking lot and the sidewalk. This
should have been cleared up with John Millar prior to site plan approval by
the P&Z.
3. Get with John Millar the City of Rexburg Public Facilities Coordinator for a
Development Agreement.
4. Include street improvement details for the work to be performed on 2000 West
and Main streets. Include sections showing granular borrow, crushed
aggregate and plant -mix. Also include any geo-textile fabrics as per
development agreement.
5. Provide access approach details that identify 6" thick concrete with #4 rebar at
18" o.c. in both directions.
6. Please identify a handicapped ramp at the corner of 200 West and Main Street.
7. Please identify trash facilities on the site plan.
8. The men's restroom could function better if the stall were moved to the front
like the women's bathroom. This way there would be a 5' circle at the stall
and a wider space in front of the sinks.
9. Construction Type IIN does not allow combustible studs in exterior walls.
Section 1 on page A5 identifies wood studs. Please change to metal or
another non-combustible material
10. Section 5 on page A5 must show 5/8" Type X gypsum on both sides of wall.
All gypsum panels should be 5/8" Type X throughout entire building
(including bathroom).
11. Dampers are required in ducts when they penetrate an area separation wall as
per the 1997 Uniform Building Code (UBC) Section 713.10 and 713.11.
Please show dampers in these areas. Including the refrigeration equipment
room.
12. Please identify a one hour door at the refrigeration equipment room as per the
UBC Section 2802.
13. Identify a one hour wall assembly between the mezzanine and the sales area
of the store.
14. The canopy details for the pump island are designed using a 70 mph wind
speed and a snow load of 30 lb/ft. Please provide new details designed with
the correct loads.
15. The foundation calculations have been made for a 2B seismic zone. This is
going to present a problem given that the foundation has already been built.
Please make new calculations and provide them to me as well as any changes
that must be implemented due to the error.
16. The Engineering calculation summary document that you have provided
identifies various floor joists constructed in the mezzanine floor that are listed
as "insufficient due to load". Please explain what you are doing about this
discrepancy.
17. Special inspections are required by code for this structure. Please indicate
what inspections will be provided and who will be performing the inspections.
18. The Fire Department has reviewed the plans. I have attached a copy of there
report to the back of this document. Please provide the necessary information
they have requested.
Please return two sets of revised plans. Let me know if I can be of any further
assistance. If you have any questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
cc John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Cente�
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 11-04-02
Plan Review Review Date: 12-02-02
Building Name: VALLEY WIDE COOP
Building Address: WEST HIGHWAY 33 AND 2000 WEST
Stories: ONE
Type of Construction: II -N
Occupancy Classification: M, B, S-1, S-2 Existing Floor Area:
N/A
New Construction Floor Area: APPROXIMATELY 17,000 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 2750 GPM/TWO HOURS
Comments: NONE
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: THREE PROPOSED HYDRANTS
Fire Hydrant Flows: UNKNOWN
Other Approved Water Source: NONE
Water Supply Acceptable: YES, SEE COMMENTS
Fire Hydrant Location Acceptable: NO, SEE COMMENTS
Water Supply Comments: FIRE HYDRANTS FLOWS TO BE VERIFIED BY AN
ENGINEER PRIOR TO CONSTRUCTION AND SUBMITTED TO FIRE DEPARTMENT FOR
APPROVAL. FIRE HYDRANT IN SOUTHWEST CORNER NEEDS TO BE MOVED,
DRAWINGS SHOW A PROPANE TANK BLOCKING ACCESS.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES
Turning Radius: YES
Clearance: YES
Length: YES Surface: YES
Complete Road Acceptable: YES
Grade: YES
Turn Arounds: YES
1 11
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Comments: MINIMUM OF ONE 2A10BC EXTINGUISHER REQUIRED WITHIN TRAVEL
DISTANCES IN EACH AREA
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: NO
Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: NO
Type Of System Required: Manual: Automatic: Both:
Type Of System Being Provided: Manual: Automatic:Both:
Components Of System Shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: NO Duct Detectors: NO
Fire Alarm System Acceptable: N/A
10).Other Corrections That Are Required By Special Occupancy Or
Conditions/Comments: Plans As Submitted Are Acceptable: NO
Plans Checked By: CHRIS HUSKINSON
Date: 12-02-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: X New Plans: X