HomeMy WebLinkAboutPLAN REVIEW - 02-00080 - Valley Wide Coop12/3/2002 Scott Spaulding Design Intelligence 3685 E Hwy. 33 Rexburg, Idaho 83440 Dear Scott, 1�///[�J/j/� P.O. Box 280 cly ���J' lL �a���%�°� 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 STATE OF IDAHO Fax (208) 359-3022 www.cl.rexburg.Id.us e-mail rexburg@ci.rexburgJd.us I have reviewed the Valley Wide Coop drawings that you have provided me and have identified the following discrepancies: 1. The ADA Standards for Accessible Design require 5 handicapped spaces be provided for a parking lot with 102 parking spaces. Parking lots with only 100 spaces are only required to have 4 handicapped spaces. One of the handicapped spaces is required to be a van accessible space with a 9' wide aisle adjacent to it. 2. The right-of-way for 2000 West is shown out in the street. The right of way must be located somewhere between the parking lot and the sidewalk. This should have been cleared up with John Millar prior to site plan approval by the P&Z. 3. Get with John Millar the City of Rexburg Public Facilities Coordinator for a Development Agreement. 4. Include street improvement details for the work to be performed on 2000 West and Main streets. Include sections showing granular borrow, crushed aggregate and plant -mix. Also include any geo-textile fabrics as per development agreement. 5. Provide access approach details that identify 6" thick concrete with #4 rebar at 18" o.c. in both directions. 6. Please identify a handicapped ramp at the corner of 200 West and Main Street. 7. Please identify trash facilities on the site plan. 8. The men's restroom could function better if the stall were moved to the front like the women's bathroom. This way there would be a 5' circle at the stall and a wider space in front of the sinks. 9. Construction Type IIN does not allow combustible studs in exterior walls. Section 1 on page A5 identifies wood studs. Please change to metal or another non-combustible material 10. Section 5 on page A5 must show 5/8" Type X gypsum on both sides of wall. All gypsum panels should be 5/8" Type X throughout entire building (including bathroom). 11. Dampers are required in ducts when they penetrate an area separation wall as per the 1997 Uniform Building Code (UBC) Section 713.10 and 713.11. Please show dampers in these areas. Including the refrigeration equipment room. 12. Please identify a one hour door at the refrigeration equipment room as per the UBC Section 2802. 13. Identify a one hour wall assembly between the mezzanine and the sales area of the store. 14. The canopy details for the pump island are designed using a 70 mph wind speed and a snow load of 30 lb/ft. Please provide new details designed with the correct loads. 15. The foundation calculations have been made for a 2B seismic zone. This is going to present a problem given that the foundation has already been built. Please make new calculations and provide them to me as well as any changes that must be implemented due to the error. 16. The Engineering calculation summary document that you have provided identifies various floor joists constructed in the mezzanine floor that are listed as "insufficient due to load". Please explain what you are doing about this discrepancy. 17. Special inspections are required by code for this structure. Please indicate what inspections will be provided and who will be performing the inspections. 18. The Fire Department has reviewed the plans. I have attached a copy of there report to the back of this document. Please provide the necessary information they have requested. Please return two sets of revised plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official cc John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Cente� Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 11-04-02 Plan Review Review Date: 12-02-02 Building Name: VALLEY WIDE COOP Building Address: WEST HIGHWAY 33 AND 2000 WEST Stories: ONE Type of Construction: II -N Occupancy Classification: M, B, S-1, S-2 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 17,000 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2750 GPM/TWO HOURS Comments: NONE 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: THREE PROPOSED HYDRANTS Fire Hydrant Flows: UNKNOWN Other Approved Water Source: NONE Water Supply Acceptable: YES, SEE COMMENTS Fire Hydrant Location Acceptable: NO, SEE COMMENTS Water Supply Comments: FIRE HYDRANTS FLOWS TO BE VERIFIED BY AN ENGINEER PRIOR TO CONSTRUCTION AND SUBMITTED TO FIRE DEPARTMENT FOR APPROVAL. FIRE HYDRANT IN SOUTHWEST CORNER NEEDS TO BE MOVED, DRAWINGS SHOW A PROPANE TANK BLOCKING ACCESS. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Turning Radius: YES Clearance: YES Length: YES Surface: YES Complete Road Acceptable: YES Grade: YES Turn Arounds: YES 1 11 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: MINIMUM OF ONE 2A10BC EXTINGUISHER REQUIRED WITHIN TRAVEL DISTANCES IN EACH AREA 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: NO Comments: 8).Fire Alarm Systems (Article 10 Section 1007)Required: NO Type Of System Required: Manual: Automatic: Both: Type Of System Being Provided: Manual: Automatic:Both: Components Of System Shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: NO Duct Detectors: NO Fire Alarm System Acceptable: N/A 10).Other Corrections That Are Required By Special Occupancy Or Conditions/Comments: Plans As Submitted Are Acceptable: NO Plans Checked By: CHRIS HUSKINSON Date: 12-02-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: X