I have reviewed the drawings for building #1 and the site plan of the Teton River Village
(identified on the plans as American Family Entertainment Center) and have identified the
following deficiencies:
1. Provide a handicap parking space adjacent to building #2. The closest handicap
parking spaces are located across a vehicle access aisle.
2. Please provide a Flood Elevation Certificate as required in the 2000 International
Building Code (IBC) Section 1612.5.
3. The geotechnical investigation for this site (included in the project Manual dated
July 14, 2003) describes the site as being located in Seismic Zone 2B. This zone is
from the 1997 Uniform Building Code (UBC). Rexburg is located in Seismic Zone
3 in the UBC. The structural design is consistent with Chapter 16 of the
International Building Code. My concern is that the Geotechnical firm may have
made recommendations based on this information. Provide me with a letter from
this firm addressing the discrepancy. Design should be applicable to the 2000 IBC.
4. The envelope compliance energy calculations for that have been provided are for
the Idaho Falls area. Our climate zone is different than Idaho Falls. The energy
calculations should be for climate zone 16 of the 2000 International Energy
Conservation Code.
5. The Fire Department has reviewed the plans. I have attached a copy of the report.
Please provide the necessary information they have requested.
These items need to be addressed before issuance of a building permit. Please let me know
if you have any questions. I can be reached during the day at 359-3020 Ext. 324.
Sincerely+�
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXB UR G -MADISON COUNTY
EMERGENCYSER VICES
26 NORTH CENTER STREET
REXBURG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code
Plan Review
Plan Date: 7-14-03
Review Date: 7-22-03
Building Name: AMERICAN FAMILY ENTERTAINMENT COMPLEX
Building Address: 485 NORTH SECOND EAST, REXBURG, IDAHO
Stories: 2 Type of Construction: H -B
Occupancy Classification: A-1, A-3
Existing Floor Area: N/A
New Construction Floor Area: 46,242 SQUARE FEET
1. Required Fire Flow (Appendix B): 4,500 GPM/FOUR HOURS
Comments. NONE
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: NOT ENOUGH HYDRANTS ON SITE PLAN FOR
REVIEW
Fire Hydrant Flows:
Fire Flow Test Location:
Fire Flow Supplied By:
Other Approved Water Source:
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO
Water Supply Comments: REQUIRED WATER FLOW INCLUDING SIZE AND
TYPE OF STRUCTURE INDICATE A MINIMUM OF FIVE HYDRANTS
WITHIN 300 OF STRUCTURE.