9/5/2002
Scott Morrill
Engineering Specialties
1576 South 3200 West
Logan, Utah 84321
Dear Scott
I have reviewed the plans for the Stone Brook Apartments and have identified the
following discrepancies:
1. Please identify and dimension planter strip (utility strip) and sidewalk on Site
Plan. Also, the driveway detail on sheet C2.1 does not show sidewalk behind
utility strip. Please identify utility strip on this page.
2. Identify fence or other suitable buffer along South property line of parking lot.
3. Please include dimensions from curb to sidewalk and the dimensions of the
sidewalk on Site Plan.
4. Make sure that a development agreement with the City has been completed. See
John Millar the Public Works Director concerning this.
5. Please provide one van accessible handicap space as required by the ADA
Standards for Accessible Design section 4.1.2 paragraph 5(b).
6. Section 310.2.2 of the 1997 Uniform Building Code (UBC) requires that this
building be constructed with 1 hr. fire rated construction throughout. Provide 2 -hr.
fire wall(s) to separate the building or a sprinkler system as alternatives or show
details for 1hr. construction. Also the walls and ceiling in the exterior stair
structure must be Ihr. rated. This will require 5/8" type "X" drywall to be used as
sheathing. The doors to the units must be 20 minute rated assemblies.
7. Foundation reinforcement does not meet Section 1914.3.5 of the 1997 Uniform
Building Code (UBC).
8. Please provide details showing location of three units to be constructed as a type
"A" unit as per Section 1103.1.9.3 of the 1997 UBC.
9. Type "A" accessible units require a lowered kitchen work space and removable
cabinet fronts. Please indicate on plans.
10. Please make note of operating controls to meet UBC Section 1106.3 for all
accessible units.
11. Please provide truss details prior to frame inspection.
12. The Fire Department has finished their review and has requested some changes. I
have attached a copy of this review to the back of this document.
Please make the necessary changes and return two sets of revised drawings to us.
If you have any questions I can be reached at (208) 359-3020 extension 324.
Sincerely
Val Christensen
Building Official
cc John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(2 08) 359-3010
1997 Uniform Fire Code Plan Date: 8-5-02
Plan Review Review Date: 8-16-02
Building Name: STONE BROOK APARTMENTS
Building Address: PIONEER ROAD AND MARIAN DRIVE
Stories: 2.5 Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 9,000 SQUARE FEET PER
BUILDING
1).Required Fire Flow (Appendix III -A): 2500 GPM FOR TWO HOURS PER
BUILDING
Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED BY 75% IF EACH
BUILDING HAS AN APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: NONE
Fire Hydrant Flows: NONE
Fire Flow Test Location: NONE
Fire Flow Supplied By: NONE
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO
Water Supply Comments: EACH BUILDING SHALL HAVE A MINIMUM OF TWO
HYDRANTS WITHIN 450 FEET CAPABLE OF SUPPLYING THE REQUIRED FIRE
FLOW. PRIOR TO CONSTRUCTION PLEASE SUPPLY FIRE DEPARTMENT WITH AN
ENGINEERS ESTIMATE OF WATER FLOW FROM EACH PROPOSED HYDRANT.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES Length: YES
Complete Road Acceptable: YES
Comments: NONE
4).Access Roads and water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: MINIMUM SIZE OF 2A10BC REQUIRED IN EACH
UNIT
Comments: TO BE MOUNTED ON A WALL IN EACH KITCHEN AREA
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: NO
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments:
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: X Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System Shown: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: HANDICAPPED UNITS SHALL HAVE HORN/STROBE UNITS THROUGHOUT
IN ADDITION TO SMOKE DETECTORS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: NO, PLEASE ADDRESS ABOVE ITEMS.
I HAVE MET WITH THE CONTRACTOR AND MADE HIM AWARE OF THE NOTED
ITEMS.
Plans Checked By: CHRIS
Date: 8-16-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: X New Plans: X