HomeMy WebLinkAboutPLAN REVIEWS - 02-00053 - Green Gables II - Three 4-PlexesP.O. Box 280 cily ��`s' «. �o rf/i�l�� 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 STATE OF IDAHO Fax (208) 359-3022 `r Kt� www.cLrexburgJd.us e-mail rexburg@ci.rexburg.id.us 8/20/2002 Stan Palmer 2916 W 17'h South Idaho Falls, Idaho 83404 Dear Dean, I have reviewed the plans for the Randy Webb Apartments and have identified the following discrepancies, additions yr questions: 1. Identify that setbacks are to eaves. 2. Identify right-of-way lines. 3. Get with John Millar the City of Rexburg Public Works Director and work out a Development Agreement. 4. Provide details of handicap parking space aisles where they connect to sidewalk and accessible route into the buildings. 5. Identify trash facilities. 6. Provide minimum foundation reinforcement as per Section 1914.3.5 of the 1997 Uniform Building Code (UBC). 7. All units on the lower level must be constructed as "Type B" units as per Section 1103.1.9.3 of the UBC. Identify as such. Please identify grab bar backing, accessible thresholds and all other accessible features. 8. Please identify smoke detectors as per the UBC and 2A-10BC fire extinguishers in each apartment unit. Smoke detectors are required in each bedroom 9. Identify that bedroom windows must meet egress as per UBC Section 310.4. Identify the type of windows being provided, The plans show 4' wide by 3' high windows. Sliders in this size will not meet the minimum requirements of the UBC. If the windows are a casement variety where the whole window opens, please identify a maximum sill height. If the windows are set at header height the sill will probably not meet code. 10. Please identify firewall construction, including draftstops if used. Unit separation must be maintained from foundation to roof sheathing. Please provide details in crawl space and attic also. 11. Please identify fire separation at the floors between units. Engineered joists have their own requirements for fire protection and are not listed in the UBC. Please provide this information on the plans. One layer of drywall will not meet manufactures minimum fire requirements for engineered floor joists. Please obtain manufacture's information for fire resistance. 12. The Building Section on sheet A-5 identifies ''/z" drywall on the upper ceiling. When trusses are placed on 24" centers, 5/8" drywall is required on ceilings. 13. On sheet A-5 the Building Section identifies that the floor sheathing is to be fastened with screws. This practice is not typical. Is it a structural requirement? If it is required, I will enforce it in the field. 14. Please identify crawl space vent locations to meet requirements of the UBC. Also identify attic ventilation to meet requirements of the UBC. 15. Please submit a copy of your plans to the State of Idaho Electrical Bureau. 16. I have attached a copy of the Fire Department review to the back of this document. Please resolve any issues identified by them. Please provide me with 2 new copies of any corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerer Val Christensen Building Official C.C. John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 5-01 Plan Review Review Date: 8-6-02 Building Name: RANDY WEBB/KARL AND CHRIS PETERSON APARTMENTS Building Address: PIONEER ROAD Stories: TWO Type of Construction: V -N Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 2944 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 1500 GPM/TWO HOURS Comments: NONE 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: OKAY Fire Hydrant Flows: UNKNOWN Fire Flow Test Location: N/A Fire Flow Supplied By: N/A Other Approved Water Source: NONE Water Supply Acceptable: SEE COMMENTS Fire Hydrant Location Acceptable: YES Water Supply Comments: PLEASE PROVIDE ESTIMATE OF WATER FLOW FROM NEW HYDRANT PRIOR TO CONSTRUCTION. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: X Length: X Surface: X Turning Radius: X Grade: X Vehicle Vertical: Clearance: Turn Arounds: X Complete Road Acceptable: YES Comments: NONE 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: SEE COMMENTS Comments: PROVIDE ONE FIRE EXTINGUISHER IN EACH UNIT, MINIMUM SIZE OF 2A10BC EACH. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: S).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: X Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System: Smoke Detectors: X Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: ALL SLEEPING ROOMS AND CORRIDORS SHALL BE PROVIDED WITH SMOKE DETECTORS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: NONE Plans As Submitted Are Acceptable: YES, PLEASE ADDRESS ABOVE ITEMS. Plans Checked By: CHRIS HUSXINSON Date: 8-6-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: