8/20/2002
Stan Palmer
2916 W 17'h South
Idaho Falls, Idaho 83404
Dear Dean,
I have reviewed the plans for the Randy Webb Apartments and have identified the
following discrepancies, additions yr questions:
1. Identify that setbacks are to eaves.
2. Identify right-of-way lines.
3. Get with John Millar the City of Rexburg Public Works Director and work
out a Development Agreement.
4. Provide details of handicap parking space aisles where they connect to
sidewalk and accessible route into the buildings.
5. Identify trash facilities.
6. Provide minimum foundation reinforcement as per Section 1914.3.5 of the
1997 Uniform Building Code (UBC).
7. All units on the lower level must be constructed as "Type B" units as per
Section 1103.1.9.3 of the UBC. Identify as such. Please identify grab bar
backing, accessible thresholds and all other accessible features.
8. Please identify smoke detectors as per the UBC and 2A-10BC fire
extinguishers in each apartment unit. Smoke detectors are required in
each bedroom
9. Identify that bedroom windows must meet egress as per UBC Section
310.4. Identify the type of windows being provided, The plans show 4'
wide by 3' high windows. Sliders in this size will not meet the minimum
requirements of the UBC. If the windows are a casement variety where
the whole window opens, please identify a maximum sill height. If the
windows are set at header height the sill will probably not meet code.
10. Please identify firewall construction, including draftstops if used. Unit
separation must be maintained from foundation to roof sheathing. Please
provide details in crawl space and attic also.
11. Please identify fire separation at the floors between units. Engineered
joists have their own requirements for fire protection and are not listed in
the UBC. Please provide this information on the plans. One layer of
drywall will not meet manufactures minimum fire requirements for
engineered floor joists. Please obtain manufacture's information for fire
resistance.
12. The Building Section on sheet A-5 identifies ''/z" drywall on the upper
ceiling. When trusses are placed on 24" centers, 5/8" drywall is required
on ceilings.
13. On sheet A-5 the Building Section identifies that the floor sheathing is to
be fastened with screws. This practice is not typical. Is it a structural
requirement? If it is required, I will enforce it in the field.
14. Please identify crawl space vent locations to meet requirements of the
UBC. Also identify attic ventilation to meet requirements of the UBC.
15. Please submit a copy of your plans to the State of Idaho Electrical Bureau.
16. I have attached a copy of the Fire Department review to the back of this
document. Please resolve any issues identified by them.
Please provide me with 2 new copies of any corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerer
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 5-01
Plan Review Review Date: 8-6-02
Building Name: RANDY WEBB/KARL AND CHRIS PETERSON APARTMENTS
Building Address: PIONEER ROAD
Stories: TWO Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 2944 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 1500 GPM/TWO HOURS
Comments: NONE
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: OKAY
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLEASE PROVIDE ESTIMATE OF WATER FLOW FROM
NEW HYDRANT PRIOR TO CONSTRUCTION.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: X Length: X Surface: X
Turning Radius: X Grade: X Vehicle Vertical:
Clearance: Turn Arounds: X
Complete Road Acceptable: YES
Comments: NONE
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO
CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: SEE COMMENTS
Comments: PROVIDE ONE FIRE EXTINGUISHER IN EACH UNIT, MINIMUM SIZE
OF 2A10BC EACH.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required: Comments:
S).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: X Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: ALL SLEEPING ROOMS AND CORRIDORS SHALL BE PROVIDED WITH
SMOKE DETECTORS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: NONE
Plans As Submitted Are Acceptable: YES, PLEASE ADDRESS ABOVE ITEMS.
Plans Checked By: CHRIS HUSXINSON Date: 8-6-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: X New Plans: