I have reviewed the drawings for the Parkside Clubhouse and have identified the following
deficiencies:
1. A new site plan was not provided with the drawing. Provide handicapped parking
and identify the accessible route from the building to the handicapped spaces and
to the pedestrian walks. Identify dimensions from the building to the other
buildings and to the property line.
2. The plans must be stamped by a licensed professional as per the 2000 International
Building Code (IBC) Section 106.1. Provide structural calculations.
3. Submit manufacturer's certificate of compliance for all components as per IBC
Section 1621.3.5.
4. Provide 1 hr. separation between the pool equipment room and the rest of the
building. Identify the door to this room as a fire rated door.
5. Identify exit signs.
6. Please provide truss details before framing inspection.
7. Energy calculations are required as per the 2000 International Energy
Conservation Code.
8. The energy code compliance documents that you provided me for the Rexburg,
Idaho Parkside Clubhouse are for Spanish Fork Utah and were created using an
outdated software. Please provide a new checklist using COM Check (available at
energycodes.com). Be sure to pick the 2000 IECC and Rexburg, Idaho from the
drop down lists.
9. I have attached a copy of the Fire Department review to the back of this
document. Please resolve any issues identified by them.
Please provide me with 2 new copies of corrected plans. If you have any questions, please
give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
E7 BUq
ora ��a /f /f P.O. Bax 280
rc o Q f;/// 0�/ ex l(�QQr y 12 North Center Street
CY Q / // Rexburg, Idaho 83440
" n Phone (208) 359.3020
STATE OF IDAHO Fax (208) 359-3022
TgeG1SHE0 , e-mail rexburg@srv.net
REXBUJ? G -MADISON COUNTY
EMERGENCYSERVICES
26 NORTH CENTER STREET
REXBURG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code Plan Date: UNKNOWN
Plan Review Review Date: 10-5-03
Building Name: GEORGETOWN CLUBHOUSE
Building Address: UNKNOWN
Stories: ONE Type of Construction: V -B
Occupancy Classification: A-3 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 4,500 SQUARE FEET
1. Required Fire Flow (Appendix B): 1750 GPM/TWO HOURS
Comments: FIRE FLOW MAY BE REDUCED IF STRUCTURE HAS AN
APPROVED AUTOMATIC FIRE SUPPRESSION SYSTEM INSTALLED.
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: TWO PROPOSED HYDRANTS
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO
Water Supply Comments: UNKNOWN HYDRANT FLOW, PLEASE PROVIDE
ENGINEERS CALCULATION FOR FLOWS. UNCLEAR OF HYDRANT
LOCATIONS, PLEASE PROVIDE IMPROVED SITE PLAN.
3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: NO
Complete Road Acceptable: NO
Length: NO Surface: OK
Comments: NO SITE PLAN INCLUDED WITH BUILDING PLANS.
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required: YES
Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN
Comments: NEED TO PROVIDE MINIMUM OF 2AI0BC EXTINGUISHER IN
KITCHEN AREA, AT LEAST TWO OTHERS IN BUILDING WITHIN TRAVEL
DISTANCES.
6. Automatic fire extinguishing systems (Section 903) Required: NO
Type of system being installed: NOT SHOWN
Sprinkler system monitoring (Section 907) required:
Comments: NONE
7. Standpipes (Section 905) required: NO
Type required: Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
Type being provided:
Automatic fuel shut-off required:
Portable fire extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: YES
Type of system required: Manual: Automatic: X Both:
Type of system being provided: Manual: Automatic: Both:
Components of system shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring:
Fire Alarm System Acceptable: NO, SMOKE DETECTORS ARE REQUIRED IN
OCCUPANCY.
10. Other corrections that are required by special occupancy or conditions:
Plans as submitted are acceptable: NO
Plans checked by: CHRIS HUSKINSON Date: 10-5-03
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: X