HomeMy WebLinkAboutPLAN REVIEWS - 02-00085 - One Stop Auto12/3/2002 Scott Spaulding Design Intelligence 3685 E Hwy. 33 Rexburg, Idaho 83440 Dear Scott, U// STATE OF IDAHO O// www.ci.rexburaJd.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the One Stop Auto drawings that you have provided me and have identified the following discrepancies: 1. Get with John Millar the City of Rexburg Public Facilities Coordinator for a Development Agreement. 2. Please identify a handicapped parking space with a five foot wide access aisle on site plan. 3. Dimension parking spaces. 4. Identify Right -Of -Way on both streets and the distances from the buildings to the Right -Of -Way on the site plan. 5. The site plan is very hard to read. The notes are not legible and are spaced at uneven intervals. 6. Please identify the East property line. If the building is within 20' of the East property line, identify 1 hour construction at roof. Or, if an access easement is located at the East of the building and is wide enough to provide the 20' wide property separation, please identify on plans and provide a copy of the agreement for our records. 7. The parapet on the South side of the building will not meet code. The parapet must be 30" above the roof at all points. An alternative to the parapet is to construct the roof as one-hour system for 5' from inside the cmu wall. Either way, please provide us with details. 8. Provide access approach details that identify 6" thick concrete with #4 rebar at 18" o.c. in both directions. 9. Please identify the size of furnace. 10. The drawings identify the Seismic Zone as 213. We are located in Seismic Zone 3. If any calculations for the structure have been created using 2B equations, please make the necessary changes. 11. Please identify all footings as being a minimum of 36" below grade for frost protection. 12. The Fire Department has reviewed the plans. I have attached a copy of there report to the back of this document. Please provide the necessary information they have requested. Please return two sets of revised plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 east. 324. Sincerely, Val Christensen Building Official cc John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Review Plan Date: 11-11-02 Review Date: 11-17-02 Building Name: ONE STOP AUTO Building Address: 21D EAST & 700 NORTH Stories: ONE Type of Construction: V -N Occupancy Classification: M Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 3,000 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 1,500 GPM/TWO HOURS Comments: NONE 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: SECOND EAST AND 700 NORTH Fire Hydrant Flows: OIC Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: NONE 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: YES Grade: YES Clearance: YES Turn Arounds: YES Complete Road Acceptable: YES 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: MINIMUM OF 2A10BC EXTINGUISHER REQUIRED IN EACH AREA 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: NO Comments: 8).Fire Alarm Systems (Article 10 Section 1007)Required: NO Type Of System Required: Manual: Automatic: Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System Shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: NO Duct Detectors: NO Fire Alarm System Acceptable: N/A 10).Other Corrections That Are Required By Special Occupancy Or Conditions/Comments: Plans As Submitted Are Acceptable: YES Plans Checked By: CHRIS HUSKINSON Date: 11-17-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: New Plans: