Loading...
HomeMy WebLinkAboutPLAN REVIEW - 02-00022 - BYUI Austin Bldg - Addition9/9/2002 Jed Walker CRS Architects P.O. Box 2421 Idaho Falls, ID 83403-2421 Dear Jed, edy 012exiary STATE OF IDAHO www.cLrexburg.jd.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg,id.us I have reviewed the drawings for the Mark Austin Building Phase 2 and have identified the following discrepancies or questions: 1. How is handicapped parking being addressed? The new addition identifies 176 new occupants and would require at minimum an additional 44 parking spaces. The ADA Standards for Accessible Design Section 4.1.2 requires that 2 handicapped parking spaces. be provided. These spaces should be close to the building and located off an accessible exit and route. 2. Section 1103.2.3 of the 1997 Uniform Building Code (UBC) requires that 50% of all entrances be handicapped accessible. With, the addition, the entire building has 5 main entries and many more entrances out of individual rooms. The new configuration would require at least 3 accessible entrances. Section 1104. 1.1 of the UBC states "When more than one exit or exit -access door is required from any accessible space, each accessible space shall be served by not more than two accessible means of egress". In order to meet the requirements of this section of the code, the existing building's handicapped exit must be used. This puts additional weight on the need to review the entire building's egress system to today's code and therefore, drives the need for 3 handicapped entrances versus the 2 shown. 3. The code compliance page identifies the woodworking lab's exits serving 89 occupants. The two exits required are too close to comply with the '/2 the diagonal distance rule. The woodworking environment combined with a finishing room creates an egress concern. An outside exit to this room is needed. 4. Sheet S501 does not contain Detail D5 as identified on Sheet S 1.01. 5. Are existing hallways constructed in a manner to allow them to be used as corridors by today's code? 6. Stair sections identify 10" runs or treads. Section 100 1.3.3 of the UBC requires a minimum stair run of 11". 7. Please see the Fire Department review that I have attached to the back of this document. Please look into the above items and return two copies of any changes to me at City Hall. Thank you for your cooperation in this matter. If you have any questions please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official cc: John Millar Chris Huskinson Bill Hamlin Rulon Neilsen REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Review Plan Date: 7-15-02 Review Date: 7-19-02 Building Name: AUSTIN BUILDING PHASE TWO, BYU-I Building Address: BYU-I CAMPUS Stories: TWO Type of Construction: II -FR Occupancy Classification: E-2 SQUARE FEET New Construction Floor Area: ***** Existing Floor Area: 68,890 1).Required Fire Flow (Appendix III -A): 2750 GPM/TWO HOURS Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED BY 75% IF ENTIRE BUILDING HAS AN APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: C-48, C-41 Fire Hydrant Flows: OKAY Fire Flow Test Location: SAME AS ABOVE Fire Flow Supplied By: BYU-I/CITY Other Approved Water Source: YES Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: YES 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: YES Grade: YES Vehicle Vertical: YES Clearance: YES Turn Arounds: N/A Complete Road Acceptable: YES Comments: NONE 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: PLEASE PROVIDE ACCESS TO BUILDING DURING CONSTRUCTION PHASE. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: PLEASE PROVIDE MINIMUM OF 2A10BC EVERY 75 FEET OF TRAVEL DISTANCE. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: YES Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: YES Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: Both: X Type Of System Being Provided: Manual: Automatic: Both: X Components Of System Shown: Smoke Detectors: X Heat Detectors: X Manual Pull Station: X Sounding Devices: X Visual Devices: X Door Holders: X Duct Detectors: X Flow Alarm: X Sprinkler Valve Monitoring: X Fire Alarm System Acceptable: NO, SEE COMMENTS BELOW 9).Other Corrections That Are Required By Special Occupancy Or Conditions: PLEASE ADDRESS THE FOLLOWING ITEMS: 1. SPRINKLER SYSTEM- IT IS MY UNDERSTANDING THE BASEMENT, SECOND FLOOR AND THE NEW ADDITION WILL BE FULLY SPRINKLERED. WHAT IS THE TIME FRAME TO COMPLETE THE ENTIRE BUILDING? PLEASE PROVIDE DETIALS IN WRITING TO THIS OFFICE. 2. FIRE ALARM SYSTEM- PLEASE REPLACE ALL STROBE NOTIFICATION DEVICES THROUGHOUT FACILITY WITH HORN/STROBE COMBINATION UNITS. I WOULD ALSO LIKE TO MEET WITH A REPRESENTATIVE TO DISCUSS THE PLACEMENT OF ALL DEVICES AND PULL STATIONS. ALSO PROVIDE ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS, CONDUDUCTOR TYPE AND SIZES, MANUFACTURERS MODEL NUMBERS AND LISTING INFORMATION FOR ALL EQUIPMENT, DEVICES AND MATERIALS, AND THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. Plans As Submitted Are Acceptable: YES, WITH ABOVE ITEMS ADDRESSED Plans Checked By: CHRIS HUSKINSON Date: 07-19-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: New Plans: