HomeMy WebLinkAboutFIRE PLAN REVIEWS - 02-00042 - Main Street Station Apartments5/23/2002
Tom Wilson
Wilson Architectural
1403 Broadway
Boise, Idaho 83706
Dear Tom,
STATE OF IDAHO
www.ci.rexburgJd.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburg.id.us
I have reviewed the Main Street Station drawings that you have provided me and
have identified the following discrepancies -
1. A fence or a suitable buffer must be provided between parking areas and other
residential properties. Please provide fence or buffer at the East side of the
project along parking lot.
2. Turn the trash dumpsters so that our side loading truckscanaccess them
without having to back up.
3. The Fire Department has marked fire lanes onto page S-2 of the drawings that
I will return to you as your "approved set". I have attached a copy of the Fire
Department review to the back of this document. Please contact Chris
Huskinson at (208) 359-3010 in you have any questions concerning the Fire
Department review.
4. The 1997 Uniform Building Code (UBC) section 1103.1.9.3 requires all grade
level dwelling units to be Type "B" Dwelling Units. Please indicate this on
plans.
5. The entry balcony of the 3 -bedroom "A" unit must be constructed as per the
1997 Uniform Building Code (UBC) section 1006.3.2.3. This section requires
the walls around the entrance balcony and the ceiling to be one hour rated.
The code requires this when the occupancy of the exit is more than 10
persons. 3-bedroomunits are frequently occupied by 6 persons.
6. Detail 6 on page A-10 does not show fire separation in the crawl space. The
fire separation between the units must be maintained throughout. The pony
walls in the crawl space and up to floor decking must be fire rocked.
7. Provide truss manufacturer specifications and detail sheets. I will need these
prior to framing inspection.
8. Please provide information identifying minimum foundation reinforcement as
per UBC section 1914.3.3.
Please provide me with two copies of any changes that are made to the plans. Let
me know if I can be of any further assistance. If you have any questions, please give me
a call at 359-3020 ext. 324.
Sincerely,
.0
Val Christensen
Building Official
cc John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 4-15-02
Plan Review Review Date: 4-30-02
Building Name: MAIN STREET STATION
Building Address: MAIN STREET BETWEEN 4Tx AND 5TN WEST
Stories: 2 Type of Construction: V -N
Occupancy Classification: R-1, B Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 5,800 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS
Comments: FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING IS EQUIPPED
WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM TO NO LESS THAN 1,500
GPM.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: A-6, A-5, A-11
Fire Hydrant Flows: OK
Fire Flow Test Location: A-6, A-5, A-11
Fire Flow Supplied By: FD
Other Approved Water Source: NONE
Water Supply Acceptable: NO, SEE COMMENTS
Fire Hydrant Location Acceptable: NONE SHOWN ON PLANS
Water Supply Comments: EXISTING HYDRANTS ARE TOO FAR AWAY TO BE
UTILIZED. PROPOSED SITE PLAN SHOWS NO NEW HYDRANTS. DEVELOPMENT
SHALL HAVE TWO HYRDANTS WITHIN 450 FEET OF EACH BUILDING.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES Length: YES Surface: YES
Turning Radius: YES Grade: OK Vehicle Vertical: YES
Clearance: OR Turn Arounds: N/A
Complete Road Acceptable: YES
Comments: NORTH SIDE OF PROPERTY SHOWS A 20 -FOOT WIDE ROAD EXITING
THE PROPERTY. THIS ROAD TO BE SIGNED AND CURBS PAINTED RED FOR FIRE
APPARATUS ACCESS. AREAS MARKED IN RED ON SITE PLAN S-2 INDICATE
FIRE LANE TO BE SIGNED AND WITH THE CURBS PAINTED RED.
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Comments: PROVIDE AT LEAST ONE EXTINGUISHER PER UNIT, MINIMUM SIZE
OF 2A10BC. CLUBHOUSE ALSO NEEDS TO BE PROVIDED WITH ONE FIRE
EXTINGUISHER PER AREA.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: UNKNOWN
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments: IN COMMUNITY BUILDING PLANS INDICATE A KITCHEN, NEED MORE
INFORMATION OF COOKING FACILITIES TO BE PROVIDED.
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: YES Both:
Type Of System Being Provided: Manual: Automatic: YES Both:
Components Shown: Smoke Detectors: YES Heat Detectors: NO
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: SMOKE AND HEAT DETECTORS REQUIRED IN COMMON AREAS SUCH AS
LAUNDRIES, RECREATION ROOMS, MECHANICAL ROOMS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: HANDICAPPED UNITS INDICATED, IF TYPE � 4 MUST BE
PROVIDED WITH HORN/STROBE UNITS THROUGHOUT IN ADDITION TO SMOKE
DETECTORS.
Plans As Submitted Are Acceptable: NO
Plans Checked By: CHRIS HUSKINSON Date: 4-30-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES
5/23/2002
Tom Wilson
Wilson Architectural
1403 Broadway
Boise, Idaho 83706
Dear Tom,
STATE OF IDAHO
www.drexburg.id.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg®ci.rexburg.id.us
I have reviewed the Main Street Station drawings that you have provided me and
have identified the following discrepancies -
1. A fence or a suitable buffer must be provided between parking areas and other
residential properties. Please provide fence or buffer at the East side of the
project along parking lot.
2. Turn the trash dumpsters so that our side loading truckscanaccess them
without having to back up.
3. The Fire Department has marked fire lanes onto page S-2 of the drawings that
I will return to you as your "approved set". I have attached a copy of the Fire
Department review to the back of this document. Please contact Chris
Huskinson at (208) 359-3010 in you have any questions concerning the Fire
Department review.
4. The 1997 Uniform Building Code (UBC) section 1103.1.9.3 requires all grade
level dwelling units to be Type "B" Dwelling Units. Please indicate this on
plans.
5. The entry balcony of the 3 -bedroom "A" unit must be constructed as per the
1997 Uniform Building Code (UBC) section 1006.3.2.3. This section requires
the walls around the entrance balcony and the ceiling to be one-hour rated.
The code requires this when the occupancy of the exit is more than 10
persons. 3 -bedroom -units are frequently occupied by 6 persons.
6. Detail 6 on page A-10 does not show fire separation in the crawl space. The
fire separation between the units must be maintained throughout. The pony
walls in the crawl space and up to floor decking must be fire rocked.
7. Provide truss manufacturer specifications and detail sheets. I will need these
prior to framing inspection.
8. Please provide information identifying minimum foundation reinforcement as
per UBC section 1914.3.3.
Please provide me with two copies of any changes that are made to the plans. Let
me know if I can be of any further assistance. If you have any questions, please give me
a call at 359-3020 ext. 324.
Sinnccer/ely,
Val Christensen
Building Official
cc John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(2 08) 359-3010
1997 Uniform Fire Code Plan Date: 4-15-02
Plan Review Review Date: 4-30-02
Building Name: MAIN STREET STATION
Building Address: MAIN STREET BETWEEN CH AND 5" WEST
Stories: 2 Type of Construction: V -N
Occupancy Classification: R-1, B Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 5,800 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS
Comments: FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING IS EQUIPPED
WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM TO NO LESS THAN 1,500
GPM.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: A-6, A-5, A-11
Fire Hydrant Flows: OR
Fire Flow Test Location: A-6, A-5, A-11
Fire Flow Supplied By: FD
Other Approved Water Source: NONE
Water Supply Acceptable: NO, SEE COMMENTS
Fire Hydrant Location Acceptable: NONE SHOWN ON PLANS
Water Supply Comments: EXISTING HYDRANTS ARE TOO FAR AWAY TO BE
UTILIZED. PROPOSED SITE PLAN SHOWS NO NEW HYDRANTS. DEVELOPMENT
SHALL HAVE TWO HYRDANTS WITHIN 450 FEET OF EACH BUILDING.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES Length: YES Surface: YES
Turning Radius: YES Grade: OK Vehicle Vertical: YES
Clearance: OK Turn Arounds: N/A
Complete Road Acceptable: YES
Comments: NORTH SIDE OF PROPERTY SHOWS A 20 -FOOT WIDE ROAD EXITING
THE PROPERTY. THIS ROAD TO BE SIGNED AND CURBS PAINTED RED FOR FIRE
APPARATUS ACCESS. AREAS MARKED IN RED ON SITE PLAN S-2 INDICATE
FIRE LANE TO BE SIGNED AND WITH THE CURBS PAINTED RED.
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Comments: PROVIDE AT LEAST ONE EXTINGUISHER PER UNIT, MINIMUM SIZE
OF 2A10BC. CLUBHOUSE ALSO NEEDS TO BE PROVIDED WITH ONE FIRE
EXTINGUISHER PER AREA.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: UNKNOWN
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments: IN COMMUNITY BUILDING PLANS INDICATE A KITCHEN, NEED MORE
INFORMATION OF COOKING FACILITIES TO BE PROVIDED.
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: YES Both:
Type Of System Being Provided: Manual: Automatic: YES Both:
Components Shown: Smoke Detectors: YES Heat Detectors: NO
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: SMOKE AND HEAT DETECTORS REQUIRED IN COMMON AREAS SUCH AS
LAUNDRIES, RECREATION ROOMS, MECHANICAL ROOMS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: HANDICAPPED UNITS INDICATED, IF TYPE � 4 MUST BE
PROVIDED WITH HORN/STROBE UNITS THROUGHOUT IN ADDITION TO SMOKE
DETECTORS.
Plans As Submitted Are Acceptable: NO
Plans Checked By: CHRIS HUSKINSON Date: 4-30-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES