HomeMy WebLinkAboutFIRE PLAN REVIEWS - 02-00042 - Main Street Station Apartments5/23/2002 Tom Wilson Wilson Architectural 1403 Broadway Boise, Idaho 83706 Dear Tom, STATE OF IDAHO www.ci.rexburgJd.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the Main Street Station drawings that you have provided me and have identified the following discrepancies - 1. A fence or a suitable buffer must be provided between parking areas and other residential properties. Please provide fence or buffer at the East side of the project along parking lot. 2. Turn the trash dumpsters so that our side loading truckscanaccess them without having to back up. 3. The Fire Department has marked fire lanes onto page S-2 of the drawings that I will return to you as your "approved set". I have attached a copy of the Fire Department review to the back of this document. Please contact Chris Huskinson at (208) 359-3010 in you have any questions concerning the Fire Department review. 4. The 1997 Uniform Building Code (UBC) section 1103.1.9.3 requires all grade level dwelling units to be Type "B" Dwelling Units. Please indicate this on plans. 5. The entry balcony of the 3 -bedroom "A" unit must be constructed as per the 1997 Uniform Building Code (UBC) section 1006.3.2.3. This section requires the walls around the entrance balcony and the ceiling to be one hour rated. The code requires this when the occupancy of the exit is more than 10 persons. 3-bedroomunits are frequently occupied by 6 persons. 6. Detail 6 on page A-10 does not show fire separation in the crawl space. The fire separation between the units must be maintained throughout. The pony walls in the crawl space and up to floor decking must be fire rocked. 7. Provide truss manufacturer specifications and detail sheets. I will need these prior to framing inspection. 8. Please provide information identifying minimum foundation reinforcement as per UBC section 1914.3.3. Please provide me with two copies of any changes that are made to the plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, .0 Val Christensen Building Official cc John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 4-15-02 Plan Review Review Date: 4-30-02 Building Name: MAIN STREET STATION Building Address: MAIN STREET BETWEEN 4Tx AND 5TN WEST Stories: 2 Type of Construction: V -N Occupancy Classification: R-1, B Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 5,800 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS Comments: FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING IS EQUIPPED WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM TO NO LESS THAN 1,500 GPM. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: A-6, A-5, A-11 Fire Hydrant Flows: OK Fire Flow Test Location: A-6, A-5, A-11 Fire Flow Supplied By: FD Other Approved Water Source: NONE Water Supply Acceptable: NO, SEE COMMENTS Fire Hydrant Location Acceptable: NONE SHOWN ON PLANS Water Supply Comments: EXISTING HYDRANTS ARE TOO FAR AWAY TO BE UTILIZED. PROPOSED SITE PLAN SHOWS NO NEW HYDRANTS. DEVELOPMENT SHALL HAVE TWO HYRDANTS WITHIN 450 FEET OF EACH BUILDING. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: YES Grade: OK Vehicle Vertical: YES Clearance: OR Turn Arounds: N/A Complete Road Acceptable: YES Comments: NORTH SIDE OF PROPERTY SHOWS A 20 -FOOT WIDE ROAD EXITING THE PROPERTY. THIS ROAD TO BE SIGNED AND CURBS PAINTED RED FOR FIRE APPARATUS ACCESS. AREAS MARKED IN RED ON SITE PLAN S-2 INDICATE FIRE LANE TO BE SIGNED AND WITH THE CURBS PAINTED RED. 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: PROVIDE AT LEAST ONE EXTINGUISHER PER UNIT, MINIMUM SIZE OF 2A10BC. CLUBHOUSE ALSO NEEDS TO BE PROVIDED WITH ONE FIRE EXTINGUISHER PER AREA. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: UNKNOWN Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments: IN COMMUNITY BUILDING PLANS INDICATE A KITCHEN, NEED MORE INFORMATION OF COOKING FACILITIES TO BE PROVIDED. 9).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: YES Both: Type Of System Being Provided: Manual: Automatic: YES Both: Components Shown: Smoke Detectors: YES Heat Detectors: NO Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: SMOKE AND HEAT DETECTORS REQUIRED IN COMMON AREAS SUCH AS LAUNDRIES, RECREATION ROOMS, MECHANICAL ROOMS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: HANDICAPPED UNITS INDICATED, IF TYPE � 4 MUST BE PROVIDED WITH HORN/STROBE UNITS THROUGHOUT IN ADDITION TO SMOKE DETECTORS. Plans As Submitted Are Acceptable: NO Plans Checked By: CHRIS HUSKINSON Date: 4-30-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: YES New Plans: YES 5/23/2002 Tom Wilson Wilson Architectural 1403 Broadway Boise, Idaho 83706 Dear Tom, STATE OF IDAHO www.drexburg.id.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg®ci.rexburg.id.us I have reviewed the Main Street Station drawings that you have provided me and have identified the following discrepancies - 1. A fence or a suitable buffer must be provided between parking areas and other residential properties. Please provide fence or buffer at the East side of the project along parking lot. 2. Turn the trash dumpsters so that our side loading truckscanaccess them without having to back up. 3. The Fire Department has marked fire lanes onto page S-2 of the drawings that I will return to you as your "approved set". I have attached a copy of the Fire Department review to the back of this document. Please contact Chris Huskinson at (208) 359-3010 in you have any questions concerning the Fire Department review. 4. The 1997 Uniform Building Code (UBC) section 1103.1.9.3 requires all grade level dwelling units to be Type "B" Dwelling Units. Please indicate this on plans. 5. The entry balcony of the 3 -bedroom "A" unit must be constructed as per the 1997 Uniform Building Code (UBC) section 1006.3.2.3. This section requires the walls around the entrance balcony and the ceiling to be one-hour rated. The code requires this when the occupancy of the exit is more than 10 persons. 3 -bedroom -units are frequently occupied by 6 persons. 6. Detail 6 on page A-10 does not show fire separation in the crawl space. The fire separation between the units must be maintained throughout. The pony walls in the crawl space and up to floor decking must be fire rocked. 7. Provide truss manufacturer specifications and detail sheets. I will need these prior to framing inspection. 8. Please provide information identifying minimum foundation reinforcement as per UBC section 1914.3.3. Please provide me with two copies of any changes that are made to the plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 ext. 324. Sinnccer/ely, Val Christensen Building Official cc John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (2 08) 359-3010 1997 Uniform Fire Code Plan Date: 4-15-02 Plan Review Review Date: 4-30-02 Building Name: MAIN STREET STATION Building Address: MAIN STREET BETWEEN CH AND 5" WEST Stories: 2 Type of Construction: V -N Occupancy Classification: R-1, B Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 5,800 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS Comments: FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING IS EQUIPPED WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM TO NO LESS THAN 1,500 GPM. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: A-6, A-5, A-11 Fire Hydrant Flows: OR Fire Flow Test Location: A-6, A-5, A-11 Fire Flow Supplied By: FD Other Approved Water Source: NONE Water Supply Acceptable: NO, SEE COMMENTS Fire Hydrant Location Acceptable: NONE SHOWN ON PLANS Water Supply Comments: EXISTING HYDRANTS ARE TOO FAR AWAY TO BE UTILIZED. PROPOSED SITE PLAN SHOWS NO NEW HYDRANTS. DEVELOPMENT SHALL HAVE TWO HYRDANTS WITHIN 450 FEET OF EACH BUILDING. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: YES Grade: OK Vehicle Vertical: YES Clearance: OK Turn Arounds: N/A Complete Road Acceptable: YES Comments: NORTH SIDE OF PROPERTY SHOWS A 20 -FOOT WIDE ROAD EXITING THE PROPERTY. THIS ROAD TO BE SIGNED AND CURBS PAINTED RED FOR FIRE APPARATUS ACCESS. AREAS MARKED IN RED ON SITE PLAN S-2 INDICATE FIRE LANE TO BE SIGNED AND WITH THE CURBS PAINTED RED. 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: PROVIDE AT LEAST ONE EXTINGUISHER PER UNIT, MINIMUM SIZE OF 2A10BC. CLUBHOUSE ALSO NEEDS TO BE PROVIDED WITH ONE FIRE EXTINGUISHER PER AREA. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: UNKNOWN Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments: IN COMMUNITY BUILDING PLANS INDICATE A KITCHEN, NEED MORE INFORMATION OF COOKING FACILITIES TO BE PROVIDED. 9).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: YES Both: Type Of System Being Provided: Manual: Automatic: YES Both: Components Shown: Smoke Detectors: YES Heat Detectors: NO Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: SMOKE AND HEAT DETECTORS REQUIRED IN COMMON AREAS SUCH AS LAUNDRIES, RECREATION ROOMS, MECHANICAL ROOMS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: HANDICAPPED UNITS INDICATED, IF TYPE � 4 MUST BE PROVIDED WITH HORN/STROBE UNITS THROUGHOUT IN ADDITION TO SMOKE DETECTORS. Plans As Submitted Are Acceptable: NO Plans Checked By: CHRIS HUSKINSON Date: 4-30-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: YES New Plans: YES