I have reviewed the Loren Stegelmeier Apartment drawings that were provided
me and have identified the following discrepancies:
1. Provide a handicapped parking space as per ICC/ANSI A117.1. The space
must have an access aisle adjacent to it.
2. The International Building Code (IBC) requires that the lower units be Type
"B" handicap adaptable units as per ICC/ANSI Al 17.1. The interior doors,
light switches, outlets, appliances, controls any many other items are required
to meet ICC/ANSI Al 17.1.
3. Provide a sidewalk to the public way. An accessible route is required from
the entrance of the Type `B" units to the public way as per the IBC Section
1104.3. With the current configuration, a ramp is required for accessibility.
Please provide details of the ramp, its handrails and guards.
4. Provide details for parking lot drainage.
5. Relocate trash dumpster. Our trash trucks are side loaders and need room to
pick up.
6. Identify one hour separation between the units. Call out type "X" sheetrock at
party walls and ceilings. Be aware that manufactured joists have different
drywall requirements than dimensional lumber. Identify on plans how the fire
separation between the upper and lower units is to be accomplished.
7. Be aware that plumbing in the party wall can cause many problems with the
integrity of the fire seperation. Plastic pipes can not penetrate the membrane
of the 1 -hour firewall unless they are properly constructed to do so. Special
fire resistive rings are required or special details that show metal parts
entering the membrane and all plastic remaining within the wall. Please show
details on plans.
8. Please identify the type and location of the furnace for each unit.
9. Please identify smoke detectors and fire extinguishers in each unit. Smoke
detectors are required in both bedrooms and also in the hall outside of the
bedrooms.
10. Please provide stair details. Include the rise and run along with guard rail and
handrail dimensions.
11. Provide structural calculations as per the 2000 IBC. Include seismic and wind
calculations for the Rexburg area. The drawings do not identify foundation
bolts or shear walls. Identify spacing of bolts and fastening procedure at shear
walls.
12. Who is the Design Professional of Responsible Charge as per IBC Section
106.3.4? If you are that individual, it is your duty for "reviewing and
coordinating submittal documents prepared by others".
13. The State of Idaho has adopted the 2000 International Energy Conservation
Code (IECC). Please provide energy calculations.
14. The Fire Department has reviewed the plans. I have attached a copy of their
report. Please provide the necessary information they have requested.
Please return two sets of revised plans and the necessary calculations. Let me
know if I can be of any further assistance. If you have any questions, please give me a
call at 359-3020 ext. 324.
Sincerely/
Val Christensen
Building Official
cc John Millar
Chris Huskinson
cily 0/ )? (exlmrf
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
REXBURG-MADISON COUNTY
EMERGENCYSER VICES
26 NORTH CENTER STREET
REXB URG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code Plan Date: 8-12-03
Plan Review Review Date: 9-5-03
Building Name: LOREN STEGELMEIER APARTMENTS
Building Address: OFF NORTH HIGHWAY 33, REXBURG
Stories: TWO Type of Construction: V -B
Occupancy Classification: R-2
Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 3700 SQUARE FEET
1. Required Fire Flow (Appendix B): 1750 GPM/TWO HOURS
Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED IF
AUTOMATIC FIRE SPRINKLER SYSTEM INSTALLED.
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: NONE USABLE
Fire Hydrant Flows: NONE
Fire Flow Test Location: NONE
Fire Flow Supplied By: NONE
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO
Water Supply Comments: NEAREST FIRE HYDRANT OVER Y2 MILE AWAY.
PROJECT REQUIRES A MINIMUM OF ONE HYDRANT WITHIN 500 FEET
OF PROPOSED STRUCTURE.
3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: OK Length: OK Surface: UNKNOWN
Complete Road Acceptable: NO
Comments: UNKNOWN ROAD SURFACE
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required: YES
Location shown: NO
Type provided acceptable: NOT SHOWN
Comments: PROVIDE MINIMUM 2A10BC FIRE EXTINGUISHER WITHIN
EACH UNIT
6. Automatic fire extinguishing systems (Section 903) Required: NO
Type of system being installed:
Sprinkler system monitoring (Section 907) required:
Comments:
7. Standpipes (Section 905) required: NO
Type required:
Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
U
Type being provided:
Automatic fuel shut-off required:
Portable fire extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: NO
Type of system required: Manual: Automatic: Both:
Type of system being provided: Manual: Automatic: Both:
Components of system shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring:
Fire Alarm System Acceptable:
10. Other corrections that are required by special occupancy or conditions: NO
Plans as submitted are acceptable: NO
Plans checked by: CHRIS HUSKTNSON Date: 9-5-03
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: X