I have reviewed the drawings for the Rexburg, Idaho Jack in the -Box and have identified
the following deficiencies:
1. The structural calculations use exposure `B" for wind design. I disagree with this
exposure. The prevailing winds come out of the West slightly from the South. As
you can see by the aerial photo that I have attached to the back of this document,
there is nothing but open field and river in the direction that the wind travels. The
exposure should be "C". Please have your structural engineer make the necessary
changes to the structural calculations and the drawings if required.
2. Please provide a Flood Elevation Certificate as required in the 2000 International
Building Code (IBC) Section 1612.5.
3. The soil investigation report identifies a layer of fill mixed with garbage covering
the building lot. If you will be over excavating and bringing in structural fill,
compaction density tests must be performed by a licensed testing firm Let us
know who will be performing these tests so that we can coordinate with them.
4. Submit manufacturer's certificate of compliance for all components as per IBC
Section 1-621.3.5.
5. Please provide energy calculations as per the 2000 International Energy
Conservation Cade.
6. The Fire Department has reviewed the plans. I have attached a copy of the report.
These items need to be addressed before issuance of a building permit. Please let me know
if you have any questions. I can be reached during the day at 359-3020 Ext. 324.
Sincerely,
olam//�K
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
RE
XBURG-MADISON COUNTY
EMERGENCYSERVICES
26 NORTH CENTER STREET
REXBURG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code Plan Date: JULY 1, 2003
Plan Review Review Date: JULY 7, 2003
Building Name: JACK IN THE BOX
Building Address: SECOND EAST AND FOURTH NORTH
Stories: ONE Type of Construction: V -B
Occupancy Classification: B Existing Floor Area: N/A
New Construction Floor Area: 2100 SQUARE FEET
1. Required Fire Flow (Appendix B): 1500 GPM FOR TWO HOURS
Comments: NONE
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: O'DELLS FURNITURE/STONERIDEG MOTOR SPORTS
Fire Hydrant Flows: OKAY
Fire Flow Test Location: AS ABOVE
Fire Flow Supplied By: FD
Other Approved Water Source: NONE
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLANS INDICATE EXISTING BUILDING ADJACENT
TO PROPSED STRUCTURE TO BE PROVIDED WITH ADDITIONAL FIRE
HYDRANT PROTECTION.....ARE THESE HYDRANTS GOING TO BE
INSTALLED NOW OR AT A LATER DATE? PLEASE ADDRESS PRIOR TO
CONSTRUCTION.
3, Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: OK
Complete Road Acceptable: YES
Comments: NONE
Length: OK Surface: OK
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required: YES
Location shown: U/K
Type provided acceptable: YES
Comments: PROVIDE A MINIMUM OF 2AIOBC IN PUBLIC AREA AND A 401KB
EXTINGUISHER IN KITCHEN AREA.
6. Automatic fire extinguishing systems (Section 903) Required: NO
Type of system being installed:
Sprinkler system monitoring (Section 907) required:
Comments:
7. Standpipes (Section 905) required: NO
Type required:
Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: YES
Type being provided: ANSUL
Automatic fuel shut-off required: YES
Portable fire extinguisher shown: YES
Comments: ANSUL SYSTEM SHALL BE FULLY TESTED IN PRESENCE OF
FIRE INSPECTOR BEFORE OCCUPANCY.
9. Fire alarm systems (Section 907) required: NO
Type of system required: Manual: Automatic: Both:
Type of system being provided: Manual: Automatic: Both:
Components of system shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring:
Fire Alarm System Acceptable:
10. Other corrections that are required by special occupancy or conditions: NONE
Plans as submitted are acceptable: YES
Plans checked by: CHRIS HUSKINSON Date: 7-07-03
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: