I have reviewed the plans for the Level 2, 3 and 4 Apartments and have identified
the following discrepancies or questions:
1. Five parking spaces needed for ordinance compliance are missing from Level
4 plan. Please make the necessary changes.
2. Level 4 and Level 2 have dead end parking spaces. These spaces are not
equipped a backing area adjacent to them The vehicles that park in these
spaces will have to back completely out the way they came in. Please make
the necessary changes to the parking plan.
3. The ADA requires that one of your handicapped parking spaces. in each
complex be a van accessible space. The aisle adjacent to a van accessible
space is required to be 96" wide. Please identify compact spaces and signage
on plans.
4. Our trash truck is a side loading variety. The trash dumpster for Level 3 may
not be located where it can feasibly be accessed. Please contact John Millar
the City Engineer concerning this issue. His telephone extension is 329.
5. Please identify privacy fencing where parking lots border other properties.
6. All units on the lower floor must be type "A" or type "B" handicapped units.
At least one type "A' unit must be provided in each complex. Please identify
the location of the type "A' units on the site plan.
7. Please provide literature on stucco for 1 -hr rating.
8. Provide a copy of the structural calculations.
9. Anchor bolts are required at all bearing walls, please identify.
10. The walk in storage space of the type "A" units does not meet ANSI Al 17.1,
section 1002.3.2.
11. Linder stair guard rails are required as per ANSI Al 17.1 section 307.4. See
figure 307.4.
12. Please provide truss details prior to framing inspection.
13. Sheet SO calls out for Special Inspections on concrete. They will also be
required for any structural field welding. Please let us know who will be
performing these inspections as soon as possible. Section 1701.1 of the 1997
Uniform Building Code (UBC) requires that the special inspectors be
employed by the owner or the engineer or architect of record acting as the
owner's agent. The Contractor isnot allowed to perform this function.
14. The units are required to be sprinklered as per the 2000 IBC.
15. The State of Idaho has adopted the 2000 International Energy Conservation .
Code. Please provide the necessary energy evaluation to meet the Code.
16. I have attached a copy of the Fire Department review top the back of this
document. The review includes redlined site drawings. These site drawings
will not be included with any fax requests. The Fire Department did not know
that type "A" dwelling units were part of this project and thus did not identify
the need for horn strobes within the type "A" units. If you have any questions
please contact Chris Huskinson at (208)359-3010.
Please provide me with 2 new stamped copies of the corrected plans. If you have
any questions, please give me a call at 359-3020 ext. 324.
Sincerely,
-------------
Val Christensen
Building Official
C.C. JohnivEllar
Chris Huskinson
7. Standpipes (Section 905) required: NO
Type required:
Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
Type being provided:
Automatic fuel shut-off required:
Portable fire extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: YES
Type of system required: Manual: Automatic: Both: X
Type of system being provided: Manual: Automatic: Both:
Components of system shown: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: REQUIRED
Fire Alarm System Acceptable: NO
10. Other corrections that are required by special occupancy or conditions:
1. FIRE ALARM SYSTEM INFORMATION NEEDS TO BE SUBMITTED
THAT INCLUDES: SUBMITTALS OF ALARM CONTROL AND
TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER
CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND
SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS
MODEL NUMBERS, AND LISTING INFORMATION FOR EQUIPMENT,
DEVICES AND MATERIALS AND INTERFACE CONNECTIONS. ADA
UNITS SHALL HAVE ALL HORN/STOBE UNITS. SUBMITTALS AND
PLANS MUST BE APPROVED PRIOR TO HAVING A BUILDING
PERMIT ISSUED.
2. FIRE SPRINIMER SYSTEM IS REQUIRED. PLANS MUST BE
SUBMITTED TO THE STATE, REVIEWED, AND APPROVED PRIOR
TO HAVING A BUILDING PERMIT ISSUED.
0
Plans as submitted are acceptable: NO
Plans checked by: CHRIS HUSKINSON Date: 6-19-03
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: X
F�`-c +,
PO. Box 280\ ifp12 North center S
treet
Rexburg, Idaho 83440
STATE OF IDAHO Phone (208) 359-3020
ay +� Fax (208) 359.3022
B4SHE�
e-mail rexburg@srv.net
REXB UR G -MADISON COUNTY
EMERGENCYSERVICES
26 NORTH CENTER STREET
REXBURG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code Plan Date: 7-01-02
Plan Review Review Date: 6-19-03
Building Name: LEVEL TWO, THREE, FOUR APARTMENTS
Building Address: PORTER ROAD AND CASPER AVENUE
Stories: 2.5 Type of Construction: V -B
Occupancy Classification: R-2 Existing Floor Area: N/A
New Construction Floor Area: APPROXIvi LATELY 8232 SQUARE FEET (EACH 12-
PLEX) AND 5712 SQUARE FEET (EACH 6-PLEX)
1. Required Fire Flow (Appendix B): 2500 GPM/TWO HOURS
Comments: FIRE FLOW MAY BE REDUCED IF STRUCTURES HAVE AN
APPROVED AUTOMATIC FIRE SUPPRESSION SYSTEM INSTALLED.
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: TWO AND FOUR ARE OKAY, THREE IS UNKNOWN
(DRAWING SHOWS 5 HYDRANTS)
Fire Hydrant Flows: U KNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO (THREE ONLY)
Water Supply Comments: FD REQUESTS HYDRANT FLOW FROM THE
ENGINEERS PRIOR TO CONSTRUCTION FOR VERIFICATION. FOUR
SHOWS HYDRANT BLOCKING DUMPSTERS; PLEASE RELOCATE.
3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: OK
Complete Road Acceptable: YES
Length: OK Surface: OK
Comments: ALL AREAS ADJACENT TO BUILDINGS AND COMMON DRIVES
SHALL BE MARKED IN RED AND POSTED "NO PARKING FIRE LANE". SEE
ATTACHED DRAWINGS.
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND 1VIADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required: YES
Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN
Comments: NEED TO PROVIDE MDTIMUM OF 2A10BC EXTINGUISHER IN
EACH UNIT
6. Automatic fire extinguishing systems (Section 903) Required: YES
Type of system being installed: NOT SHOWN
Sprinkler system monitoring (Section 907) required: YES
Comments: PLEASE PROVIDE FIRE ALARM AND FIRE SPRINKLER
DRAWINGS PRIOR TO ISSUANCE OF BUILDING PERMIT
r� l
L
22.7'
20.0'
DO
6
�V E
j y E T.'
11V wl
5.7'
R3.O'
S89'44'Q�"W 270.00'
22.0'
8.0'
26.3'
15.0'
11
R5.0'-wi
10.1
33.5'
a,
31.5"1
10.0
FF. R4S
r 7 i 273.90' EME ELEya56.2
TO
BOUNDARY DESCRIPTION
BLOCK 4, LOT 5, OF THE WESTATES SUBDIVISION NO. 1 SECTION 25,
TOWNSHIP 6 NORTH, RANGE 39, E.M.B. CITY OF REXBURG. MADISON
COUNTY, IDAHO
5'
Lij
INVERT ELEVATION
TBC
TOP BACK OF CURB
Z
FLOW LINE
TOC
TOP OF CONCRETE
RF
REVERSE FLOW
L-Izz
00 PARKING STALLS
3
'
0
Q
4 STANDARD 43
=
L0 4 COMPACT 14
1
Q2
HANDICAPPED - 3
�)
SCALE 1' = 20'
ck�
TOTAL 60
<I
I
I
VICINITY MAP
SYMBOL LEGEND
— — SECTION UNE
PROPERTY UNE/PLAT BOUNDARY
R.O.W. UNE
EASEMENT UNE
CENTERUNE
DRAINAGE CHANNEL FLOWUNE
PROPOSED CURB & GUTTER
EXISTING CURB & GUTTER
PROPOSED VERTICAL CURB
EXISRNG VERTICAL CURB
ABBREVIATIONS
INV
INVERT ELEVATION
TBC
TOP BACK OF CURB
FL
FLOW LINE
TOC
TOP OF CONCRETE
RF
REVERSE FLOW
NOTES
1. ALL DISTANCES AND DATA SHALL BE CHECKED BY THE CONTRACTOR PRIOR TO THE START
OF CONSTRUCTION. IN CASE OF CONFUCT THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY
SO THAT CLARIFICATION MAY BE MADE PRIOR TO THE START OF THE WORK.
2. THE CONTRACTOR SHALL RETAIN AND PROTECT OR REMOVE AND REPLACE ALL
LANDSCAPING, TREES, UTILITIES, DITCHES, CULVERTS, FENCES, MAILBOXES, SIGNS, UGHTPOLES,
HEADGATES, EXISTING ASPHALT PAVING, AND ALL OTHER MISCELLANEOUS ITEMS NOT LOCATED
IN A PUBLIC RIGHT OF WAY. ANY DAMAGE DONE BY THE CONTRACTOR SHALL BE REPAIRED AT
HIS EXPENSE.
3. WHERE WORK IS PERFORMED ON EASEMENTS, THE CONTRACTOR SHALL TAKE EVERY
PRECAUTION TO ELIMINATE ANY ADVERSE EFFECTS ON THE ADJACENT PROPERTY. ALL TOPSOIL
SHALL BE SALVAGED AND REPLACED.
4. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE ARRANGEMENTS FOR WATER
REQUIRED FOR COMPACTION, ANY DUST PREVENTION MEASURES, AND FOR TESTING OF LINES.
S. THE CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL SIGNING WHERE REQUIRED IN
ACCORDANCE WITH THE FEDERAL MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING SOURCES FOR GRANULAR
MATERIAL, WATER FOR CONSTRUCTION, PREAPPOVEO WASTE STFE(S), AND ADDITIONAL MATERIALS
THAT MAY BE NECESSARY FOR PROPERLY CONSTRUCTING THE PROJECT.
7. CONSTRUCTION SHALL CONFORM WITH THE LATEST EDITION OF THE UNIFORM BUILDING
CODE, EXCEPT WHERE OTHER APPLICABLE CODES OR THESE DRAWINGS AND/OR
SPECIFICATIONS ARE MORE RESTRICTIVE.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING WITH OSHA REQUIREMENTS
DURING CONSTRUCTION FOR TRENCH EXCAVATION, CONFINED SPACE AND OTHER SAFETY
STANDARDS REQUIRED DURING CONSTRUCTION.
DRAWN JCC D TE CHECKEDBEC
LATE p�4s5w T`E4 4
REXBU° `_ =
NO REVISIONS RG SV DAT 4-10-03 BEC ) FORSGREN
/gyp
Thi. document or any port Nereof in detail DESIGNED p J00 =
! d<.ign Concept i] the pamonol proper( of DATE p0.0JECT ENGINEERIDAHO
Fpraglen Mapcioie., mo. o ,hall net pe,''„p �' ASSOC/AYES, INC.
copied wttM1Dut the wntten oulhanxauon f APPROVED — BEC
FOl.gren .Y.pniates, InG. GATE PROJECT MANA6E0. ffARKI
NOTES & DETAILS
EFL to
kli T (_q 4 .o ROJECT NO.
LEI- 2 AP R I S I_. m _ng.
SHEET NO.
HORIZONTAL CONTROL PLAN CP_l
r
E;
1
til + - • . ` �__,.� ,
\ r
nm u�Bls t ]slsos.]s+a
/
E 731511. x ]R.n]1 1021
N]!
51pa M' \ 31593AX1'.
3
illir �. W Y- Y
�A
BOUNDARY DESCRIPTION
IP6—p\L4 i 1`: LOT 4, BLOCK 5, OF THE WESTATES SUBDIVISION NO. 1
( I SECTION 25, TOWNSHIP 6 NORTH, RANGE 39, E.M.B. CITY
1\\/ OF REXBURG, MADISON COUNTY, IDAHO
` fME---�5-�f� C10i I it
+ f
SQUAREPERCENT
FOOTAGE ACREAGE OF TOTAL
F
f TOTAL AREA 48787 1.12 1005
\ + + I TOTAL BUILDING AREA 8861 0.16 145
�� • + / . + + +�" + + TOTAL IMPREMOUS AREA 27228 0.82 555
TOTAL LANDSCAPED AREA 14687 0.36 315
SNOW STORAGE 105
y / N
PARKING STALLS
` 4
— 4 � STANDARD 44
_--�•" COMPACT 14
HANDICAPPED 3
SCALE 1" = 201 TOTAL 61
+++
+++ +
E ]615
it ]6Ih°N.
/ + r
ABBREVIATIONS
SYMBOL LEGEND
—•--•-----
SECTION LINE
-------
PROPERTY UNE/PLAT BOUNDARY
-------
R.O.W. UNE
- - - - - - - - -
- EASEMENT LINE
— - —
CENTERLINE
--------------
DRAINAGE CHANNEL FLOWUNE
PROPOSED CURB & GUTTER
TOC TOP OF CONCRETE
EXISTING CURB & GUTTER
PROPOSED VERTICAL CURB
RF REVERSE FLOW
EXISTING VERTICAL CURB
BOUNDARY DESCRIPTION
IP6—p\L4 i 1`: LOT 4, BLOCK 5, OF THE WESTATES SUBDIVISION NO. 1
( I SECTION 25, TOWNSHIP 6 NORTH, RANGE 39, E.M.B. CITY
1\\/ OF REXBURG, MADISON COUNTY, IDAHO
` fME---�5-�f� C10i I it
+ f
SQUAREPERCENT
FOOTAGE ACREAGE OF TOTAL
F
f TOTAL AREA 48787 1.12 1005
\ + + I TOTAL BUILDING AREA 8861 0.16 145
�� • + / . + + +�" + + TOTAL IMPREMOUS AREA 27228 0.82 555
TOTAL LANDSCAPED AREA 14687 0.36 315
SNOW STORAGE 105
y / N
PARKING STALLS
` 4
— 4 � STANDARD 44
_--�•" COMPACT 14
HANDICAPPED 3
SCALE 1" = 201 TOTAL 61
+++
+++ +
E ]615
it ]6Ih°N.
/ + r
ABBREVIATIONS
NOTES
CHECKEDBEC
DATE
1. ALL DISTANCES AND DATA SHALL BE CHECKED BY THE CONTRACTOR PRIOR TO THE START
INV INVERT ELEVATION
OF CONSTRUCTION. IN CASE OF CONFLICT THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY
BEC
SO THAT CLARIFICATION MAY BE MADE PRIOR TO THE START OF THE WORK.
TBC TOP BACK OF CURB
PROJECT ENGINEER
APPROVED —
2. THE CONTRACTOR SHALL RETAIN AND PROTECT OR REMOVE AND REPLACE ALL
FL FLOW UNE
LANDSCAPING, TREES, UTILITIES, DITCHES, CULVERTS, FENCES, MAILBOXES, SIGNS, UGHTPOLES,
HEADGATES, EXISTING ASPHALT PAVING, AND ALL OTHER MISCELLANEOUS ITEMS NOT LOCATED
TOC TOP OF CONCRETE
IN A PUBLIC RIGHT OF WAY. ANY DAMAGE DONE BY THE CONTRACTOR SHALL BE REPAIRED AT
HIS EXPENSE.
RF REVERSE FLOW
3. WHERE WORK IS PERFORMED ON EASEMENTS, THE CONTRACTOR SHALL TAKE EVERY
PRECAUTION TO EUMINATE ANY ADVERSE EFFECTS ON THE ADJACENT PROPERTY. ALL TOPSOIL
SHALL BE SALVAGED AND REPLACED.
4. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE ARRANGEMENTS FOR WATER
REQUIRED FOR COMPACTION, ANY DUST PREVENTION MEASURES, AND FOR TESTING OF LINES.
VICINITY MAP
l _
5. THE CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL SIGNING WHERE REQUIRED IN
ACCORDANCE WITH THE FEDERAL MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING SOURCES FOR GRANULAR
MATERIAL, WATER FOR CONSTRUCTION, PREAPPOVED WASTE SITE(S), AND ADDITIONAL MATERIALS
THAT MAY BE NECESSARY FOR PROPERLY CONSTRUCTING THE PROJECT.
7. CONSTRUCTION SHALL CONFORM WITH THE LATEST EDITION OF THE UNIFORM BUILDING
CODE, EXCEPT WHERE OTHER APPLICABLE CODES OR THESE DRAWINGS AND/OR
SPECIFICATIONS ARE MORE RESTRICTIVE.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING WITH OSHA REQUIREMENTS
DURING CONSTRUCTION FOR TRENCH EXCAVATION, CONFINED SPACE AND OTHER SAFETY
STANDARDS REQUIRED DURING CON5TRUCTLYI� � �� 1
FRO REVIrW s iI V
PROJECT NO.
,
^= FORSGREN LEVEL 3 APARTMENTS 01-02—(
REXBURG9soo SHEET NO.
IDAHOg ASSOCIATES, INC. HORIZONTAL CONTROL PLAN CP -1
iMg1G-"d�
DRAWN JCC
DATE
CHECKEDBEC
DATE
REVISIONS i BY DAT
4-10-03
BEC
tlent or any Port thereof In
eslgn Concept Is the personal
of Fors,,.h AssOCiotes. IDin
not be copied without the
,tFOrlEatlon Of FOr,roh
DESIGNED
DATE
PROJECT ENGINEER
APPROVED —
BEC
DATE
PROJECT MANAGER
VICINITY MAP
l _
5. THE CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL SIGNING WHERE REQUIRED IN
ACCORDANCE WITH THE FEDERAL MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING SOURCES FOR GRANULAR
MATERIAL, WATER FOR CONSTRUCTION, PREAPPOVED WASTE SITE(S), AND ADDITIONAL MATERIALS
THAT MAY BE NECESSARY FOR PROPERLY CONSTRUCTING THE PROJECT.
7. CONSTRUCTION SHALL CONFORM WITH THE LATEST EDITION OF THE UNIFORM BUILDING
CODE, EXCEPT WHERE OTHER APPLICABLE CODES OR THESE DRAWINGS AND/OR
SPECIFICATIONS ARE MORE RESTRICTIVE.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING WITH OSHA REQUIREMENTS
DURING CONSTRUCTION FOR TRENCH EXCAVATION, CONFINED SPACE AND OTHER SAFETY
STANDARDS REQUIRED DURING CON5TRUCTLYI� � �� 1
FRO REVIrW s iI V
PROJECT NO.
,
^= FORSGREN LEVEL 3 APARTMENTS 01-02—(
REXBURG9soo SHEET NO.
IDAHOg ASSOCIATES, INC. HORIZONTAL CONTROL PLAN CP -1
iMg1G-"d�
5. THE CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL SIGNING WHERE REQUIRED IN
ACCORDANCE WITH THE FEDERAL MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING SOURCES FOR GRANULAR
MATERIAL, WATER FOR CONSTRUCTION, PREAPPOVED WASTE SITE(S), AND ADDITIONAL MATERIALS
THAT MAY BE NECESSARY FOR PROPERLY CONSTRUCTING THE PROJECT.
7. CONSTRUCTION SHALL CONFORM WITH THE LATEST EDITION OF THE UNIFORM BUILDING
CODE, EXCEPT WHERE OTHER APPLICABLE CODES OR THESE DRAWINGS AND/OR
SPECIFICATIONS ARE MORE RESTRICTIVE.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING WITH OSHA REQUIREMENTS
DURING CONSTRUCTION FOR TRENCH EXCAVATION, CONFINED SPACE AND OTHER SAFETY
STANDARDS REQUIRED DURING CON5TRUCTLYI� � �� 1
FRO REVIrW s iI V
PROJECT NO.
,
^= FORSGREN LEVEL 3 APARTMENTS 01-02—(
REXBURG9soo SHEET NO.
IDAHOg ASSOCIATES, INC. HORIZONTAL CONTROL PLAN CP -1
iMg1G-"d�
j
ry�yyy I �/
r
I
20.8'
25.0'
n
R3.0'
SYMBOL LEGEND
ABBREVIATIONS
— SECTION UNE
NO REVISIONS BY DAT
— PROPERTY UNE/PLAT BOUNDARY
INV INVERT ELEVATION
R.O.W. UNE
DESIGNED O-1
— EASEMENT UNE
TBC TOP BACK OF CURB
CENTERUNE
— •• — ••
— DRAINAGE CHANNEL FLOWUNE
FL FLOW LINE
PROPOSED CURB & GUTTER
9.0-��
EXISTING CURB & GUTTER
75
PROPOSED VERTICAL CURB
�C
EXISTING VERTICAL CURB
n
R3.0'
�� Tatanetm •�
�— 29.3' t
75.0 8.0' I C MP T
r— 22.3'
— Sla
1 T
7
ITSIsosAxx
22.0'
25.0'
I 2\'
22.0' 2
,,— R5.Q'
R5.Q'
25. '
7'
— 68.0' R.O.W. —
5.0' FAC TO FAI
21.5' 21.5'
-
— 201
ABBREVIATIONS
NOTES
NO REVISIONS BY DAT
1. ALL DISTANCES AND DATA SHALL BE CHECKED BY THE CONTRACTOR PRIOR TO THE START
INV INVERT ELEVATION
OF CONSTRUCTION. IN CASE OF CONFLICT THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY
DESIGNED O-1
SO THAT CLARIFICATION MAY BE MADE PRIOR TO THE START OF THE WORK.
TBC TOP BACK OF CURB
BEC
paTE
su assl
FL FLOW LINE
LANDSCAPING, TREES, UTLTIES, DITCHES, CULVERTS, FENCES, MAILBOXES, SIGNS, UGHTPOLES,
9.0-��
18.0
75
IN A PUBLIC RIGHT OF WAY. ANY DAMAGE DONE BY THE CONTRACTOR SHALL BE REPAIRED AT
HIS EXPENSE
RF REVERSE FLOW
ststzi em
T
ma.nep
SHALL BE SALVAGED AND REPLACED.
4. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE ARRANGEMENTS FOR WATER
REQUIRED FOR COMPACTION, ANY DUST PREVENTION MEASURES, AND FOR TESTING OF LINES.
men n.,
�� Tatanetm •�
�— 29.3' t
75.0 8.0' I C MP T
r— 22.3'
— Sla
1 T
7
ITSIsosAxx
22.0'
25.0'
I 2\'
22.0' 2
,,— R5.Q'
R5.Q'
25. '
7'
— 68.0' R.O.W. —
5.0' FAC TO FAI
21.5' 21.5'
-
— 201
ABBREVIATIONS
NOTES
NO REVISIONS BY DAT
1. ALL DISTANCES AND DATA SHALL BE CHECKED BY THE CONTRACTOR PRIOR TO THE START
INV INVERT ELEVATION
OF CONSTRUCTION. IN CASE OF CONFLICT THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY
DESIGNED O-1
SO THAT CLARIFICATION MAY BE MADE PRIOR TO THE START OF THE WORK.
TBC TOP BACK OF CURB
BEC
paTE
2. THE CONTRACTOR SHALL RETAIN AND PROTECT OR REMOVE AND REPLACE ALL
FL FLOW LINE
LANDSCAPING, TREES, UTLTIES, DITCHES, CULVERTS, FENCES, MAILBOXES, SIGNS, UGHTPOLES,
HEADGATES, EXISTING ASPHALT PAVING, AND ALL OTHER MISCELLANEOUS ITEMS NOT LOCATED
TOC TOP OF CONCRETE
IN A PUBLIC RIGHT OF WAY. ANY DAMAGE DONE BY THE CONTRACTOR SHALL BE REPAIRED AT
HIS EXPENSE
RF REVERSE FLOW
3. WHERE WORK IS PERFORMED ON EASEMENTS, THE CONTRACTOR SHALL TAKE EVERY
PRECAUTION TO ELIMINATE ANY ADVERSE EFFECTS ON THE ADJACENT PROPERTY. ALL TOPSOIL
SHALL BE SALVAGED AND REPLACED.
4. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE ARRANGEMENTS FOR WATER
REQUIRED FOR COMPACTION, ANY DUST PREVENTION MEASURES, AND FOR TESTING OF LINES.
SCALE 1' - 20'
BOUNDARY DESCRIPTION
BLOCK 4, LOT 7, OF THE WESTATES SUBDIVISION NO. 1 SECTION 25,
TOWNSHIP 6 NORTH, RANGE 39, E.M.B. CIN OF RD(BURG, MADISON
COUNTY, IDAHO
PARKING STALLS
DRAWN JCC
DATE
CHECKEDBEC
PATE
COMPACT
NO REVISIONS BY DAT
5-12-03
BEC
TK. document o, any pod IE~ in detail
pr desian concept id Ilse penonol p1,opedy of
Fo'gren msocblee• Inc. one snoll t ee
Copied Riftut the .ritten CutM1mimtron of
Fweg,en As ... x a. Inc.
DESIGNED O-1
PROJECT ENGINEER
APPROVED —
BEC
paTE
PROJECT .....ER
SCALE 1' - 20'
BOUNDARY DESCRIPTION
BLOCK 4, LOT 7, OF THE WESTATES SUBDIVISION NO. 1 SECTION 25,
TOWNSHIP 6 NORTH, RANGE 39, E.M.B. CIN OF RD(BURG, MADISON
COUNTY, IDAHO
PARKING STALLS
STANDARD
44
COMPACT
13
HANDICAPPED
3
TOTAL
60
VICINITY MAP
��■ter
1 ■
01
ffix
�1
em
II� L��lI
IF
�;-!
__
5. THE CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL SIGNING WHERE REQUIRED IN
ACCORDANCE WITH THE FEDERAL MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING SOURCES FOR GRANULAR
MATERIAL, WATER FOR CONSTRUCTION, PREAPPOVED WASTE STTE(5), AND ADDITIONAL MATERIALS
THAT MAY BE NECESSARY FOR PROPERLY CONSTRUCTING THE PROJECT.
7. CONSTRUCTION SHALL CONFORM WITH THE LATEST EDITION OF THE UNIFORM BUILDING
CODE, EXCEPT WHERE OTHER APPLICABLE CODES OR THESE DRAWINGS AND/OR
SPECIFICATIONS ARE MORE RESTRICTIVE.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMING WITH OSHA REQUIREMENTS
DURING CONSTRUCTION FOR TRENCH EXCAVATION, CONFINED SPACE AND OT}I1Ef,
STANDARDS REQUIRED DURING CONSTRUCTION.L -
'' ) ,flCO
e
��R '
NOTES & DETAILS
I '
EW ON L )r"
sp MALE PROJECT NO.
REXBURG, FORSGRE
.Te°�� LEVEL 4 APARTMENTS 01-02—(
` Essoo N
IDAHO R ASSOCIATES, INC. SHEET NO.
•ED �D HORIZONTAL CONTROL PLAN Cp—1
(Mgln