Loading...
HomeMy WebLinkAboutPLAN REVIEWS - 03-00016 - Gringo's Restaurant - New Buildingl/////per// P.O. Box 280 ely of U,ex�U///��0, (ur� 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 STATE OF IDAHO Fax (208) 359-3022 I b - ' b „r„ www.drexburg.id.us rg.id. us a mai rex urg ci.rex urg.id.us �� 5/1/2003 Scott Spaulding Design Intelligence 3685 E Hwy. 33 Rexburg, Idaho 83440 Dear Scott, I have reviewed the Gringos Restaurant drawings that you have provided me and have identified the following discrepancies: 1. A site plan must be provided. I have attached a copy of the site plan requirements to the back of this document. The parking lot must be designed to City of Rexburg standards. There will need to be an ADA compliant van accessible handicap parking place. 2. I will need information for the future installation of any cooking hoods. 3. Provide exit lights and emergency lights as per code. 4. Occupancy limits must be posted near the exits. 5. The Fire Department has reviewed the plans. I have attached a copy of their report to the back of this document. Please provide the necessary information they have requested. Please return two sets of revised plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official cc Stephen Zollinger John Millar Chris Huskinson ulto ° P.O. Box 280 DI 2e x is rF 12 North Center Street v 0 Rexburg, Idaho 83440 a " Phone (208) 359-3020 STATE OF IDAHO Fax (208) 359-3022 9g(ISHEO e-mail rexburg@srv.net Site Plan Checklist Applicant Information Applicant: ❑ Owner Applicant's Address:_ Recorded Owner: Recorded Owner Address: ❑ Purchaser ❑ Lessee File Number: Phone: Zip: Phone: FAX: Development Information Project Name: Property Address: ❑ 1. Site plan must be drawn to scale, be legible and also be submitted electronically if possible. ❑ 2. Adjoining streets labeled. ❑ 3. Right -of-way location and width, curb to curb widths and sidewalk location. ❑ 4. Building location, sq footage and dimensions, with distance to property lines. ❑ 5. Show existing and proposed easements. ❑ 6. Existing utilities (waterlines, sanitary sewer lines, manholes, storm drains). ❑ 7. Proposed utilities including tie in location to existing services and new easements. ❑ 8. Proposed storm drain and sanitary sewer elevations (for pipe inverts at manholes and catch basins). ❑ 9. Storm drainage plan for parking lot and roof areas, with calculations. ❑ 10. Fire hydrants and fire suppression lines (including tie to City lines). ❑ Sprinkled ❑ Not Sprinkled ❑ 11. Parking (including parking lot, drainage arrows, dimension of lot, distance between rows, and total numbers). ❑ 12. Landscaping (type and total area, including dimensions). ❑ 13. Trash facilities. ❑ 14. North Arrow ❑ 15. Drawing to Scale, including a graphic scale (11 %2 x 17" paper if possible). ❑ 16. Proposed street improvements (curb, gutter, sidewalk, pavement, etc.) ❑ 17. Legal description of proposed building site included. ❑ 18. Percent of lot covered by building or paving calculated. ❑ 19. Show 10% snow storage area. ❑ 20. Distance of entrances from street corner indicated. ❑ 21. Current Vicinity Map. (8 %2 x 11 ") at 1 " = 300' scale, showing location of the property. °'NOTE: SITE PLANS MUST BE COMPLETE AND SUBMITTED FOR REVIEW BEFORE THE PROJECT WILL BE PLACED ON THE PLANNING & ZONING AGENDA.' .*..�*..........aae�...�.......a�aa.....�.�a...*�.. �.....aa�.aa�a..:�+aa �*.aa•� FAME ;��Illfiiii III I'li'll 26 NORTH CENTER STREET REXR URG, IDAHO 83440 208-359-3010 208-359-3006 FAX 2000 International Fire Code Plan Date: 4-16-03 Plan Review Review Date: 4-29-03 Building Name: GRINGO'S RESTAURANT Building Address: NEAR 23 SOUTH CENTER Stories: ONE Type of Construction: V -B Occupancy Classification: A-2, S-1 Existing Floor Area: N/A New Construction Floor Area: 9600 SQUARE FEET 1. Required Fire Flow (Appendix B): 2750 GPM/TWO HOURS Comments: REQUIRED FIRE FLOW MAY BE REDUCED UP TO 75% IF AN APPROVED FUZE SPRINKLER SYSTEM IS INSTALLED. 2. Water Supply (Section 508, Appendix C) Required: YES Fire Hydrant Location: MAIN AND CENTER, MAIN AND CARLSON, CARLSON AND COLLEGE AVE. Fire Hydrant Flows: OK Fire Flow Test Location: SAME AS ABOVE Fire Flow Supplied By: FD Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: OCCUPANCY CURRENTLY HAS THREE FIRE HYDRANTS WITHIN 450 FEET 3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES Acceptable Width: X Length: X Surface: X Complete Road Acceptable: YES Comments: NONE 4. Access Roads and Water Supply, including fire hydrants are required to be installed and made serviceable prior to and during time of construction (Section 501): Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED. 5. Installation of portable fire extinguishers (Section 906) Required: YES Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN Comments: OCCUPANCY REQUIRES A CLASS "K" EXTINGUISHER IN KITCHEN AREA IN ADDITION TO TWO ADDITIONAL 2AIOBC EXTINGUISHERS IN BUILDING. 6. Automatic fire extinguishing systems (Section 903) Required: NO Type of system being installed: Sprinkler system monitoring (Section 907) required: Comments: 7. Standpipes (Section 905) required: NO Type required: Comments: 8. Ventilating hood and duct fire extinguisher system (Section 609) required: YES Type being provided: NOT SHOWN Automatic fuel shut-off required: YES Portable fire extinguisher shown: NOT SHOWN Comments: PLEASE PROVIDE SIZE, TYPE, MANUFACTURER, ETC. OF HOOD SYSTEM TO BE INSTALLED. 9. Fire alarm systems (Section 907) required: NO Type of system required: Manual: Automatic: Both: Type of system being provided: Manual: Automatic: Both: Components of system shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: 10. Other corrections that are required by special occupancy or conditions: PLANS SUBMITTED SHOW A NARROWING OF THE EGRESS PATH NEAR THE HOSTESS STATION THAT MAY REDUCE TOTAL OCCUPANCY LIMITS IN DINING AREA. Plans as submitted are acceptable: NO Plans checked by: CHRIS HUSKINSON Date: 4-29-03 Please furnish comments back to the plan reviewer in the following manner: Written Comments: New Plans: ****THIS PLAN REVIEW IS INCOMPLETE. INSPECTOR STILL WAITING FOR SEATING ARRANGEMENT DRAWINGS FROM OWNER FOR COMPLETE OCCUPANCY LIMITS.*******