HomeMy WebLinkAboutPLAN REVIEWS - 03-00014 - Academy Apartments - New 8-Plex3/19/2003 Newell Goldberry Sunberg and Associates 111 E. 16`h Idaho Falls, ID 83404 Dear Newell, STATE OF IDAHO www.c1. rexburg.id.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@cI.rexburg.Id.us I have reviewed the Glenn Reed Apartment drawings and have identified the following discrepancies: 1. Please identify a parking buffer as per the Rexburg Zoning Ordinance where the parking lots adjoin other properties. 2. The sidewalk and the curb and gutter at the entrance access must be constructed per City of Rexburg design requirements (6 inches thick with steel reinforcement). Please identify on plans. 3. The walls and door of the laundry must be 1 hr. fire rated as per Table 302. 1.1 of the 2000 International Building Code (IBC). 4. Please provide details for the drains pipes that will have to penetrate the fire resistive party walls at the laundry and where the bedroom sinks are adhacent to the wall. 5. Please provide structural calculations for either allowable stress design or the LRFD design method. Also provide Spectral Response Coefficients for the one second and the short. 6. Clearly identify all required braced wall panels on the plans. Include their nailing procedures. I am assuming that you are using. some of the interior gypsum walls in your calculations. 7. The plans show a truss clip on the wall section but do not identify the type or the spacing of the connectors. 8. Provide a quality assurance plan for seismic resistance systems as per IBC section 1705. 9. The Fire Department has reviewed the plans. I have attached a copy of their report. Please provide the necessary information they have requested. Please return two sets of revised plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 eat. 324. Sincerely, Val Christensen Building Official cc John Millar Chris Huskinson REXBURG MADISON COUNTY EMERGENCYSER VICES 26 NORTH CENTER STREET REXB URG, IDAHO 83440 208-359-3010 208-359-3006 FAX 2000 International Fire Code Plan Date: 2-27-03 Plan Review Review Date: 3-18-03 Building Name: ACADEMY (GLEN REED) APARTMENTS Building Address: 450 SOUTH FOURTH WEST Stories: 2 Type of Construction: V -B Occupancy Classification: R-2 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 5,891 SQUARE FEET 1. Required Fire Flow (Appendix B): 2,000 GPM/TWO HOURS Comments: WITH FULLY SPRINKLERED BUILDING FIRE FLOW DROPS TO 1500 GPM 2. Water Supply (Section 508, Appendix C) Required: YES Fire Hydrant Location: 4Tn SOUTH/4TH WEST Fire Hydrant Flows: EXISTING OK Fire Flow Test Location: 4TH SOUTH/4TH WEST Fire Flow Supplied By: RMCES Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: NONE 3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES Acceptable Width: YES Complete Road Acceptable: YES Comments: NONE Length: YES Surface: YES 4. Access Roads and Water Supply, including fire hydrants are required to be installed and made serviceable prior to and during time of construction (Section 501): Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED. 5. Installation of portable fire extinguishers (Section 906) Required: YES Location shown: NOT SHOWN Type provided acceptable: NOT SHOWN Comments: MINIMUM SIZE OF 2A10BC FIRE EXTINGUISHER REQUIRED TO BE MOUNTED ON THE WALL IN EACH UNIT. 6. Automatic fire extinguishing systems (Section 903) Required: NO Type of system being installed: Sprinkler system monitoring (Section 907) required: Comments: 7. Standpipes (Section 905) required: NO Type required: Comments: 8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO Type being provided: Automatic fuel shut-off required: Portable fire extinguisher shown: Comments: 9. Fire alarm systems (Section 907) required: YES Type of system required: Manual: Automatic: X Both: Type of system being provided: Manual: Automatic: Both: Components of system shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: PLANS DO NOT SHOW SMOKE DETECTORS OR HORN/STROBE UNITS IN HANDICAPPED APARTMENTS. 10. Other corrections that are required by special occupancy or conditions: Plans as submitted are acceptable: YES, WITH ABOVE ITEMS ADDRESSED PRIOR TO BUILDING PERMIT BEING ISSUED. Plans checked by: CHRIS HUSKINSON Date: 3-18-03 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: X