I have reviewed the Fastenall drawings that you have provided me and have
identified the following discrepancies:
1. The handicapped parking space can not be located across a parking lot aisle
unless all the spaces are across the aisle. Move the handicapped over next to
the building.
2. Please identify trash facilities on the site plan.
3. Change the design criteria from 1997 TIBC to the 2000 IBC. The building
type is Type VB. Seismic and wind are handled differently in the new code.
Please change cover sheet and submit calculations.
4. We adopted the 2000 International Energy Conservation Code (IECC) this
January I n. Please submit an energy evaluation as per this code. Please
identify insulation location and r -value, window u -value, heating equipment
and cooling equipment. A lighting plan and calculations must also be
provided. Please identify how you will insulate the slab edge as per Section
802.2.7 of the IECC.
5. The Fire Department has reviewed the plans. I have attached a copy of their
report to the back of this document. Please provide the necessary information
they have requested.
Please return two sets of revised plans. Let me know if I can be of any further
assistance. If you have any questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen -
Building Official
cc John Millar
Chris Huskinson
I
REXBURG-MADISON COUNTY
EMERGENCYSER VICES
26 NORTH CENTER STREET
REXBURG, IDAHO 83440
208-359-3010
208-359-3006 FAX
2000 International Fire Code Plan Date: 1-21-03
Plan Review Review Date: 1-23-03
Building Name: FASTENALL BUILDING
Building Address: DIVIDEND DRIVE, REXBURG BUSINESS PARK
Stories: ONE Type of Construction: V -B
Occupancy Classification: S-2, B Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 4650 SQUARE FEET
1. Required Fire Flow (Appendix B): 1750 GPM/TWO HOURS
Comments: FIRE FLOW MAY BE REDUCED TO 1500 GPM/TWO HOURS IF AN
APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM IS INSTALLED.
2. Water Supply (Section 508, Appendix C) Required: YES
Fire Hydrant Location: B-54, B-55
Fire Hydrant Flows: OK
Fire Flow Test Location: SAME
Fire Flow Supplied By: FD
Other Approved Water Source: NONE
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: SEE COMMENTS
Water Supply Comments: HYDRANTS NOT ON SITE PLAN, UNKNOWN IF
ADDITIONAL HYDRANTS ARE REQUIRED. I HAVE SPOKEN TO DESIGN
INTELLIGENCE AND WAS TOLD AN UPDATED PLAN WOULD BE
PROVIDED.
3, Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES
Acceptable Width: YES Length: YES Surface: YES
Complete Road Acceptable: YES
Comments: NONE
4. Access Roads and Water Supply, including fire hydrants are required to be installed
and made serviceable prior to and during time of construction (Section 501):
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE
OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED.
5. Installation of portable fire extinguishers (Section 906) Required: YES
Location shown: NO Type provided acceptable: NOT SHOWN
Comments: MEVIMUM OF 2AIOBC FIRE EXTINGUISHERS REQUIRED IN
EACH OCCUPANCY WITH TRAVEL DISTANCES.
6. Automatic fire extinguishing systems (Section 903) Required: NO
Type of system being installed:
Sprinkler system monitoring (Section 907) required:
Comments:
7. Standpipes (Section 905) required: NO
Type required: Comments:
8. Ventilating hood and duct fire extinguisher system (Section 609) required: NO
Type being provided:
Automatic fuel shut-off required:
Portable fire extinguisher shown:
Comments:
9. Fire alarm systems (Section 907) required: NO
Type of system required: Manual: Automatic: Both:
Type of system being provided: Manual: Automatic: Both:
Components of system shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring:
Fire Alarm System Acceptable:
10. Other corrections that are required by special occupancy or conditions: PLANS
SUBMITTED SHOULD BE DRAWN TO 2000 IFC REQUHiEMENTS,
PLEASE UPDATE. PLEASE ADDRESS ABOVE ITEMS BEFORE A
BUILDING PERMIT WILL BE ISSUED.
Plans as submitted are acceptable: SEE ABOVE COMMENTS
Plans checked by: CHRIS HUSKINSON Date: 1-23-03
Please furnish comments back to the plan reviewer in the following manner:
Written Comments: X New Plans: X
' Transmission Result Report(MemoryTX) ( Jan•24. 2003 11:46AM )
I)
2)
Date/Time: Jan•24. 2003 11:44AM
File Page
No• Mode Destination pg (s) Result Not Sent
----------------------------------------------------------------------------------------------------
0288 Memory TX 93590140 P - 4 OK
----------------------------------------------------------------------------------------------------
Reason for error
E.I) Han6 up or I inn fai I E.2) B u s Y
E.3) No answer E.4) No facsimile connection
�e 6Tie (lily Df JLCS()lLi7 IzSom suea<
o..wy asoaaao
H�relenel Jei.Aitl
STATE OF ld ran Wel bPJP[i
rexbnrJ - anmv nrrWpOa.lovrug.M.v
IrzAnom
soon 6pdWding
Ddsign W-WhAsson
3685 E Hwy. 33
Rexheg, Idaho 93440
Deer Swtt,
I have seviexM the Fenemll dmwiega flan you have Mttide4 me aM hate
identified Ilia fullowing discrepencres:
1. The hassimppai pakmg spare emnat Is, locafd aunts a posting lot a6k
rmleas all tW spaces ere ewss the aisle Move the haMiwppsd over rotl to
the helld'wg.
2. P"mkLoMffl trash f"Hilks on Ne silo plan.
3. Change the design mitaie from 19WU13C W the 2000 IBC. The building
"is Type", seivnicad wid sre hasdld diBcremly ie tic swwde.
Please ch ed the 2W lab ad tram@dwlafnm
A. Wa adopt¢d the 2(g0lala«tliomlFmgy Caasemtion Code(IECC)this
identify le. Pleaseoostio anenegyevahaioaspen Wit wing Plus
identity heu44nn lorslnaasd r -value, wmdowu-Sable, hosting w�ut
adwolfingkawidreta how
wyou plannedwkum, slab munalmd
pmvidd. tl,o a dcmily dint you will ®mdete theslab cdgeaepa SwLw
802.2.'/oflhe lECC.
5. The Fun Ucpemnes4 hm «viencithe phos Ihays atlshede wpy of Wee
« t ¢Beek oflldodocumwt. Please prdvidel�rewsery htfnm®tine
1hoyboYhave rzquested.
Pksx tctamtvv sate oFrerisd pHaa Came knowdl wn be afwy further
assistance. Ifyouhavenayqueatidm,p6sgie..allat359-3020¢ 324.
Sis�zrely�
4!L -Y
vol Clainwaen
Building OMsiat