4/24/2002
Brent Hilton
Hilton Architects
6895 South 900 East
Salt Lake City, UT 84047
Dear Brent,
I have reviewed the plans for the Cougar Apartments and have identified the
following discrepancies or questions:
1. Please provide dimensions on parking plan (site plan). The parallel spaces
along the laundry are too short. Parallel spaces should be 22' long or longer.
You need 2 spaces per dwelling unit. It appears that you are 7 spaces short.
2. The ADA requires that one of your handicapped parking spaces be a van
accessible space. The aisle adjacent to a van accessible space is required to be
96" wide. The other handicapped spaces require a 60' aisle. Please identify
these aisles and dimensions on parking plan.
3. Compact parking spaces are to be signed. Please identify compact spaces and
signage on plans.
4. Some of the trash dumpsters are located in parking lot corners. Our trash
trucks are side loading and will not be able to access these dumpsters.
5. Please identify privacy fencing where parking lots border other properties.
6. All units on the lower floor must be type "A" or type `B" handicapped units.
Please identify the location of all handicapped units on the site plan.
7. Please identify location(s) of 2 hr. fire-wall(s).
8. Please provide literature on stucco for 1 -hr rating.
9. The footings in the entry do not have the required 36" of ground cover for
frost protection.
10. Please provide truss details prior to framing inspection.
11. Sheet S 1 calls out for Special Inspections on concrete and structural field
welding. Please let us know who will be performing these inspections as soon
as possible. Section 1701.1 of the 1997 Uniform Building Code (UBC)
requires that the special inspectors be employed by the owner or the engineer
or architect of record acting as the owner's agent. Let us know if you will be
employing the special inspectors. The Contractor is not allowed to perform
this function.
12. I have attached a copy of the Fire Department review top the back of this
document.
Please provide me with 2 new stamped copies of the corrected plans. If you have
any questions, please give me a call at 359-3020 ext. 324.
sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 8-02
Plan Review Review Date: 9-12-02
Building Name: COURGAR APARTMENTS
Building Address: WESTATES SUBDIVISION
Stories: 3 Type of Construction: V -I
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 21,000 SQ. FEET
1).Required Fire Flow (Appendix III -A): 4,000 GPM/FOUR HOURS
Comments: AN APPROVED AUTOMATIC SPRINKLER SYSTEM IS REQUIRED FOR
ALL BUILDINGS IN THIS PROJECT. (AS OF THIS DATE NO PLANS HAVE BEEN
SUBMITTED FOR THE LAUNDRY FACILITY, HENCE IT IS UNKNOWN THE STATUS
OF THAT BUILDING). WITH A SPRINKLER SYSTEM THE MINIMUM FIRE FLOW
REQUIRED IS 1500 GPM/2 HOURS.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: OKAY
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: NONE
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: YES, SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLEASE PROVIDE AN ESTIMATED FIRE FLOW FROM
EACH HYDRANT PRIOR TO APPROVAL
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES
Turning Radius: YES
Clearance: OK
Length: YES Surface: YES
Grade: OK Vehicle Vertical: UNKNONW
Turn Arounds: YES
Complete Road Acceptable: SEE COMMENTS BELOW
Comments: ALL AREAS ADJACENT TO BUILDINGS NOT MARKED FOR PARKING
SHALL BE SIGN R NO PARKING FIRE LANE IN ADDITION TO HAVING THE
CURB PAINTED RED -AND MAINTAINED, --
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: MINIMUM OF ONE 2A10BC EXTINGUISHER PER
UNIT
Comments: NONE
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: YES Type Of System Being Installed: UNKNOWN
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: YES
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: Both: YES
Type Of System Being Provided: Manual: Automatic: UNKNOWN
Components Of System Shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO,
PLEASE INDICATE SMOKE DETECTORS AND THEIR PLACEMENT. SEE COMMENTS
BELOW
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: FIRE ALARM SYSTEM: PLEASE SUBMIT SUBMITTALS OF ALARM
CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER
CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE
DROP CALCULATIONS, MANUFACTURERS MODEL NUMBERS, AND LISTING
INFORMATION FOR EQUIPMENT, DEVICES AND MATERIALS AND INTERFACE
CONNECTIONS. ADA UNITS SHALL HAVE ALL HORN/STROBE UNITS.
FINAL PLANS: MOST CURRENT PLANS DO NOT MATCH SITE PLAN AS APPROVED
BY P & Z, PLEASE RECTIFY.
Plans As Submitted Are Acceptable: NO
Plans Checked By: CHRIS HUSKINSON Date: 9-12-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES
/�//l/�l1fx�1 //h///, P.O. Box 280
cify of U.exl ar7 12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
STATE OF IDAHO Fax (208) 359-3022
I
"Htt www.ci.rexburg.id.us a -mai rexburgQci.rexvurg.1d.us
4/24/2002
Brent Hilton
Hilton Architects
6895 South 900 East
Salt Lake City, UT 84047
Dear Brent,
I have reviewed the plans for the Cougar Apartments and have identified the
following discrepancies or questions:
1. Please provide dimensions on parking plan (site plan). The parallel spaces
along the laundry are too short. Parallel spaces should be 22' long or longer.
You need 2 spaces per dwelling unit. It appears that you are 7 spaces short.
2. The ADA requires that one of your handicapped parking spaces be a van
accessible space. The aisle adjacent to a van accessible space is required to be
96" wide. The other handicapped spaces require a 60' aisle. Please identify
these aisles and dimensions on parking plan.
3. Compact parking spaces are to be signed. Please identify compact spaces and
'signage on plans.
4. Some of the trash dumpsters are located in parking lot corners. Our trash
trucks are side loading and will not be able to access these dumpsters.
5. Please identify privacy fencing where parking lots border other properties.
6. All units on the lower floor must be type "A" or type `B" handicapped units.
Please identify the location of all handicapped units on the site plan.
7. Please identify location(s) of 2 hr. firewall(s).
8. Please provide literature on stucco for 1-br rating.
9. The footings in the entry do not have the required 36" of ground cover for
frost protection.
10. Please provide truss details prior to framing inspection.
11. Sheet S 1 calls out for Special Inspections on concrete and structural field
welding. Please let us know who will be performing these inspections as soon
as possible. Section 1701.1 of the 1997 Uniform Building Code (UBC)
requires that the special inspectors be employed by the owner or the engineer
or architect of record acting as the owner's agent. Let us know if you will be
employing the special inspectors. The Contractor is not allowed to perform
this function.
12. I have attached a copy of the Fire Department review top the back of this
document.
Please provide me with 2 new stamped copies of the corrected plans. If you have
any questions, please give me a call at 359-3020 eat. 324.
sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 8-02
Plan Review Review Date: 9-12-02
Building Name: COURGAR APARTMENTS
Building Address: WESTATES SUBDIVISION
Stories: 3 Type of Construction: V -I
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 21,000 SQ. FEET
1).Required Fire Flow (Appendix III -A): 4,000 GPM/FOUR HOURS
Comments: AN APPROVED AUTOMATIC SPRINKLER SYSTEM IS REQUIRED FOR
ALL BUILDINGS IN THIS PROJECT. (AS OF THIS DATE NO PLANS HAVE BEEN
SUBMITTED FOR THE LAUNDRY FACILITY, HENCE IT IS UNKNOWN THE STATUS
OF THAT BUILDING). WITH A SPRINKLER SYSTEM THE MINIMUM FIRE FLOW
REQUIRED IS 1500 GPM/2 HOURS.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: OKAY
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: NONE
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: YES, SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLEASE PROVIDE AN ESTIMATED FIRE FLOW FROM
EACH HYDRANT PRIOR TO APPROVAL
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES
Turning Radius: YES
Clearance: OK
Length: YES Surface: YES
Grade: OK vehicle vertical: UNKNONW
Turn Arounds: YES
Complete Road Acceptable: SEE COMMENTS BELOW
Comments: ALL AREAS ADJACENT TO BUILDINGS NOT MARKED FOR PARKING
SHALL BE SIGN � NO PARKING FIRE LANE IN ADDITION TO HAVING THE
-CURB-PAINTED RED AND -MAINTAINED, ---- -
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: MINIMUM OF ONE 2A10BC EXTINGUISHER PER
UNIT
Comments: NONE
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: YES Type Of System Being Installed: UNKNOWN
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: YES
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: Both: YES
Type Of System Being Provided: Manual: Automatic: UNKNOWN
Components Of System Shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO,
PLEASE INDICATE SMOKE DETECTORS AND THEIR PLACEMENT. SEE COMMENTS
BELOW
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: FIRE ALARM SYSTEM: PLEASE SUBMIT SUBMITTALS OF ALARM
CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER
CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE
DROP CALCULATIONS, MANUFACTURERS MODEL NUMBERS, AND LISTING
INFORMATION FOR EQUIPMENT, DEVICES AND MATERIALS AND INTERFACE
CONNECTIONS. ADA UNITS SHALL HAVE ALL HORN/STROBE UNITS.
FINAL PLANS: MOST CURRENT PLANS DO NOT MATCH SITE PLAN AS APPROVED
BY P & Z, PLEASE RECTIFY.
Plans As Submitted Are Acceptable: NO
Plans Checked By: CHRIS HUSKINSON Date: 9-12-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES