I have reviewed the plans for the Comfort Construction Apartments in the
Andrews Addition and have identified the following discrepancies, additions or
questions:
1. Provide storm pond calculations.
2. Storm pond is not located within the boundaries of the project. Please
provide easement information.
3. Get with John Millar and work out a Development Agreement.
4. Identify that setbacks are to eaves.
5. Identify right-of-way lines.
6. Identify handicap parking spaces along with signs identifying them and
the accessible routes into the buildings.
7. Identify trash facilities.
8. Provide minimum foundation reinforcement as per Section 1914.3.5 of the
1997 Uniform Building Code (UBC).
9. Please identify the exact Iocations of the HTT16 or PHD2 holdowns.
Sheet A03 identifies them with an "A" symbol at specific locations on the
floor plan but contradicts these locations in the note below by calling them
out at ends of the shear panels.
10. Please provide truss details as soon as you can get them from the supplier,
but before framing inspection.
11. All units on the lower level must be constructed as "Type B" units as per
Section 1103.1.9.3 of the UBC. Identify as such. Please identify grab bar
backing, accessible thresholds and all other accessible features.
12. Please identify smoke detectors as per the UBC and 2A-IOBC fire
extinguishers in each apartment unit.
13. Identify that bedroom windows must meet egress as per UBC Section
310.4.
14. Please identify firewall construction, including draftstops if used. Unit
separation must be maintained from foundation to roof sheathing. Please
provide details.
15. Please identify fire separation at the floors between units. Engineered
joists have their own requirements for fire protection and are not listed in
the UBC. Please provide this information on the plans.
16. Please submit a copy of your plans to the State of Idaho Electrical Bureau.
17. I have attached a copy of the Fire Department review to the back of this
document. Please resolve any issues identified by them.
Please provide me with 2 new copies of any corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(2 08) 359-3010
1997 Uniform Fire Code Plan Date: 7-2-02
Plan Review Review Date: 8-6-02
Building Name: ANDREWS APARTMENTS, DIVISION 1
Building Address: ANDREWS PLACE
Stories: TWO Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 4856 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS
Comments: REQUIRED FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING
EQUIPPED WITH APPROVED AUTOMATIC SPRINKLER SYSTEM.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: YES
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: NONE
Other Approved Water Source: NONE
Water Supply Acceptable: SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLEASE PROVIDE AN ESTIMATED WATER FLOW FROM
NEW HYDRANT PRIOR TO CONSTRUCTION.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width
Turning Radius: X
Clearance:
X Length: X Surface: X
Grade: X Vehicle Vertical:
Turn Arounds: X
Complete Road Acceptable: YES
Comments:
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO
CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: SEE COMMENTS
Comments: PROVIDE ONE FIRE EXTINGUISHER, MINIMUM SIZE OF 2A10BC,
MOUNTED IN EACH UNIT.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: YES Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: PLANS DO NOT SHOW SMOKE DETECTORS. PROVIDE ONE DETECTOR
IN EACH SLEEPING ROOM AND ONE IN EACH CORRIDOR LEADING TO EACH
ROOM.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: NO, PLEASE ADDRESS ABOVE ITEMS.
Plans Checked By: CHRIS HUSXINSON Date: 8-6-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: X New Plans:
7/25/2002
Steven Yearsley
Forsgren Engineering
350 North 2°d East
Rexburg, Idaho 83440
Dear Steven,
edy 0/V LL.exiU/Ll/ lC//
STATE OF IDAHO
www.ci.rexburti id.0
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburg.id.us
I have reviewed the plans for the Continental Park Apartments and have identified
the following discrepancies, additions or questions:
1. Provide storm pond calculations.
2. Get with John Millar and work out a Development Agreement.
3. Identify that setbacks are to eaves.
4. Show right-of-way lines. If they do not exist, please provide
documentation dedicating the area from the back of the sidewalks towards
the street to the City of Rexburg.
5. Identify handicap parking spaces along with signs identifying them and
the accessible routes into the buildings.
6. Identify trash facilities.
7. Sheet DT -4 calls out welded wire fabric. Please change this to %" rebar at
18" o.c. in both directions as per the City of Rexburg specifications. Also
identify the approach and sidewalk at the approach as 6" thick. The curb
and gutter must also be reinforced. Please identify 24 4 rebar in the curb
and gutter section.
8. The architectural drawings and the stair drawings must be stamped by a
licensed professional.
9. All units on the lower level must be constructed as "Type B" units as per
Section 1103.1.9.3 of the 1997 Uniform Building Code (UBC). Please
change bathroom configuration for compliance. Please identify grab bar
backing, accessible thresholds and all other accessible features.
10. For the "Type A" unit please identify grab bar backing, accessible
thresholds and all other accessible features.
11. Please identify smoke detectors as per the UBC and 2A-1 OBC fire
extinguishers in each apartment unit.
12. Sheet SL3 identifies 2" washers on the anchor bolts. Are these the 2"
square washers as identified in the UBC?
13. Please identify firewall construction, including draftstops. Unit separation
must be maintained from foundation to roof sheathing.
14. Please identify fire separation at the floors between units. Engineered
joists have their own requirements for fire protection and are not listed in
the UBC. Please provide this information on the plans.
15. Please identify attic ventilation as per the UBC.
16. I have attached a copy of the Fire Department review to the back of this
document. Please resolve any issues identified by them.
Please provide me with 2 new copies of any corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerely,
�0
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
Lyle Cook
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 5-02
Plan Review Review Date: 7-17-02
Building Name: CONTINENTAL PARK APARTMENTS
Building Address: CORNER OF 5" WEST AND 7" SOUTH
Stories: 2.5 Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 5400 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS
Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED BY 75 PERCENT IF
BUILDINGS HAVE AN APPROVED AUTOMATIC SPRINKLER SYSTEM
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: TWO PROPOSED
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location:
Fire Flow Supplied By:
Other Approved Water Source: NONE
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: YES
Water Supply Comments: NONE
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES Length: YES Surface: YES
Turning Radius: Grade: Vehicle Vertical:
Clearance: Turn Arounds:
Complete Road Acceptable: YES
Comments:
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES
Location Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Comments: PROVIDE MINIMUM OF ONE FIRE EXTINGUISHER PER UNIT,
MINIMUM SIZE OF 2A10BC EACH
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: NO
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required: Comments:
S).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: NO
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments:
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES, SEE
COMMENTS
Type Of System Required: Manual: Automatic: Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System Shown: Smoke Detectors:
Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: PROVIDE SMOKE DETECTORS IN EACH SLEEPING ROOM AND
ADJACENT HALLWAYS/CORRIDORS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: WITH ABOVE ITEMS COMPLIED WITH
Plans Checked By: CHRIS HUSKINSON Date: 7-17-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: New Plans:
8/7/2002
Dean Mortimer
7403 South 1'' East
Idaho Falls, Idaho 83404
Dear Dean,
edy ollexlur7
STATE OF IDAHO
www.drexburc.id.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburg.id.us
I have reviewed the plans for the Comfort Construction Apartments in the
Andrews Addition and have identified the following discrepancies, additions or
questions:
1. Provide storm pond calculations.
2. Storm pond is not located within the boundaries of the project. Please
provide easement information.
3. Get with John Millar and work out a Development Agreement.
4. Identify that setbacks are to eaves.
5. Identify right-of-way lines.
6. Identify handicap parking spaces along with signs identifying them and
the accessible routes into the buildings.
7. Identify trash facilities.
8. Provide minimum foundation reinforcement as per Section 1914.3,5 of the
1997 Uniform Building Code (UBC).
9. Please identify the exact Iocations of the HTT16 or PHD2 holdowns.
Sheet A03 identifies them with an "A" symbol at specific locations on the
floor plan but contradicts these locations in the note below by calling them
out at ends of the shear panels.
10. Please provide truss details as soon as you can get them from the supplier,
but before framing inspection.
11. All units on the lower level must be constructed as "Type B" units as per
Section 1103.1.9.3 of the UBC. Identify as such. Please identify grab bar
backing, accessible thresholds and all other accessible features.
12. Please identify smoke detectors as per the UBC and 2A-IOBC fire
extinguishers in each apartment unit.
13. Identify that bedroom windows must meet egress as per UBC Section
310.4.
14. Please identify firewall construction, including draftstops if used. Unit
separation must be maintained from foundation to roof sheathing. Please
provide details.
15. Please identify fire separation at the floors between units. Engineered
joists have their own requirements for fire protection and are not listed in
the UBC. Please provide this information on the plans.
16. Please submit a copy of your plans to the State of Idaho Electrical Bureau.
17. I have attached a copy of the Fire Department review to the back of this
document. Please resolve any issues identified by them.
Please provide me with 2 new copies of any corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 7-2-02
Plan Review Review Date: 8-6-02
Building Name: ANDREWS APARTMENTS, DIVISION 1
Building Address: ANDREWS PLACE
Stories: TWO Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 4856 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS
Comments: REQUIRED FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING
EQUIPPED WITH APPROVED AUTOMATIC SPRINKLER SYSTEM.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: YES
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: NONE
Other Approved Water Source: NONE
Water Supply Acceptable: SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLEASE PROVIDE AN ESTIMATED WATER FLOW FROM
NEW HYDRANT PRIOR TO CONSTRUCTION.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: X Length: X Surface: X
Turning Radius: X Grade: X Vehicle Vertical:
Clearance: Turn Arounds: X
Complete Road Acceptable: YES
Comments:
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO
CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: SEE COMMENTS
Comments: PROVIDE ONE FIRE EXTINGUISHER, MINIMUM SIZE OF 2A10BC,
MOUNTED IN EACH UNIT.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: YES Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: PLANS DO NOT SHOW SMOKE DETECTORS. PROVIDE ONE DETECTOR
IN EACH SLEEPING ROOM AND ONE IN EACH CORRIDOR LEADING TO EACH
ROOM.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: NO, PLEASE ADDRESS ABOVE ITEMS.
Plans Checked By: CHRIS HUSRINSON Date: 8-6-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: X New Plans:
7/25/2002
Steven Yearsley
Forsgren Engineering
350 North 2°d East
Rexburg, Idaho 83440
Dear Steven,
cily 01 1' LL.evALV.!/U,2U 7
STATE OF IDAHO
www.cj.rexbur.qJd.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburgJd.us
I have reviewed the plans for the Continental Park Apartments and have identified
the following discrepancies, additions or questions;
1.
Provide storm pond calculations.
2.
Get with John Millar and work out a Development Agreement.
3.
Identify that setbacks are to eaves.
4.
Show right-of-way lines. If they do not exist, please provide
documentation dedicating the area from the back of the sidewalks towards
the street to the City of Rexburg.
5.
Identify handicap parking spaces along with signs identifying them and
the accessible routes into the buildings.
6.
Identify trash facilities.
7.
Sheet DT -4 calls out welded wire fabric. Please change this to '/2" rebar at
18" o.c. in both directions as per the City of Rexburg specifications. Also
identify the approach and sidewalk at the approach as 6" thick. The curb
and gutter must also be reinforced. Please identify 24 4 rebar in the curb
and gutter section.
r,o-r -DoN4 -�x_ 8.
The architectural drawings and the stair drawings must be stamped by a
2 5E7 -C
licensed professional.
CONT"LS ----> 9•
All units on the lower level must be constructed as "Type B" units as per
14PeK.1 t+& BCNlm?
Section 1103.1.9.3 of the 1997 Uniform Building Code (UBC). Please
ro t LC -7
change bathroom configuration for compliance. Please identify grab bar
backing, accessible thresholds and all other accessible features.
Cp►.t-r►w tj 1Q.
For the "Type A" unit please identify grab bar backing, accessible
Krk4s o (Y4anjTs
thresholds and all other accessible features.
11.
Please identify smoke detectors as per the UBC and 2A-IOBC fire
extinguishers in each apartment unit.
12.
Sheet SL3 identifies 2" washers on the anchor bolts. Are these the 2"
square washers as identified in the UBC?
13. Please identify firewall construction, including draftstops. Unit separation
must be maintained from foundation to roof sheathing.
Np —j 14. Please identify fire separation at the floors between units. Engineered
MW, LI TVWwA&-'� joists have their own requirements for fire protection and are not listed in
the UBC. Please provide this information on the plans.
15. Please identify attic ventilation as per the UBC.
16. I have attached a copy of the Fire Department review to the back of this
document. Please resolve any issues identified by them.
Please provide me with 2 new copies of any corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
Lyle Cook
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(2 08) 359-3010
1997 Uniform Fire Code Plan Date: 5-02
Plan Review Review Date: 7-17-02
Building Name: CONTINENTAL PARK APARTMENTS
Building Address: CORNER OF 5" WEST AND 7T" SOUTH
Stories: 2.5 Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 5400 SQUARE
FEET/BUILDING
1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS
Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED BY 75 PERCENT IF
BUILDINGS HAVE AN APPROVED AUTOMATIC SPRINKLER SYSTEM
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: TWO PROPOSED
Fire Hydrant Flows:_UNKNOWN
Fire Flow Test Location:
Fire Flow Supplied By: -
Other Approved Water Source: NONE
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: YES
Water Supply Comments: NONE
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES j
r
Acceptable: Width: YES Length: YES Surface: YES
Turning Radius: Grade: Vehicle Vertical:
Clearance: Turn Arounds:
Complete Road Acceptable: YES
Comments:
4).Access Roads and water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER
WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES
Location Acceptable: NOT SHOWN
Type Provided Acceptable: NOT SHOWN
Comments: PROVIDE MINIMUM OF ONE FIRE EXTINGUISHER PER UNIT,
MINIMUM SIZE OF 2A10BC EACH
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: NO
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required: Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: NO
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments:
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES, SEE
COMMENTS
Type Of System Required: Manual: Automatic: Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System Shown: Smoke Detectors:
Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: PROVIDE SMOKE DETECTORS IN EACH SLEEPING ROOM AND
ADJACENT HALLWAYS/CORRIDORS.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: WITH ABOVE ITEMS COMPLIED WITH
Plans Checked By: CHRIS HUSKINSON Date: 7-17-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: New Plans:
8/16/2002
Scott Spaulding
Design Intelligence
135 East Main
Rexburg, Idaho 83440
Dear Scott,
STATE OF IDAHO
www.cLrexburgJd.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburg.id.us
I have reviewed the Bowen Apartment drawings that you have provided me and
have identified the following discrepancies:
1. The lot is too small for the amount of units that are being requested. My
calculations identify 7 units allowed.
2. Elevations at parking and drives are incomplete.
3. Show 5' wide City sidewalk, curb/gutter and driveway approach.
4. Why is the curb around the parking lot incomplete? There are trees drawn in the
parking area near the spot where the curbs end. Please let me know what is going
on here.
5. A fence is required where the parking lot is adjacent to other residential property.
Please identify on plans.
6. Page SO identifies special inspections being required for the bolts in concrete.
Who will be performing these inspections? Please provide us information
regarding frequency of inspection and any details associated with these
inspections.
7. Please provide 1 hr. construction at all walls around mechanical and laundry.
Identify on plans.
8._ The doors to the units need to be fire rated assemblies. Please identify as such.
9. There seems to be a bust in the floor plan dimensions. The tubs are shown to fit
nicely in an area that by my calculations is only I' 11-7/8" wide.
10. The "Typical Exterior Wall Except At Entry" detail on sheet S i identifies on
layer of 1/2" drywall an ceiling. 5/8" is the minimum on ceilings with 24" o.c.
framing.
11. Please identify attic access and attic ventilation as per the 1997 Uniform Building
Code (CIBC).
12. Show smoke detectors in each bedroom and one in common area outside
bedrooms.
13. Provide a copy of the plans to the State of Idaho Electrical Bureau.
14. The Fire Department has reviewed the plans. I have attached a copy of there
report.
Please return two sets of revised plans. Let me know if I can be of any further
assistance. If you have any questions, please give me a call at 359-3020 eat. 324.
Sincerely,
Val Christensen
Building Official
cc John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 8-5-02
Plan Review Review Date: 8-6-02
Building Name: BOWEN APARTMENTS
Building Address: FOURTH WEST, REXBURG
Stories: TWO Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: APPROXIMATELY 7200 TOTAL SQUARE FEET
1).Required Fire Flow (Appendix III -A): 1500 GPM/TWO HOURS
Comments: REQUIRED FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING
EQUIPPED WITH APPROVED AUTOMATIC SPRINKLER SYSTEM.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: ONE HYDRANT SHOWN
Fire Hydrant Flows: UNKNOWN
Fire Flow Test Location: N/A
Fire Flow Supplied By: NOT AVAILABLE
Other Approved Water Source: NONE
Water Supply Acceptable: SEE COMMENTS
Fire Hydrant Location Acceptable: YES
Water Supply Comments: PLEASE PROVIDE AN ESTIMATED WATER FLOW FROM
NEW HYDRANT PRIOR TO CONSTRUCTION.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: X Length: X Surface: X
Turning Radius: X Grade: X Vehicle Vertical:
Clearance: Turn Arounds: X
Complete Road Acceptable: YES
Comments:
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO
CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: SEE COMMENTS
Comments: PROVIDE ONE FIRE EXTINGUISHER, MINIMUM SIZE OF 2A10BC,
MOUNTED IN EACH UNIT.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required: Comments:
8).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: YES Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System: Smoke Detectors: X Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: PLANS DO NOT SHOW SMOKE DETECTORS. PROVIDE ONE DETECTOR
IN EACH SLEEPING ROOM AND ONE IN EACH CORRIDOR LEADING TO EACH
ROOM.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: