HomeMy WebLinkAboutPLAN REVIEWS - 02-00049 - 885 Andrews PI - 4 Plex8/7/2002 Dean Mortimer 7403 South 1" East Idaho Falls, Idaho 83404 Dear Dean, 01,Y till U.eW4lur7 STATE OF IDAHO www.drexburg.id.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci. rexburg.id.us I have reviewed the plans for the Comfort Construction Apartments in the Andrews Addition and have identified the following discrepancies, additions or questions: 1. Provide storm pond calculations. 2. Storm pond is not located within the boundaries of the project. Please provide easement information. 3. Get with John Millar and work out a Development Agreement. 4. Identify that setbacks are to eaves. 5. Identify right-of-way lines. 6. Identify handicap parking spaces along with signs identifying them and the accessible routes into the buildings. 7. Identify trash facilities. 8. Provide minimum foundation reinforcement as per Section 1914.3.5 of the 1997 Uniform Building Code (UBC). 9. Please identify the exact Iocations of the HTT16 or PHD2 holdowns. Sheet A03 identifies them with an "A" symbol at specific locations on the floor plan but contradicts these locations in the note below by calling them out at ends of the shear panels. 10. Please provide truss details as soon as you can get them from the supplier, but before framing inspection. 11. All units on the lower level must be constructed as "Type B" units as per Section 1103.1.9.3 of the UBC. Identify as such. Please identify grab bar backing, accessible thresholds and all other accessible features. 12. Please identify smoke detectors as per the UBC and 2A-IOBC fire extinguishers in each apartment unit. 13. Identify that bedroom windows must meet egress as per UBC Section 310.4. 14. Please identify firewall construction, including draftstops if used. Unit separation must be maintained from foundation to roof sheathing. Please provide details. 15. Please identify fire separation at the floors between units. Engineered joists have their own requirements for fire protection and are not listed in the UBC. Please provide this information on the plans. 16. Please submit a copy of your plans to the State of Idaho Electrical Bureau. 17. I have attached a copy of the Fire Department review to the back of this document. Please resolve any issues identified by them. Please provide me with 2 new copies of any corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (2 08) 359-3010 1997 Uniform Fire Code Plan Date: 7-2-02 Plan Review Review Date: 8-6-02 Building Name: ANDREWS APARTMENTS, DIVISION 1 Building Address: ANDREWS PLACE Stories: TWO Type of Construction: V -N Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 4856 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS Comments: REQUIRED FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING EQUIPPED WITH APPROVED AUTOMATIC SPRINKLER SYSTEM. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: YES Fire Hydrant Flows: UNKNOWN Fire Flow Test Location: N/A Fire Flow Supplied By: NONE Other Approved Water Source: NONE Water Supply Acceptable: SEE COMMENTS Fire Hydrant Location Acceptable: YES Water Supply Comments: PLEASE PROVIDE AN ESTIMATED WATER FLOW FROM NEW HYDRANT PRIOR TO CONSTRUCTION. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width Turning Radius: X Clearance: X Length: X Surface: X Grade: X Vehicle Vertical: Turn Arounds: X Complete Road Acceptable: YES Comments: 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: SEE COMMENTS Comments: PROVIDE ONE FIRE EXTINGUISHER, MINIMUM SIZE OF 2A10BC, MOUNTED IN EACH UNIT. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: YES Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System: Smoke Detectors: X Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: PLANS DO NOT SHOW SMOKE DETECTORS. PROVIDE ONE DETECTOR IN EACH SLEEPING ROOM AND ONE IN EACH CORRIDOR LEADING TO EACH ROOM. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: Plans As Submitted Are Acceptable: NO, PLEASE ADDRESS ABOVE ITEMS. Plans Checked By: CHRIS HUSXINSON Date: 8-6-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: 7/25/2002 Steven Yearsley Forsgren Engineering 350 North 2°d East Rexburg, Idaho 83440 Dear Steven, edy 0/V LL.exiU/Ll/ lC// STATE OF IDAHO www.ci.rexburti id.0 P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the plans for the Continental Park Apartments and have identified the following discrepancies, additions or questions: 1. Provide storm pond calculations. 2. Get with John Millar and work out a Development Agreement. 3. Identify that setbacks are to eaves. 4. Show right-of-way lines. If they do not exist, please provide documentation dedicating the area from the back of the sidewalks towards the street to the City of Rexburg. 5. Identify handicap parking spaces along with signs identifying them and the accessible routes into the buildings. 6. Identify trash facilities. 7. Sheet DT -4 calls out welded wire fabric. Please change this to %" rebar at 18" o.c. in both directions as per the City of Rexburg specifications. Also identify the approach and sidewalk at the approach as 6" thick. The curb and gutter must also be reinforced. Please identify 24 4 rebar in the curb and gutter section. 8. The architectural drawings and the stair drawings must be stamped by a licensed professional. 9. All units on the lower level must be constructed as "Type B" units as per Section 1103.1.9.3 of the 1997 Uniform Building Code (UBC). Please change bathroom configuration for compliance. Please identify grab bar backing, accessible thresholds and all other accessible features. 10. For the "Type A" unit please identify grab bar backing, accessible thresholds and all other accessible features. 11. Please identify smoke detectors as per the UBC and 2A-1 OBC fire extinguishers in each apartment unit. 12. Sheet SL3 identifies 2" washers on the anchor bolts. Are these the 2" square washers as identified in the UBC? 13. Please identify firewall construction, including draftstops. Unit separation must be maintained from foundation to roof sheathing. 14. Please identify fire separation at the floors between units. Engineered joists have their own requirements for fire protection and are not listed in the UBC. Please provide this information on the plans. 15. Please identify attic ventilation as per the UBC. 16. I have attached a copy of the Fire Department review to the back of this document. Please resolve any issues identified by them. Please provide me with 2 new copies of any corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, �0 Val Christensen Building Official C.C. John Millar Chris Huskinson Lyle Cook REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 5-02 Plan Review Review Date: 7-17-02 Building Name: CONTINENTAL PARK APARTMENTS Building Address: CORNER OF 5" WEST AND 7" SOUTH Stories: 2.5 Type of Construction: V -N Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 5400 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED BY 75 PERCENT IF BUILDINGS HAVE AN APPROVED AUTOMATIC SPRINKLER SYSTEM 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: TWO PROPOSED Fire Hydrant Flows: UNKNOWN Fire Flow Test Location: Fire Flow Supplied By: Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: NONE 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: Grade: Vehicle Vertical: Clearance: Turn Arounds: Complete Road Acceptable: YES Comments: 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: PROVIDE MINIMUM OF ONE FIRE EXTINGUISHER PER UNIT, MINIMUM SIZE OF 2A10BC EACH 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: NO Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: S).Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: NO Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments: 9).Fire Alarm Systems (Article 10 Section 1007)Required: YES, SEE COMMENTS Type Of System Required: Manual: Automatic: Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System Shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: PROVIDE SMOKE DETECTORS IN EACH SLEEPING ROOM AND ADJACENT HALLWAYS/CORRIDORS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: Plans As Submitted Are Acceptable: WITH ABOVE ITEMS COMPLIED WITH Plans Checked By: CHRIS HUSKINSON Date: 7-17-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: New Plans: 8/7/2002 Dean Mortimer 7403 South 1'' East Idaho Falls, Idaho 83404 Dear Dean, edy ollexlur7 STATE OF IDAHO www.drexburc.id.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the plans for the Comfort Construction Apartments in the Andrews Addition and have identified the following discrepancies, additions or questions: 1. Provide storm pond calculations. 2. Storm pond is not located within the boundaries of the project. Please provide easement information. 3. Get with John Millar and work out a Development Agreement. 4. Identify that setbacks are to eaves. 5. Identify right-of-way lines. 6. Identify handicap parking spaces along with signs identifying them and the accessible routes into the buildings. 7. Identify trash facilities. 8. Provide minimum foundation reinforcement as per Section 1914.3,5 of the 1997 Uniform Building Code (UBC). 9. Please identify the exact Iocations of the HTT16 or PHD2 holdowns. Sheet A03 identifies them with an "A" symbol at specific locations on the floor plan but contradicts these locations in the note below by calling them out at ends of the shear panels. 10. Please provide truss details as soon as you can get them from the supplier, but before framing inspection. 11. All units on the lower level must be constructed as "Type B" units as per Section 1103.1.9.3 of the UBC. Identify as such. Please identify grab bar backing, accessible thresholds and all other accessible features. 12. Please identify smoke detectors as per the UBC and 2A-IOBC fire extinguishers in each apartment unit. 13. Identify that bedroom windows must meet egress as per UBC Section 310.4. 14. Please identify firewall construction, including draftstops if used. Unit separation must be maintained from foundation to roof sheathing. Please provide details. 15. Please identify fire separation at the floors between units. Engineered joists have their own requirements for fire protection and are not listed in the UBC. Please provide this information on the plans. 16. Please submit a copy of your plans to the State of Idaho Electrical Bureau. 17. I have attached a copy of the Fire Department review to the back of this document. Please resolve any issues identified by them. Please provide me with 2 new copies of any corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 7-2-02 Plan Review Review Date: 8-6-02 Building Name: ANDREWS APARTMENTS, DIVISION 1 Building Address: ANDREWS PLACE Stories: TWO Type of Construction: V -N Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 4856 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS Comments: REQUIRED FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING EQUIPPED WITH APPROVED AUTOMATIC SPRINKLER SYSTEM. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: YES Fire Hydrant Flows: UNKNOWN Fire Flow Test Location: N/A Fire Flow Supplied By: NONE Other Approved Water Source: NONE Water Supply Acceptable: SEE COMMENTS Fire Hydrant Location Acceptable: YES Water Supply Comments: PLEASE PROVIDE AN ESTIMATED WATER FLOW FROM NEW HYDRANT PRIOR TO CONSTRUCTION. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: X Length: X Surface: X Turning Radius: X Grade: X Vehicle Vertical: Clearance: Turn Arounds: X Complete Road Acceptable: YES Comments: 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: SEE COMMENTS Comments: PROVIDE ONE FIRE EXTINGUISHER, MINIMUM SIZE OF 2A10BC, MOUNTED IN EACH UNIT. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: YES Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System: Smoke Detectors: X Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: PLANS DO NOT SHOW SMOKE DETECTORS. PROVIDE ONE DETECTOR IN EACH SLEEPING ROOM AND ONE IN EACH CORRIDOR LEADING TO EACH ROOM. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: Plans As Submitted Are Acceptable: NO, PLEASE ADDRESS ABOVE ITEMS. Plans Checked By: CHRIS HUSRINSON Date: 8-6-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: 7/25/2002 Steven Yearsley Forsgren Engineering 350 North 2°d East Rexburg, Idaho 83440 Dear Steven, cily 01 1' LL.evALV.!/U,2U 7 STATE OF IDAHO www.cj.rexbur.qJd.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburgJd.us I have reviewed the plans for the Continental Park Apartments and have identified the following discrepancies, additions or questions; 1. Provide storm pond calculations. 2. Get with John Millar and work out a Development Agreement. 3. Identify that setbacks are to eaves. 4. Show right-of-way lines. If they do not exist, please provide documentation dedicating the area from the back of the sidewalks towards the street to the City of Rexburg. 5. Identify handicap parking spaces along with signs identifying them and the accessible routes into the buildings. 6. Identify trash facilities. 7. Sheet DT -4 calls out welded wire fabric. Please change this to '/2" rebar at 18" o.c. in both directions as per the City of Rexburg specifications. Also identify the approach and sidewalk at the approach as 6" thick. The curb and gutter must also be reinforced. Please identify 24 4 rebar in the curb and gutter section. r,o-r -DoN4 -�x_ 8. The architectural drawings and the stair drawings must be stamped by a 2 5E7 -C licensed professional. CONT"LS ----> 9• All units on the lower level must be constructed as "Type B" units as per 14PeK.1 t+& BCNlm? Section 1103.1.9.3 of the 1997 Uniform Building Code (UBC). Please ro t LC -7 change bathroom configuration for compliance. Please identify grab bar backing, accessible thresholds and all other accessible features. Cp►.t-r►w tj 1Q. For the "Type A" unit please identify grab bar backing, accessible Krk4s o (Y4anjTs thresholds and all other accessible features. 11. Please identify smoke detectors as per the UBC and 2A-IOBC fire extinguishers in each apartment unit. 12. Sheet SL3 identifies 2" washers on the anchor bolts. Are these the 2" square washers as identified in the UBC? 13. Please identify firewall construction, including draftstops. Unit separation must be maintained from foundation to roof sheathing. Np —j 14. Please identify fire separation at the floors between units. Engineered MW, LI TVWwA&-'� joists have their own requirements for fire protection and are not listed in the UBC. Please provide this information on the plans. 15. Please identify attic ventilation as per the UBC. 16. I have attached a copy of the Fire Department review to the back of this document. Please resolve any issues identified by them. Please provide me with 2 new copies of any corrected plans. If you have any questions, please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official C.C. John Millar Chris Huskinson Lyle Cook REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (2 08) 359-3010 1997 Uniform Fire Code Plan Date: 5-02 Plan Review Review Date: 7-17-02 Building Name: CONTINENTAL PARK APARTMENTS Building Address: CORNER OF 5" WEST AND 7T" SOUTH Stories: 2.5 Type of Construction: V -N Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 5400 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2,000 GPM/TWO HOURS Comments: FIRE FLOW REQUIREMENTS MAY BE REDUCED BY 75 PERCENT IF BUILDINGS HAVE AN APPROVED AUTOMATIC SPRINKLER SYSTEM 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: TWO PROPOSED Fire Hydrant Flows:_UNKNOWN Fire Flow Test Location: Fire Flow Supplied By: - Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: NONE 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES j r Acceptable: Width: YES Length: YES Surface: YES Turning Radius: Grade: Vehicle Vertical: Clearance: Turn Arounds: Complete Road Acceptable: YES Comments: 4).Access Roads and water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: PROVIDE MINIMUM OF ONE FIRE EXTINGUISHER PER UNIT, MINIMUM SIZE OF 2A10BC EACH 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: NO Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: NO Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments: 9).Fire Alarm Systems (Article 10 Section 1007)Required: YES, SEE COMMENTS Type Of System Required: Manual: Automatic: Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System Shown: Smoke Detectors: Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: PROVIDE SMOKE DETECTORS IN EACH SLEEPING ROOM AND ADJACENT HALLWAYS/CORRIDORS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: Plans As Submitted Are Acceptable: WITH ABOVE ITEMS COMPLIED WITH Plans Checked By: CHRIS HUSKINSON Date: 7-17-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: New Plans: 8/16/2002 Scott Spaulding Design Intelligence 135 East Main Rexburg, Idaho 83440 Dear Scott, STATE OF IDAHO www.cLrexburgJd.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the Bowen Apartment drawings that you have provided me and have identified the following discrepancies: 1. The lot is too small for the amount of units that are being requested. My calculations identify 7 units allowed. 2. Elevations at parking and drives are incomplete. 3. Show 5' wide City sidewalk, curb/gutter and driveway approach. 4. Why is the curb around the parking lot incomplete? There are trees drawn in the parking area near the spot where the curbs end. Please let me know what is going on here. 5. A fence is required where the parking lot is adjacent to other residential property. Please identify on plans. 6. Page SO identifies special inspections being required for the bolts in concrete. Who will be performing these inspections? Please provide us information regarding frequency of inspection and any details associated with these inspections. 7. Please provide 1 hr. construction at all walls around mechanical and laundry. Identify on plans. 8._ The doors to the units need to be fire rated assemblies. Please identify as such. 9. There seems to be a bust in the floor plan dimensions. The tubs are shown to fit nicely in an area that by my calculations is only I' 11-7/8" wide. 10. The "Typical Exterior Wall Except At Entry" detail on sheet S i identifies on layer of 1/2" drywall an ceiling. 5/8" is the minimum on ceilings with 24" o.c. framing. 11. Please identify attic access and attic ventilation as per the 1997 Uniform Building Code (CIBC). 12. Show smoke detectors in each bedroom and one in common area outside bedrooms. 13. Provide a copy of the plans to the State of Idaho Electrical Bureau. 14. The Fire Department has reviewed the plans. I have attached a copy of there report. Please return two sets of revised plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 eat. 324. Sincerely, Val Christensen Building Official cc John Millar Chris Huskinson REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 8-5-02 Plan Review Review Date: 8-6-02 Building Name: BOWEN APARTMENTS Building Address: FOURTH WEST, REXBURG Stories: TWO Type of Construction: V -N Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 7200 TOTAL SQUARE FEET 1).Required Fire Flow (Appendix III -A): 1500 GPM/TWO HOURS Comments: REQUIRED FIRE FLOW MAY BE REDUCED BY 75% IF BUILDING EQUIPPED WITH APPROVED AUTOMATIC SPRINKLER SYSTEM. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: ONE HYDRANT SHOWN Fire Hydrant Flows: UNKNOWN Fire Flow Test Location: N/A Fire Flow Supplied By: NOT AVAILABLE Other Approved Water Source: NONE Water Supply Acceptable: SEE COMMENTS Fire Hydrant Location Acceptable: YES Water Supply Comments: PLEASE PROVIDE AN ESTIMATED WATER FLOW FROM NEW HYDRANT PRIOR TO CONSTRUCTION. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: X Length: X Surface: X Turning Radius: X Grade: X Vehicle Vertical: Clearance: Turn Arounds: X Complete Road Acceptable: YES Comments: 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: SEE COMMENTS Comments: PROVIDE ONE FIRE EXTINGUISHER, MINIMUM SIZE OF 2A10BC, MOUNTED IN EACH UNIT. 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: YES Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System: Smoke Detectors: X Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO Comments: PLANS DO NOT SHOW SMOKE DETECTORS. PROVIDE ONE DETECTOR IN EACH SLEEPING ROOM AND ONE IN EACH CORRIDOR LEADING TO EACH ROOM. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: