Loading...
HomeMy WebLinkAboutCLARK APTS MULT DOCS 2 - 03-00021 - American Manor Apartments - RemodelJ. D. Hancock City Attorney City of Rexburg 30 South 2nd West P. 0. Box 427 Rexburg, Idaho 83440 (208) 356-5493 IN THE DISTRICT COURT OF THE SEVENTH JUDICIAL DISTRICT OF THE STATE OF IDAHO IN AND FOR THE COUNTY OF MADISON MAGISTRATES DIVISION STATE OF IDAHO, ) Plaintiff, ) VS. ) STEVEN CLARK, ) Defendant. ) Case No. CRIMINAL COMPLAINT PERSONALLY APPEARED before me this day of October, 1990, Gordon Tychsen, Rexburg City Fire Inspector, of Rexburg, in the County of Madison, who being duly sworn, complains and says: COUNT I. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to remove combustible material from around hot gas vent pipe on the top floor in the attic in Apartment 6-A of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.222 as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. CRIMINAL COMPLAINT -1- COUNT II. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to remove combustible material from around hot gas vent pipe on the top floor in the attic in Apartment 7-A of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.222 as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. COUNT III. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to remove combustible material from around hot gas vent pipe on the top floor in the attic in Apartment 8-A of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.222 as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. COUNT IV. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to remove combustible material from around hot gas vent pipe on the top floor in the attic in Apartment 9-A of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.222 as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. COUNT V. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to remove combustible material from around hot gas vent pipe on CRIMINAL COMPLAINT -2- the top floor in the attic in Apartment 10-A of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.222 as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. COUNT VI. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to have a one -inch clearance with a metal collar in all apartments of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.404, paragraph D, as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. COUNT VII. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to properly vent all heating equipment of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.404, paragraph C, as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. COUNT VIII. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to seal the electrical chase of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 11.401, as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. CRIMINAL COMPLAINT -3- COUNT IX. That Steven Clark of 625 South 5000 West, Rexburg, Idaho, on or about the 15th day of October, 1990, in the City of Rexburg, County of Madison, State of Idaho, did fail to have portable fire extinguishers installed in each apartment of the Cottages Apartments located at 151 South First East, Rexburg, Idaho, in violation of the Uniform Fire Code, Section 10.315, paragraph F, as adopted by Rexburg City Ordinance No. 689 and also Idaho Code, Section 41-253, a misdemeanor. All of which is contrary to the form, force and effect of the statute and ordinances in such cases made and provided and against the peace and dignity of the state of Idaho. Said complainant therefore prays that a summons be issued to the said Steven Clark and that he may be dealt with according to the law. c- n GordonG ychsen Rexburg City Fire Inspector SUBSCRIBED AND SWORN TO before me this 9� day of October, 1990. Brent J. Moss, Magistrate CRIMINAL COMPLAINT -4- October 15, 1990 ELECTRICAL INSPECTION FOR THE COTTAGES NO LABELING Apartment Number: 6-A No panel cover on fan light over tub Outlet bed loose - Northwest Outlet North wall doesn't work 7-A No cover on kitchen outlet Only one circuit in kitchen Southwest bedroom outlet doubled up Closet transformer exposed Wiring laying next to chimney 8-A Oulets not covered properly in kitchen Exhaust fans missing in all bathrooms 9-A Doorbell transformer and wire exposed Switch covers in bathroom not flush with wall Bathroom fan does not work Ceiling light box exposed in bathroom Panel spaces not covered in panel 10-A Doorbell transformer hanging and wires exposed Panel spaces exposed in panel box Outlets not covered properly No cover plates on switch 6-B Switch cover missing in kitchen Only one kitchen circuit Panel breaker spaces not covered Outlet cover missing northwest bedroom Bare wires exposed over kitchen cabinet sink 7-B Southwest bedroom outlet hanging, and no cover Doorbell transformer hanging, wires exposed in closet 8-B Kitchen outlet not covered properly Only one kitchen circuit No bath fans Doorbell transformer and wires exposed 9-B Cover missing on outlet Doorbell transformers and wires exposed Outlets not covered properly (some) 10-B Switch cover missing Missing outlet covers Doorbell transformer and wires exposed Panel breaker spaces coverings missing 6-C Panel breaker spaces not covered No outlet covers Loose, bare wires hanging down in furnace room Bath fan cover not on properly One circuit in the kitchen other than refrigerator circuit 7-C No bath fan Panel breaker spaces covered with cardboard Northeast bedroom - recepticle don't work 8-C Dishwasher wire exposed No ceiling fan cover Panel breaker spaces missing, no coverings Heater panel covering missing (wire exposed) 9-C Kitchen outlets not fastened down properly Light does not cover ceiling box Bedroom switch (?) Electric cover does not cover boxes (switches and outlets) Panel breaker spaces open Bath ceiling fan cover does not cover the hole 10-C Unit not completed Outside: Looks like number 6-3 wire partially buried, is not direct burial cable. (?) General Notes: 1. All exterior exposed metal and wood should be painted. UBC Sec. 2720 2. Many electrical outlet boxes need either large plates or fill holes around boxes. UBC Sec. 307 (a) 3. Grind rough, sharp edges on steel railing. 4. Complete siding. UBC Sec. 307 (a) 5. Paint all exterior door casings UBC Sec. 307 (a) 6. Need to anchor all steel supports of overhang to concrete base and bolt all support plates. UBC Sec. 2712 (h) 7. Cover underside of overhang and stair landings 8. Install exterior grills or weather heads to all bathroom fan exhausts. UBC Sec. 1205 (c) *9. Strip enterior parking lot and driving lanes. *10. Complete south parking lot and entrance drive. *11. Complete area drain in south parking lot. 12. Should have base board in all apartments. UBC Sec. 307 (a) **13. Has broken curb off on 2nd South for access to the apartments. Should be replaced with a cut out curb. * Items numbered 9,10, and 11 are from the Planning and Zoning Ordinance # 478 of the City of Rexburg, Section 46 (c) ** Item number 13 is from the Planning and Zoning Ordinance # 478 if the City of Rexburg, Section 10 FJ�e�R Q OSP G'9 Q (L y U "D 9R[ISHE� NILE L. BOYLE Mums ROSE BAGLEY RICHARDRHORNER TRF URER&FIN"CVL OFFM Applewood Apts c/o Steve Clark 625 South 5000 West Rexburg, Idaho 83440 STATE OF IDAHO March 8, 1996 Re: Building Inspection Results t��TiTi��IFTi71 P.O. BOX 280 12 NORTH CENTER STREET REXBURG, IDAHO 83440 PHONE (208) 359-3020 FAX (208) 359-3022 As a result of the recent visit by the U.B.C. Appeals Board to your property known as Applewood Apartments, the City of Rexburg has been made aware of possible problems in your structures that go beyond the items identified in the February 9, 1996 letter from the City Engineer. The cumulative effect of the items brought to the City's attention by the U.B.C. Board, and the items in the February 9th letter, leaves the City with no choice but to formally request, that you obtain an evaluation, and advice from an independent source as to the structural and mechanical integrity of the various buildings located on your property. As has been discussed in the past, the City of Rexburg has an obligation to issue occupancy permits to only those structures which are safe for habitation, and if it cannot be determined that your structures fall within this category, it is possible that your occupancy permit could be rescinded. On behalf of the City of Rexburg, I would welcome the opportunity to meet with you and your representatives, and discuss the findings of an independent architect or structural engineer with respect to your property. If you have questions concerning what is being asked of you, please don't hesitate to contact me during regular business hours at 359-3020 ext. 316. Sincerely, Stephen P. Rexburg City Attorney cc: Joe Laird, City Engineer Nile L. Boyle, Mayor Page Item # Descri t. Response Proposed Action Final Action 1 1 headroom New Const., will fix R&R with correct height 1 2 crossbrace Not code None 1 3A stair New Const., will fix R&R with correct rise 1 3B stair New Const., will fix R&R with correct run 1 3C 1conc.pile Safety, will fix Remove concrete 1 4 draincover Safety, will fix Secure in place 1 5 back lFixed Temporarily trench Weighing long term fix 1 6 elect.wires Covered with dirt Done 2 7 3story Ruled in 1990 as 2 1/2 None story, City required an engineers examination (done by John Meyer of Idaho Falls) and ruled that e were not a 3 story building. 3 8 ASW Built per Building None Inspector Requirements at that time. 3 9 Draftstop Built per Building Will add necessary draft 3 `� Inspector Requirements at stop. that time. 4 10 ovrhngs at Built per Building None elks Inspector Requirements at hat time. 4 11 boiler room Done with exception of Will tape Joints for 1 hr I I tape in some units separation. 4 12 smoke det. Built per Building None Inspector Requirements and UBC requirements at that time. 4 13 heating All heating units None functioning properly at this time (20 below on day of inspection.) 4 14 1 hr firewall Built per Building None Inspector Requirements at that time. 5 15 smoke det. Built per Building None Inspector Requirements and UBC requirements at that time. 5 16 4" sphere Built per Building None Inspector Requirements and UBC requirements at that time. 6 1 landing Safety, will fix R&R with appropriate dimensions. 6 2 egress Built per Building None Inspector Requirements at hat time. 6 3 Iandin See 6-1 7 4 egress See 6-2 7 5 ASW ISee 3-8 8 6 draftstop Added draft stop Done requested 8 7 1 set stairs Built per Building None Inspector Requirements at that time, also more than 10 other approved student housing with similar situation. 8 8 old stairs Redoing all stairs on first Will conform to codes. units. 9 9 1 hr Built per Building None firewall Inspector Requirements at that time. 9 10 boiler room See 4-11 9 11 smoke del. See 4-12 9 12 heating See 4-13 9 13 1 hr firewall See 4-14 10 14 Ismoke det. See 4-12 10 15 4" sphere See 5-16 11 1 landin See 6-1 11 2 e ress See 6-2 11 3 landing See 6-1 12 4 hdroom/ rdApproved when built Will add guardrail I 12 5 egress See 6-2 12 6 hdroom/ rdSee 12-4 12 7 e ress See 6-2 12 8 smoke det. Battery was dead, (smoke Done detectors are checked once a week 13 9 ASW See 3-8 13 10 Draftstop Done see 8-6 13 11 1 set stairs See 8-7 13 12 old stairs See 8-8 14 13 1 hr firewall ISee 9-9 14 14 boiler room See 4-11 14 15 smoke det. See 4-12 15 16 heatin See 4-13 15 17 1 hr firewall See 4-14 15 18 smoke det. See 5-15 15 19 4" sphere See 5-16 18 1 egress See 6-2 18 2 egress See 6-2 18 3 iearess See 6-2 18 4 Iheadroom jApproved when built None 18 5 draftstop Done see 8-6 18 6 1 set stairs See 8-7 19 7 old stairs See 8-8 19 8 1 set stairs See 8-7 19 9 1 hr See 4-14 firewall 19 10 boiler room See 4-11 19 11 smoke det. See 5-15 20 12 heating See 4-13 20 13 1hrfirewall See 9-9 20 14 smoke det. See 5-15 20 15 4" sphere See 5-16 21 16 sloe Safety ill fix 21 17 frid a Safety ill move 22 1 egress See 6-2 22 2 draftstop Done see 8-6 22 3 1 set stairs See 8-7 22 4 old stairs See 8-8 23 5 1 hr firewall See 4-14 23 6 beam Safety ill fix 23 7 1hr&fireblk Done 23 8 1hr&fireblk jDone 23 9 smoke det. See 5-15 24 10 heating See 4-13 24 11 1 hr firewall See 4-14 24 12 smoke det. See 5-15 24 13 4" sphere See 5-16 25 14 sloe See 21-16 26 1 hd/str/In a Approved when built 26 2 1 hr/loun a Approved when built 27 3 entire bldg According to Joe code states 50% of building must be damaged to have o bring up to all new codes, this building is less than 20% Bring burned apt. up to new codes leave rest per old code. 27 4 draftstop Done see 8-6 27 5 1 set stairs See 8-7 27 6 old stairs See 8-8 28 7 1 hr firewall See 4-14 28 8 1hr/loun a See 26-2 28 9 boiler room See 4-11 28 10 smoke det. See 5-15 28 11 heating See 4-13 29 12 back Done Working on permanent fix _ 29 13 1 hr firewall See 4-14 29 14 smoke det. lSee 5-15 29 15 4" sphere See 5-16 30 901 address Will add 30 902 fire road Currently exists, students were not parked properly. Seeking stronger punishments for lack of varking compliance. _ 30 903 hydrants Built per city requirements at that time. No other complexes have fire hydrants. 30 8504 outlets A few broken or missing cover lates Done 30 1002 fire ext. No issue Maintained as required. 30 1007 smoke det. Built as per city re uirements at that time. None 30 1202 a ress/stor storage eliminated Done 31 1103 storage Ineed more organization tin process 31 1103 storage no combustibles in boiler Done 32 elec. romex safety ill run throw h conduit 32 elec. light safety ill secure to bid3 32 elec. romex safety ill secure to foists 32 elec. -box safety done 33 elec. fluor safety done 33 elec. cove late safety done 33 elec. Panel safety done 33 elec. Iromex safety ill secure % 33 elec. Ifluor Isafety will around 34 elec. labeling safet ill complete labeling8 - 34 elec. GFI 83 NEC states not necessa None 34 elec. Ifficture safety ill secure to ceilin 34 elec. wet room Approved by state inspectors at time of construction. None 34 elec. GFI See above 34-GFI 34 elec. wet room See above 34 -wet room 35 elec. open panel safety done 35 elec. GFI See above 34-GFI 35 elec. wet room See above 34 -wet room 35 elec. GFI See above 34-GFI 35 elec. Wet room See above 34 -wet room 35 elec. Ifixt. box safety ill add box 35 elec. et room See above 34 -wet room 35 elec. Icloset fbd. safety ill chap a out E 36 elec, Wet room See above 34 -wet room 36 elec. IGFI ISee above 34-GFI 36 elec. Hight flicker Isafety will fix 36 elec. Ilabelina ISee 34-labelin 36 elec. Wet room Isee above 34 -wet room 36 elec. JGIFI Isee above 34-GFI 37 elec. Iromex safety done 37 elec. cover late safety done 37 elec. romex safety done 37 elec. '-box safety done 37 elec. GFI See above 34-GFI 37 elec. wet room See above 34 -wet room 37 elec. GFI See above 34-GFI 37 elec. wet room See above 34 -wet room Page Item # Descri t. Response Proposed Action Final Action 1 1 headroom New Const., will fix R&R with correct height 1 2 crossbrace Not code None 1 3A stair New Const., will fix R&R with correct rise 1 3B stair New Const., will fix R&R with correct run 1 3C lconc.pile Safety, will fix Remove concrete 1 4 draincover Safety, will fix Secure in place 1 5 back Fixed Temporarily trench Weighing Iona term fix 1 6 elect.wires lCovered with dirt Done 2 7 3story Ruled in 1990 as 2 1/2 None story, City required an engineers examination (done by John Meyer of Idaho Falls) and ruled that e were not a 3 story building. 3 8 ASW Built per Building None Inspector Requirements at that time. 3 9 Draflslop Built per Building Will add necessary draft 3...� Inspector Requirements at stop. (no a".r, (jo--) that time. 47 10 lovrhngs at Built per Building None alk s Inspector Requirements at hat time. 4 11 boiler room Done with exception of Will tape joints for 1 hr I tape in some units separation. 4 12 smoke det. Built per Building None Inspector Requirements and UBC requirements at that time. 4 13 heating All heating units None functioning properly at this time (20 below on day of inspection.) 4 14 1 hr firewall Built per Building None Inspector Requirements at that time. 5 15 smoke det. Built per Building None Inspector Requirements and UBC requirements at that time. 5 16 4" sphere Built per Building None Inspector Requirements and UBC requirements at that time. 6 1 landing Safety, will fix R&R with appropriate `3 dimensions.' 6 2 egress Built per Building None Inspector Requirements at that time. 6 3 landing See 6-1 7 4 egress ISee 6-2 7 5 ASW See 3-8 8 6 draftslop Added draft stop requested Done 8 7 1 set stairs Built per Building Inspector Requirements at that time, also more than 10 other approved student housing with similar situation. None 8 S old stairs Redoing all stairs on first units. Will conform to codes. 9 9 1 hr Built per Building firewall Inspector Requirements at that time. None 9 10 boiler room See 4-11 9 11 smoke det. See 4-12 9 12 heatin See 4-13 9 13 1 hr firewall See 4-14 10 14 smoke det. See 4-12 10 15 4" sphere See 5-16 11 1 landin See 6-1 11 2 e ress See 6-2 11 3 landing See 6-1 12 4 hdroom/ rd Approved when built Will add guardrail I 12 5 e ress See 6-2 12 6 hdroom/ rd See 12-4 12 7 egress See 6-2 12 8 smoke det. Battery was dead, (smoke detectors are checked once a week Done 13 9 ASW See 3-8 13 10 Draftstop Done see 8-6 13 11 1 set stairs See 8-7 13 12 old stairs See 8-8 14 13 1 hr firewall See 9-9 14 14 boiler room See 4-11 14 15 smoke det. See 4-12 15 16 lheatina See 4-13 15 17 11 hr firewall See 4-14 15 18 Ismoke det. ISee 5-15 15 19 4" sphere See 5-16 18 1 egress See 6-2 18 2 egress See 6-2 18 3 egress See 6-2 18 4 headroom Approved when built None 18 5 draftstop Done see 8-6 18 6 1 set stairs See 8-7 19 7 old stairs See 8-8 19 8 1 set stairs See 8.7 19 9 1 hr See 4-14 firewall 19 10boiler room See 4-11 19 11 smoke det. See 5-15 20 12 heatin See 4-13 20 13 1 hr firewall See 9-9 20 14 smoke det. See 5-15 20 15 4" sphere See 5-16 21 16 sloe Safety ill fix 21 17 frid a Safety ill move 22 1 egress See 6-2 22 2 draftstop Done see 8-6 22 3 1 set stairs See 8-7 22 4 old stairs See 8-8 23 5 1 hr firewall See 4-14 23 6 beam Safety ill fix 23 7 1hr&fireblk Done 23 8 1hr&fireblk Done 23 9 smoke det. See 5-15 24 10 heating See 4-13 24 11 1 hr firewall See 4-14 24 12 smoke det. See 5-15 24 13 4" s here See 5-16 25 14 sloe See 21-16 26 1 hd/str/In a Approved when built 26 2 1hr/lounge Approved when built 27 3 entire bldg According to Joe code states 50% of building must be damaged to have o bring up to all new codes, this building is less than 20% Bring burned apt. up to new codes leave rest per old code. 27 4 draftstoD Done see 8-6 27 5 1 set stairs See 8-7 27 6 old stairs See 8-8 28 7 1 hr firewall See 4-14 28 8 1hr/loun a See 26-2 28 9 boiler room See 4-11 28 10 smoke det. See 5-15 28 11 heatin See 4-13 29 12 back Done Working on permanent fix 29 13 1 hr firewall See 4-14 29 14 smoke det. See 5-15 29 15 4" sphere See 5-16 30 901 address Will add 30 902 fire road Currently exists, students ere not parked properly. Seeking stronger punishments for lack of parking compliance. # 30 903 hydrants Built per city requirements at that time. No other complexes have fire hydrants. 30 8504 outlets A few broken or missing cover plates Done 30 1002 fire ext. No issue Maintained as required. 30 1007 smoke det. Built as per city requirements at that time. None 30 1202 a ress/stor storage eliminated Done 31 11103 storage need more organization In process 31 1103 storage no combustibles in boiler Done 32 elec. romex safety ill nm through conduit f ^ 32 elec. light safety ill secure to bldg3 32 elec. romex safety ill secure to 'oists 32 elec. -box safety done 33 elec. fluor safety done 33 elec. cove late safety done 33 elec. panel safety done 33 elec. romex safety ill secure 33 elec. fluor safety ill around 34 elec. labeling safety ill complete labeling 34 elec. GFI '63 NEC states not -necessary None 34 elec. fixture safety ill secure to calling 34 elec. wet room pproved by stale inspectors at time of construction. None 34 elec. GFI See above 34-GFI 34 elec. wet room See above 34 -wet room 35 elec. open panel safety done 35 elec. GFI See above 34-GFI 35 elec. Wet room See above 34 -wet room 35 elec. GFI See above 34-GFI 35 elec. wet room See above 34 -wet room 35 elec. fixt. box safety ill add box 35 elec. wet room See above 34 -wet room 35 elec. closet fixt. safety ill change out 36 elec. wet room See above 34 -wet room 36 elec. GFI See above 34-GFI 36 elec. light flicker safety ill fix -, 36 elec. Ilabelina ISee(34-labeling) 36 elec. wet room See above 34 -wet room 36 elec. GFI See above 34-GFI 37 elec. romex safety done 37 elec. cover late safety done 37 elec. romex safety done 37 elec. '-box safety done 37 elec. GFI See above 34-GFI 37 elec. Wet room lSee above 34 -wet room 37 elec. GFI See above 34-GFI 37 elec. wet room See above 34 -wet room Page Item # Descri t. Response Proposed Action Final Action 1 1 headroom New Const., will fix R&R with correct height 1 2 crossbrace Not code None 1 3A stair New Const., will fix R&R with correct rise 1 3B stair New Const., will fix R&R with correct run 1 3C conc. ile Safety, will fix Remove concrete 1 4 draincover Safety, will fix Secure in place ' < 1 5 back Fixed Temporarily trench Weighing Iona term fix 1 6 elect.wires Covered with dirt Done 2 7 3story Ruled in 1990 as 2 1/2 None story, City required an engineers examination (done by John Meyer of Idaho Falls) and ruled that e were not a 3 story building. 3 8 ASW Built per Building None Inspector Requirements at that time. 3 9 Draftstop Built per Building Will add necessary draft <� Inspector Requirements at stop. (rt r(c q,<<n°l that time. 4 10 lovrhngs atBuilt per Building None WKSInspector Requirements at hal time. 4 11 boiler room Done with exception of Will tape joints for 1 hr I tape in some units 4 12 smoke det. _separation. Built per Building None Inspector Requirements and UBC requirements at that time. 4 13 heating All heating units None functioning properly at this time (20 below on day of inspection.) 4 14 1 hr firewall Built per Building None Inspector Requirements at that time. 5 15 smoke det. Built per Building None Inspector Requirements and UBC requirements at that time. 5 16 4" sphere Built per Building None Inspector Requirements and UBC requirements at hat time. 6 1 landing Safety, will fix R&R with appropriate dimensions. 6 2 egress Built per Building None Inspector Requirements at that time. 6 3 landing See 6-1 7 4e ress See B-2 7 5 SW See 3-8 8 6 draftstop Added draft slop requested Done 8 7 1 set stairs Built per Building Inspector Requirements at that time, also more than 10 other approved student housing with similar situation. None 8 8 old stairs Redoing all stairs on first units. Will conform to codes. _ 9 9 1 hr Built per Building firewall Inspector Requirements at that time. None 9 10 boiler room See 4-11 9 11 smoke det. See 4-12 9 12 heatin See 4-13 9 13 1 hr firewall See 4-14 10 14 smoke det. See 4-12 10 15 4" sphere See 5-16 11 1 landin See 6-1 11 2 e ress See 6-2 11 3 landin See 6-1 12 4 hdroom/ rd roved when built Will add guardrail 12 5 e cess See 6-2 12 6 hdroom/ rd See 12-4 12 7 e ress See 6-2 12 8 smoke det. Battery was dead, (smoke detectors are checked once a week Done 13 9 ASW See 3-8 13 10 Draftstop Done see 8-6 13 11 1 set stairs See 8-7 13 12 lold stairs See 8-8 14 13 11 hr firewall See 9-9 14 14 lboiler room See 4-11 14 15 Ismoke det. See 4-12 15 16 See 4-13 15 17 ll See 4-14 15 18 t. See 5-15 15 19 See 5-16 Ze 18 1 See 6-2 18 2 See 6-2 18 3 See 6-2 18 4 roved when built None 18 5 draftsto Done see 8-6 18 6 irs See 8-7 19 7 See 8-8 19 8 irs See 8-7 19 9 See 4-14 IheatinSee 19 10 m See 4-11 19 11 et. See 5-15 20 12 See 4-13 20 13 1 hr firewall See 9-9 20 14 smoke det. See5-15 20 15 4" sphere See 5-16 21 16 sloe Safety ill fix 21 17 fridge Safety ill move 22 1 egress See 6-2 22 2 draftstop Done see 8-6 22 3 1 set stairs See 8-7 22 4 old stairs See 8-6 23 5 1 hr firewall See 4-14 23 6 lbeam Safety ill fix 23 7 11hr&fireblk Done 23 8 1hr&fireblk Done 23 9 smoke det. See 5-15 24 10 heating See 4-13 24 11 1 hr firewall See 4-14 24 12 smoke det. see 5-15 24 13 4" sphere See 5-16 25 14 sloe See 21-16 26 1 hd/str/In a A proved when built 26 2 1hr/loun a Approved when built 27 3 entire bldg According to Joe code states 50% of building must be damaged to have o bring up to all new codes, this building is less han 20% Bring bumed apt, up to new codes leave rest per old code. 27 4 1draftstop Done see 8-6 27 5 1 set stairs See 8-7 27 6 old stairs See 8-8 28 7 1 hr firewall See 4-14 28 8 1hr/loun a See 26-2 28 9 boiler room See 4-11 28 10 smoke det. See 5-15 28 11 heatin See 4-13 29 12 back Done Working on permanent fix 29 13 1 hr firewall See 4-14 29 14 smoke det. See 5-15 29 15 4" sphere See 5-16 30 901 address Will add 30 902 fire road Currently exists, students ere not parked properly. Seeking stronger punishments for lack of parking compliance. 30 903 hydrants Built per city requirements at that time. No other complexes have fire hydrants. 30 8504 outlets A few broken or missing cover plates Done 30 1002 fire ext. No Issue Maintained as required. 30 1007 smoke det. .requirements Built as per city at that time. None 30 1202 a ress/stor storage eliminated Done 31 1103 storage Ineed more o anization In process 31 1103 Stora a no combustibles in boiler Done 32 eleC. romex safety ill run through conduit 32 elec. light safety ill secure to bld 3 32 elec. romex safety ill secure to loists 32 elec. '-box safety done 33 elec. fluor safety done 33 elec. cove late safety done 33 elec. panel safety done 33 elec. Iromex safety ill secure 7- 33 elec. Fluor safety ill ground 34 elec. labeling safety ill complete labeling 34 elec. GFI '63 NEC states not necessary None 34 elec. fixture safety ill secure to ceilin 34 elec. wet room Approved by state inspectors at time of construction. None 34 elec. GFI ISee above 34-GFI 34 elec. 1wet room ISee above 34 -wet room 35 elec. open panel safety done 35 elec. GFI See above 34-GFI 35 elec. wet room See above 34 -wet room 35 elec. GFI See above 34-GFI 35 elec. wet room See above 34 -wet room 35 elec. fixt. box safety ill add box 35 elec. wet room See above 34 -wet room 35 elec. closet fixt. safety ill chan a out 4 36 elec. Iwet room See above 34 -wet room 36 elec. GFI See above 34-GFI 36 elec. fl ht flicker safety ill fix 36 elec. Ilabelina See(34-labeling) 36 elec. wet room See above 34 -wet room 36 elec. GFI See above 34-GFI 37 elec. romex safety done 37 elec. coverplatesIsafety done 37 elec. romex safety done 37 elec. -box safety done 37 elec. GFI See above 34-GFI 37 elec. wet room See above 34 -wet room 37 elec. GFI See above 34-GFI 37 elec. wet room See above 34 -wet room CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS February 20, 1996 Mr. Stephen Clark, et al. 625 S 5000 W Rexburg, ID 83440 RE: Building Inspection Appeal for Applewood Apartments Dear Mr. Clark, et al.: NONE :..a . wrreSVeb-%Vald .20 The Uniform Building Code Board of Appeals, duly established by action of the Rexburg City Council, has met to consider your appeal over the Building Inspection Report of the Applewood Apartment located at 151 S 1st E in Rexburg. We have considered the Building Inspector's reports of February 9, 1996 for buildings 1A, 1B, 1C, 2, 3, and 4 in accordance with our authority as we understand it from the Code and have made the following determinations: 1) The Building Official's reports appear to be in compliance with applicable provisions of the Uniform Building Code and the inspections were not completed in an arbitrary nor capricious manner. 2) Previous actions by the Building Inspector(s), the inspection process, the issuance of permits, and the issuance of a certificate of occupancy do not absolve the building owner(s) of the responsibilities to meet all applicable provisions of the Code. Specifically, Section 307(f) gives specific authority to suspend or revoke a certificate of occupancy issued under the provision of the Code whenever "...it is determined that the building or structure, or portion thereof, is in violation of any ordinance or regulation or any provisions of this (UBC) code". If further information is required, please advise. Sincerely, CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS Charles Cartmill Ted Hill John Watson cc: City of Rexburg Winston Dyer Bart Stevens @ 1 2 O c D z 0 d O r r D W N D z b In m z to -J Co CID CD 00 Rexburg ci1y 0 2, x surf STATE OF • JOHN C. NRTER MAYdi ROSE BAGLEY Q RK RICHARD HORNER, TR FZER Steve Clark Route ill Box 230A Rexburg, Idaho 83440 Dear Mr. Clark: 12 NORTH CENTER ST. PHONE 12081 3593020 RE%BURG. IDAHO 83440 October 15, 1986 Chuck Frost, Chairman of Planning & Zoning, Nile Brown, Building Inspector, and Gordon Tychsen, Fire Inspector have recently inspected your parking area at your apartments on South 1st East. Their recommendations were: (1) You must have a 20 foot Driveway which is kept clear at all times for a Fire Lane; (2) You must warn your students that they can't park on the street or in your driveway. They also should not block any of the neighbor's driveways. On November 1 their cars will be towed away if they park on the street overnight. (3) You will not be allowed to build anymore apartments until you come to the Planning & Zoning with a Plot Plan and show adequate parking for your apartments. If you would like to discuss this further please attend the Planning & Zoning meeting on October 22, 1986, at 7:30 P. M. 7Sinc rely, n C Porter, Mayor rb 9Gh0CRNT�'� r O�PEXBURG �O Cly ly n m� geIISHEO NILE LL..yBOYLE ROSE BAGLEY "WK RICHARD HORNER THWURER 6 MMM WMER Mr. Steve Clark Applewood Apartments 151 So. 1st. East St. Rexburg, Idaho 83440 Dear Mr. Clark, V/ 2(exlmlry STATE OF IDAHO P.O. BOX 280 12 NORTH CENTER STREET REXBURG, IDAHO 83440 PHONE (208) 359-3020 FAX (208) 359-3022 February 9, 1996 Enclosed herewith are evaluations of the Applewood Apartment buildings. There are separate evaluations from: (1) State Electrical Inspector for Electrical Code Items, (2) City Fire Marshall regarding Fire Code Items, and (3) City Building Official for Uniform Building Code Items. These evaluations cover the four main apartment building. These buildings are shown on the enclosed map as Building 1-A, 1-B, & 1-C, Building 2, Building 3, and Building 4 which is the building that just had the fire. The two houses were not inspected or evaluated. It is our understanding that you want to bring these apartment buildings up to the various code standards. As soon as you have had a chance to read this material, we would like to meet with you to learn of your schedule for these improvements. There are a number of safety problems pointed out in these evaluations and we would like to see them eliminated as soon as possible. Very truly yours, Joseph A. Laird, P.E. CITY ENGINEER & BUILDING OFFICIAL STEVE CLARK APARTMENTS 151 SO. 1ST. EAST ST. BLDG. NO. 1A -- APTS. NUMBERS 101 to 105, 201 to 205 & 301 to 305. AT THE JOINT REQUEST OF STEVE CLARK, RICKS COLLEGE AND THE CITY OF REXBURG, THE SUBJECT BUILDING AND APARTMENTS WERE INSPECTED FOR ANY SAFETY VIOLATIONS OF THE UNIFORM BUILDING CODE. THIS INSPECTION WAS CONDUCTED ON FEBRUARY 2, 1996. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 1. -- Apartment # -305 - Headroom at stairs near this apartment is too low. Slopes across the the walkway with headrooms of 5'-9" to 6-8". Sec. 3306 (o) states that stairway headroom shall be not lelss than 6-8". 2. -- The tall sets of columns holding up the stairways need at least one set of cross -bracing to give the supporting structure the necessary sway bracing. 3. --The walkway (at point where stairs come up from the lower level) has wooden tie steps. The measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8". B. - The run shall be not less than 11 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. There is also a large roc k or mound of concrete embedded within the concrete sidewalk at this point that creats a tripping hazard . This rock or mound of concrete needs to be moved out of the way and a level piece of sidewalk installed in it's place 4. -- Storm drainage runoff at this east end of the main driveway is also a continuing problem. The metal plates and channels put across the sidewald are frequently out of their proper position and create a tripping problem for pedestrians using the sidewalk. 5 -- .Storm drainage runoff is also still a problem all along the north side of Buildings IA., 1B and 1-C where the storm drainage runoff from your buildings and property runs across the sidewalk just on the north side of your north fenceline , frequently causing silt deposition problems and/or icing problems in the winter. This storm drainage runoff is also eroding away the topsoil adjacent to your north building foundation footing which could cause settlement problems for this building. 6. -- On the north side of this building, we found that the main electrical line going from the power pole over to the building electrical metering and distribution facilities was just lying on top of the ground with no earth cover over it. It is very lucky that no one has come in contact with it as they could have been electrocuted. 7.-- Number of Stories and Size of Building - Sec. 408 provides a definition for GRADE (Adjacent Ground Level) and Sec. 420 provides a definition for First Story. Considering these definitions, this building does not have a basement. It has a First Floor, a Second Floor and a Third Floor. The area of the First Floor is approximately 4332 sq. ft. The area of the Second Floor is approximately 4897sq. ft. The area of the Third Floor is also approximately 4897 sq. ft. Sec. 1202 (b) states that: Group R, Division 1 Occupancies more than two stories in height or having more than 3000 square feet of floor area above the first story shall be of not less than one-hour fire -resistive construction throughout, except as provided in Section 1705 (b) 2. Sec. 1705 (b) 2 covers interior partitions. As this building is "more than two stories in height', it therefore has to be of one-hour fire - resistive construction throughout. This means that all exterior walls, all interior bearing walls, and all floor/ceiling assemblies within the entire building have to be of one-hour fire - resistive construction standards. This means that both sides of all of these referenced walls and ceilings have to be covered with at least one 5/8" layer of gypsum wallboard. / Sec. 1211 states that: A manual and automatic approved fire alarm system shall be installed in apartment houses that are three or more stories in height or contain more than 15 dwelling units ----in accordance with the Fire Code. Sec. 3802 (h) states that: An automatic sprinkler system shall be installed throughout every apartment house three or more stories in height or containing more than 15 dwelling units, As an alternate to the above, you could choose to construct a retaining wall (located at least 5 ft. away from the building) along the north side of the building and raise the ground level all along this north side to such an elevation that the bottom floor would qualify as a "basement". Under this scenario, the requirement for a fire alarm system and a fire sprinkler system would be eliminated. The Second Floor would still be over 3000 Sq. ft. so you would have to construct an Area Separation Wall at some interior location (say between Apts. 103,203 & 303 and Apts 104,204&304.) See discussion in the following Item # 8 on Area Separation Walls. Also note the following described requirements for one-hour fire walls separating apartment units (Item # 14) and one hour fire walls required along the exterior wall fronting on the three exterior exit balconies(Item # 10). Or, as indicated above, you could add extra gypsum wallboard as required to make the building one-hour fire -resistive throughout 8. -- Area Separation Walls - There should be a 2 -hour Area Separation Wall on the east end of this building and somewhere near the center of the building. Area Separation Walls are a very critical component of the fire protection system as they separate or divide a large building down into "smaller buildings". They are designed to help prevent the spread of fire from one of these "smaller buildings" to another. In this case, the required 2 -hour Area Separation Wall consists of five parts: A. The 2 -hour area separation wall(ASW) itself, which basically consists of 2 layers of 5/8 inch, type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing; B. The walls and eves on either end of the area separation wall (ASW) which have to meet 1 -hr. fire -resistive standards for 5 ft. either side of the area separation wall; C. When the trusses are parallel with the area separation wall(ASW), all roof framing within 5 ft. of the ASW must be encapsulated within a 1 -hr. fire -resistive shield (in this case, possibly, 2 layers of type X gypsum wallboard along the bottom chord of the trusses over to the nearest truss 5 ft. or more from the ASW, and then up, along and covering the entire face of the truss up to the bottom of the roof sheathing); D.There can be no openings in the roof within 5 ft. of the ASW; and E. The entire building is provided with not less than a Class B roofing. The above description basically sets forth what is required in Sec.505(e) 2 and Sec. 505(e) 3, Exception 2 (1985 UBC) for Sec 505 (f) 3 and 505 (0 4, Exception 2, in 1991 UBC]. There are also other possible alternatives set forth in Sec. 505 that could be considered. The ASW at the east end of this building does not meet the requirements of Sec. 505. The west end of Apartments 106 & 206 only have one layer of 1/2" gypsum wallboard, while the east ends of Apartments 105, 205 & 305 have two layers of 5/8" gypsum wallboard. The walls and eves within 5 ft. of the ASW do not meet 1 -hr. fire -resistive standards. The attic truss protection does not meet 1 -hr. fire -resistive standards. We did not check for openings within 5 ft. of the ASW or the type of roofing material that was on the buildings. This ASW does not meet the requirements of Sec. 505 (e) 5 -Buildings of Different Heights in the 1985 UBC [Sec. 505 (f) 6 in the 1991 UBC] either. In accordance with Sec. 505 (e) 5. the 2 hr. ASW must be extended up to a point 30 inches above the lower roof lever, provided the exterior wall for a height of 10 feet above the lower roof is of one-hour fire -resistive construction with openings protected by assemblies having a three -fourths -hour fire -protection rating. The second required Area Separation Wall could be located at any of the 2 hr. fire -resistive walls between the apartments. As indicated above, the rest of the ASW features, i.e. side wall treatment, attic truss treatment, roof type and exclusion of roof openings would all have to be adequately addressed at which ever secondary location is chosen. 9. -- The attic area did have draft stops (two layers of 5/8" thick gypsum wallboard) in line with the walls separating tenant spaces from each other and from other uses " as is required in Sec. 2516 (f) 4 B (ii). (pg. 204 of 1985 UBC) However some of these drafts stops did not go clear Pe. 3. Bldg. 1-A up to the underside of the roof sheathing as is required in the code. These draft stops need to be extended up to the bottom of the roof sheathing. 10. -- That portion of the exterior front building wall adjacent to the 1 st floor, 2nd floor and 3rd floor exterior exit balcony and that portion of the roof above these exterior exit balconies were not, but should have been, constructed to one-hour fire -resistive standards. See Sec. 3305 (g) which states that: " Walls of corridors and exterior exit balconies serving a Group R, Division 1 Occupancy having an occupant load of 10 or more --- shall be of not less than one-hour fire - resistive construction and the ceilings shall be not less than that required for a one-hour fire - resistive floor or roof system." 11. -- Sec. 1213 -- Every room containing a boiler, central heating plant or hot-water supply boiler in Division 1 Occupancies shall be separated from the rest of the building by not less than a one-hour fire -resistive occupancy separation. This requirement pertains to both walls and floor/ceilings. Note: This separation requirement does not apply for such rooms with equipment serving only one dwelling unit. 12. -- Throughout the apartment complex, some smoke detectors were battery operated and some were hardwired. Section 1210 (a) 3 states that: "In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source." Therefore, all smoke detectors should have been hard -wired into the building wiring system when they were originally installed. Some smoke detectors were not located in accordance with Sec. 1210 (a) 4. ( Also see Fire Marshal's comments) 13. -- Sec. 1211. -- Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 70 degrees F. at a point 3 feet above the floor in all habitable rooms. In these as in many of the other dwelling units, the stove oven and/ or portable electric heaters were being used to increase the temperature in the apartments. This review did not determine if the thermostats were not working properly or if the heating system was not capable of providing the required heat; whatever the reason, the heating facilities need to be repaired or upgraded so they meet the code requirements. 14. -- SEC. 1202 (b) -- "Walls and floors separating dwelling units in the same building shall be of not less than one-hour fire -resistive construction." All walls and ceilings within this building were found to be covered with 1/2" gypsum wallboard.except for the 2hr. Area Separation Walls which had 2 layers of 5/8 " gypsum wallboard on each side of the 2 x 4 or 2 x 6 framing. Pg. 4, Bldg. I- One-hour fire -resistive construction usually consists of one layer of 5/8 inch, Type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing and 1 layer of 5/8 inch, Type X gypsum wallboard on the bottom of the floor/ceiling assembly. The walls and ceilings throughout the building appear to be of 1/2 inch gypsum wallboard; therefore additional layers of gypsum wallboard are required over the existing "walls and floors separating dwelling units " or "walls and floors separating dwelling units from other uses." (such as furnace rooms ). THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 15. -- Smoke Detectors. Sec. 1210 (a) 4 (or Sec. 310.9.1.4 in 94 UBC) now states that: " In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area." 16. -- Guardrail opening dimensions. Sec. 1712 (a) (or Sec. 509.3 in 94 UBC) now states that: " Open guardrails shall have intermediate rails or an ornamental pattern such that a sphere 4 inches in diameter cannot pass through." NOTE: THIS INSPECTION WAS GENERALLY LIMITED TO ITEMS IN PLAIN AND FULL VIEW OF THE INSPECTOR. ATTICS WERE INSPECTED FROM THE ATTIC ACCESS OPENING. GYPSUM WALLBOAD THICKNESSES WERE MEASURED AT ELECTRICAL OUTLET FIXTURES AND LIGHT FIXTURES OR WHERE OPENINGS IN THE EXTERIOR SIDING MADE THE GYPSUM WALLBOAD VISIBLE AND MEASUREABLE. NO ATTEMPT WAS MADE TO ASCERTAIN THE STRUCTURAL SOUNDNESS OF THE BUILDINGS OR RELATED FACILITIES. THIS INSPECTION AND REPORT DO NOT PROFESS TO HAVE COVERED ALL OF THE ITEMS INCLUDED IN THE UNIFORM BUILDING CODE. Joseph A. Laird, P.E. CITY ENGINEER & BUILDING OFFICIAL Pg.5, Bldg. 1-A 2-9-96 Date STEVE CLARK APARTMENTS 151 SO. 1ST. EAST ST. BLDG. NO. IB -- APTS. NUMBERS 106, 107, 206, & 207. AT THE JOINT REQUEST OF STEVE CLARK, RICKS COLLEGE AND THE CITY OF REXBURG, THE SUBJECT BUILDING AND APARTMENTS WERE INSPECTED FOR ANY SAFETY VIOLATIONS OF THE UNIFORM BUILDING CODE. THIS INSPECTION WAS CONDUCTED ON FEBRUARY 2, 1996. THE FOLLOWING LISPED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1985, 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 1. -- Apartment # 106 - The landing in front of the main doorway is 4 1/2 inches lower than the sill of the doorway. Sec. 3304 (h) states that: "Regardless of occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall not be more than 1 inch lower than the threshold of the doorway." The measured length of the landing in the direction of travel (outward from the door to the first step) is 36 inches. Sec. 3304 (i) states that: "Landings shall have a length measured in the direction of travel of not less than 44 inches." The measured stairway headroom is 6'- 8" which is adequate. Measured stairway risers: One riser @ 8 3/4" and three risers @ 7 1/2" each. Measured stairway runs: Two @ 9 5/8" & one @ 9 1/8 ". These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8" B. - The run shall be not less than 11 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. 2. -- Apartment # 106 - Bedroom window is 3' 10" x 2' 10" horizontal slider with 30" x 32" = 5.11 sq. ft. of openable area which does not meet net area of 5.7 sq.ft. required by UBC Sec. 1204. 3. -- Apartment # 107 - The landing in front of the main doorway is 4 1/2 inches lower than the sill of the doorway. Sec. 3304 (h) states that: "Regardless of occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall not be more than 1 inch lower than the threshold of the doorway." The measured length of the landing in the direction of travel (outward from the door to the first step) is 27 inches. Sec. 3304 (i) states that: "Landings shall have a length measured in the direction of travel of not less than 44 inches." The measured stairway headroom is 6-2". Required headroom is 6'- 6" in Sec. 3306 (p) of the 1985 UBC. Required headroom is 6'- 8" in 1988, 1991, & 1994 UBC Measured stairway risers: One @ 6 1/2", one @6", one @ 7 1/2 & two @ 8". Measured stairway runs: Two @ 9 3/4", one @ 8 1/2" & one @ 11" These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8". B. - The run shall be not less than 11 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. 4.-- Apartment # 206 - Bedroom windows ( 3' 10" x 2' 10" with 30" x 32" = 5.11 sq. ft. openable area) do not meet the requirements for escape or rescue windows as set forth in UBC Sec. 1204. 5. -- Area Separation Walls - There should be 2 -hour Area Separation Walls on both the east and west ends of this building. Area Separation Walls are a very critical component of the fire protection system as they separate or divide a large building down into "smaller buildings". They are designed to help prevent the spread of fire from one of these "smaller buildings" to another. In this case, the required 2 -hour Area Separation Wall consists of five parts: A. The 2 -hour area separation wall(ASW) itself, which basically consists of 2 layers of 5/8 inch, type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing; B. The walls and eves on either end of the area separation wall (ASW) which have to meet 1 -hr. fire -resistive standards for 5 ft. either side of the area separation wall; C. When the trusses are parallel with the area separation wall(ASW), all roof framing within 5 ft. of the ASW must be encapsulated within a 1 -hr. fire -resistive shield (in this case, possibly, 2 layers of type X gypsum wallboard along the bottom chord of the trusses over to the nearest truss 5 ft. or more from the ASW, and then up, along and covering the entire face of the truss up to the bottom of the roof sheathing); D.There can be no openings in the roof within 5 ft. of the ASW; and E. The entire building is provided with not less than a Class B roofing. The above description basically sets forth what is required in Sec.505(e) 2 and Sec. 505(e) 3, Exception 2 (1985 UBC) [or Sec 505 (f) 3 and 505 (f) 4, Exception 2, in 1991 UBC]. There are also other possible alternatives set forth in Sec. 505 that could be considered. The ASWs at either end of this building do not meet the requirements of Sec. 505. The east end of Apartments 107 & 207 only have one layer of 1/2 gypsum wallboard, while the west ends of Apartments 108 & 208 have two layers of 5/8" gypsum wallboard. The walls and APINARIIIIII-Iffm eves within 5 ft. of the ASW do not meet 1 -hr. fire -resistive standards. The attic truss protection does not meet 1 -hr. fire -resistive standards. We did not check for openings within 5 ft. of the ASW or the type of roofing material that was on the buildings. This ASW does not meet the requirements of Sec. 505 (e) 5 -Buildings of Different Heights in the 1985 UBC [Sec. 505 (1) 6 in the 1991 UBC] either. The west end of Apartments 106 & 206 only have one layer of 1/2" gypsum wallboard, while the east ends of Apartments 105, 205 & 305 have two layers of 5/8" gypsum wallboard. The walls and eves within 5 ft. of the ASW do not meet 1 -hr. fire -resistive standards. The attic truss protection does not meet ]-hr. fire -resistive standards. We did not check for openings within 5 ft. of the ASW or the type of roofing material that was on the buildings. This ASW does not meet the requirements of Sec. 505 (e) 5 -Buildings of Different Heights in the 1985 UBC [Sec. 505 (f) 6 in the 1991 UBC] either. 6. -- The attic area did not have draft stops " in line with the walls separating tenant spaces from each other and from other uses " as is required in Sec. 2516 (f) 4 B (ii). (pg. 204 of 1985 UBC) 7. -- The 2nd story (Apartments 206 & 207) has an occupant load of 12. Sec. 3303 (a), Exception 2 states that: "Two or more dwelling units on the second story may have access to only one common exit when the total occupant load does not exceed 10." The occupant load of 12 for this story is larger than the allowed occupant load of 10. Therefore a second stairway is required from the 2nd story exterior exit balcony. 8. -- Main stairway to 2nd story apartments. Speaking generally regarding all the main stairway units, the tread rise was usually around 7 1/2 inches with the top rise usually being 9 to 10 inches in height. The tread run was found to be usually around 10 to 10 1/2 inches; however some tread runs were as small as 8 3/4 inches. These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. B. - The run shall be not less than i 1 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. The interior edge of the stairway runner is approximately 8 inches from the side of the building. This leaves a potentially dangerous gap between stair and building where someone could fall and be injured. A guardrail is required along this interior edge of the stairway to bring it into conformance with Sec. 1711. The wire mesh stairway treads seem to be breaking loose from the perimeter bracing and need to be rewelded, replaced or repaired in some other manner so that they are safe and capable of carrying the required load set forth in Table 16A of the UBC , namely that: "Individual stair treads shall be designed to support a 300 pound concentrated load placed in a position which would cause maximim stress." Maintenance needs to be accomplished as is required in Sec.104 (d). 9. -- That portion of the exterior building wall adjacent to the 2nd floor exterior exit balcony and that portion of the roof above the exterior exit balcony were not, but should have been, constructed to one-hour fire -resistive standards. See Sec. 3305 (g) which states that: " Walls of corridors and exterior exit balconies serving a Group It, Division 1 Occupancy having an occupant load of 10 or more --- shall be of not less than one-hour fire -resistive construction and the ceilings shall be not less than that required for a one-hour fire -resistive floor or roof system." J 10. -- Sec. 1213 -- Every room containing a boiler, central heating plant or hot-water supply boiler in Division I Occupancies shall be separated from the rest of the building by not less than a one-hour fire -resistive occupancy separation. This requirement pertains to both walls and floor/ceilings. 11. -- Throughout the apartment complex, some smoke detectors were battery operated and some were hardwired. Section 1210 (a) 3 states that: "In new constriction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source." Therefore, all smoke detectors should have been hard -wired into the building wiring system when they were originally installed. Some smoke detectors were not located in accordance with Sec. 1210 (a) 4. ( Also see Fire Marshal's comments) 12. -- Sec. 1211. -- Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 70 degrees F. at a point 3 feet above the floor in all habitable rooms. In these as in many of the other dwelling units, the stove oven and/ or portable electric heaters were being used to increase the temperature in the apartments. This review did not determine if the thermostats were not working properly or if the heating system was not capable of providing the required heat; whatever the reason, the heating facilities need to be repaired or upgraded so they meet the code requirements. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE. 13. -- SEC. 1202 (b) -- "Walls and floors separating dwelling units in the same building shall be of not less than one-hour fire -resistive construction." One-hour fire -resistive construction usually consists of one layer of 5/8 inch, Type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing and 1 layer of 5/8 inch, Type X gypsum wallboard on the bottom of the floor/ceiling assembly. The walls and ceilings throughout the building appear to be of 1/2 inch gypsum wallboard; therefore additional layers of gypsum wallboard are required over the existing "walls and floors separating dwelling units " or "walls and floors separating dwelling units from other uses." (such as furnace rooms or storage rooms as was required in the 1985 UBC.) All walls and ceilings within this building were found to be covered with 1/2" gypsum wallboard. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 14. -- Smoke Detectors. Sec. 1210 (a) 4 (or Sec. 310.9.1.4 in 94 UBC) now states that: " In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area." 15. -- Guardrail opening dimensions. Sec. 1712 (a) (or Sec. 509.3 in 94 UBC) now states that: " Open guardrails shall have intermediate rails or an ornamental pattern such that a sphere 4 inches in diameter cannot pass through." NOTE: THIS INSPECTION WAS GENERALLY LIMITED TO ITEMS IN PLAIN AND FULL VIEW OF THE INSPECTOR. ATTICS WERE INSPECTED FROM THE ATTIC ACCESS OPENING. GYPSUM WALLBOAD THICKNESSES WERE MEASURED AT ELECTRICAL OUTLET FIXTURES AND LIGHT FIXTURES OR WHERE OPENINGS IN THE EXTERIOR SIDING MADE THE GYPSUM WALLBOAD VISIBLE AND MEASUREABLE. NO ATTEMPT WAS MADE TO ASCERTAIN THE STRUCTURAL SOUNDNESS OF THE BUILDINGS OR RELATED FACILITIES. THIS INSPECTION AND REPORT DO NOT PROFESS TO HAVE COVERED ALL OF THE ITEMS INCLUDED IN THE UNIFORM BUILDING CODE. 2-9-96 Joseph A. Laird, P.E. Date. CITY ENGINEER & BUILDING OFFICIAL Pg. 5, Bldg. 1-B STEVE CLARK APARTMENTS 151 SO. 1 ST. EAST ST. BLDG. NO. i C — APTS. NUMBERS 108, 109, 208, & 209. AT THE JOINT REQUEST OF STEVE CLARK, RICKS COLLEGE AND THE CITY OF REXBURG, THE SUBJECT BUILDING AND APARTMENTS WERE INSPECTED FOR ANY SAFETY VIOLATIONS OF THE UNIFORM BUILDING CODE. THIS INSPECTION WAS CONDUCTED ON FEBRUARY 2, 1996. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1985, 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 1. -- Apartment # 109 - The landing in front of the main doorway is 4 1/2 inches lower than the sill of the doorway. Sec. 3304 (h) states that: "Regardless of occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall not be more than 1 inch lower than the threshold of the doorway." The measured length of the landing in the direction of travel (outward from the door to the first step) is 24 1/2 inches. Sec. 3304 (i) states that: "Landings shall have a length measured in the direction of travel of not less than 44 inches." The measured stairway headroom is 6-2 1/2". Required headroom is 6- 6" in Sec. 3306 (p) of the 1985 UBC. Required headroom is 6'- 8" in 1988, 1991, & 1994 UBC Measured stairway risers: Top riser @ 5 1/2" and other risers @ 6 1/2" each. Measured stairway runs: Two @ 10 1/2", one @ 12" & one @ 10" These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8". B. - The run shall be not less than I 1 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. 2. -- Apartment # 109 - Bedroom windows are 5'8" x 2'8" horizontal slider = 6.25 sq. ft. of openable area, which meet code requirements for area, width and height. However the bottom of the sill is 50 " above the floor which is more than the 44" maximum floor- to- sill height allowed by UBC Sec. 1204. 3. -- Apartment # 108 - The landing in front of the main doorway is 6 1/2 inches lower than the sill of the doorway. Sec. 3304 (h) states that: "Regardless of occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall not be more than 1 inch lower than the threshold of the doorway." The measured length of the landing in the direction of travel (outward from the door to the first step) is 32 inches. Sec. 3304 (i) states that: "Landings shall have a length measured in the direction of travel of not less than 44 inches." The measured stairway headroom is 6'-1 1/2". Required headroom is 6'- 6" in Sec. 3306 (p) of the 1985 UBC. Required headroom is 6'- 8" in 1988, 1991, & 1994 UBC Measured stairway risers: 2 risers @ 6 1/2" each and 2 risers @ 7 1/2' each. Measured stairway runs: One @ 9", one @ 10" & one @ 11" These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8" B. - The run shall be not less than 11 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. 4.-- Apartment # 108 - Interior stairs between living room and bedrooms. Stairs going up to one bedroom are 34 to 36 inches in width with 5'-10" of headroom at the top of the stairs. Stairs going down to two bedrooms are 32 "wide and have headrooms of 5'-8" and 6'-1". There is no guardrail separating the upper stairs from the lower stairs. Required headroom is 6'- 6" in Sec. 3306 (p) of the 1985 UBC. Required headroom is 6'- 8" in 1988, 1991, & 1994 UBC. Required stairway width is T- 0" as set forth in Sec. 3306 (b) . Sec. 1711 requires a guardrail along stairs whenever there is more than a 30 inch difference in elevation between two different levels. 5.-- Apartment # 208 - Bedroom windows ( 28" x 19" = 3.69 sq. ft. openable area) do not meet the requirements for escape or rescue windows as set forth in UBC Sec. 1204. 6.-- Apartment # 208 - Interior stairs between living room and bedrooms. Stairs go up to two bedrooms and down to one bedroom. Stairs are 34 " wide and have headrooms of 6-0" and 6-8". There is no guardrail separating the upper stairs from the lower stairs. Required headroom is 6'- 6" in Sec. 3306 (p) of the 1985 UBC. Required headroom is 6'- 8" in 1988, 1991, & 1994 UBC. Required stairway width is Y- 0" as set forth in Sec. 3306 (b) . Sec. 1711 requires a guardrail along stairs whenever there is more than a 30 inch difference in elevation between two different levels. 7. -- Apartment # 209 - Bedroom windows (22" x 30" = 4.58 sq.ft. openable area) do not meet the requirements for escape or rescue windows as set forth in UBC Sec. 1204. 8. -- Apartment # 209 - Kitchen smoke detector not working. Pe 2 Bldg 1- C 9. -- Area Separation Walls - There should be a 2 -hour Area Separation Walls on the west end of this building. Area Separation Walls are a very critical component of the fire protection system as they separate or divide a large building down into "smaller buildings". They are designed to help prevent the spread of fire from one of these "smaller buildings" to another. In this case, the required 2 -hour Area Separation Wall consists of five parts: A. The 2 -hour area separation wall(ASW) itself, which basically consists of 2 layers of 5/8 inch, type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing; B. The walls and eves on either end of the area separation wall (ASW) which have to meet 1 -hr. fire -resistive standards for 5 ft. either side of the area separation wall; C. When the trusses are parallel with the area separation wall(ASW), all roof framing within 5 ft. of the ASW must be encapsulated within a 1 -hr. fire -resistive shield (in this case, possibly, 2 layers of type X gypsum wallboard along the bottom chord of the trusses over to the nearest truss 5 ft. or more from the ASW, and then up, along and covering the entire face of the truss up to the bottom of the roof sheathing); D.There can be no openings in the roof within 5 ft. of the ASW; and E. The entire building is provided with not less than a Class B roofing. The above description basically sets forth what is required in Sec.505(e) 2 and Sec. 505(e) 3, Exception 2 (1985 UBC) [or Sec 505 (f) 3 and 505 (f) 4, Exception 2, in 1991 UBC]. There are also other possible alternatives set forth in Sec. 505 that could be considered. The ASW at the west end of this building does not meet the requirements of Sec. 505. The east end of Apartments 107 & 207 only have one layer of 1/2" gypsum wallboard, while the west ends of Apartments 108 & 208 have two layers of 5/8" gypsum wallboard. The walls and eves within 5 ft. of the ASW do not meet 1 -hr. fire -resistive standards. The attic truss protection does not meet 1 -hr. fire -resistive standards. We did not check for openings within 5 ft. of the ASW or the type of roofing material that was on the buildings. This ASW does not meet the requirements of Sec. 505 (e) 5 -Buildings of Different Heights in the 1985 UBC [Sec. 505 (f) 6 in the 1991 UBC] either. 10. -- The attic area did not have draft stops " in line with the walls separating tenant spaces from each other and from other uses " as is required in Sec. 2516 (f) 4 B (ii). (pg. 204 of 1985 UBC) 11. — The 2nd story (Apartments 208 & 209) has an occupant load of 12. Sec. 3303 (a), Exception 2 states that: "Two or more dwelling units on the second story may have access to only one common exit when the total occupant load does not exceed 10." The occupant load of 12 for this story is larger than the allowed occupant load of 10. Therefore a second stairway is required from the 2nd story exterior exit balcony. 12. -- Main stairway to 2nd story apartments. Speaking generally regarding all the main stairway units, the tread rise was usually around 7 1/2 incites with the top rise usually being 9 to 10 inches in height. The tread run was found to be usually around 10 to 10 1/2 inches; however some tread runs were as small as 8 3/4 inches. These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. B. - The run shall be not less than 11 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. The interior edge of the stairway runner is approximately 7 1/2 inches from the side of the building. This leaves a potentially dangerous gap between stair and building where someone could fall and be injured. A guardrail is required along this interior edge of the stairway to bring it into conformance with Sec. 1711. The wire mesh stairway treads seem to be breaking loose from the perimeter bracing and need to be rewelded, replaced or repaired in some other manner so that they are safe and capable of carrying the required load set forth in Table 16A of the UBC , namely that: "Individual stair treads shall be designed to support a 300 pound concentrated load placed in a position which would cause maximim stress." Maintenance needs to be accomplished as is required in Sec. 104 (d). 13. -- That portion of the exterior building wall adjacent to the 2nd floor exterior exit balcony and that portion of the roof above the exterior exit balcony were not, but should have been, constructed to one-hour fire -resistive standards. See Sec. 3305 (g) which states that: " Walls of corridors and exterior exit balconies serving a Group R, Division 1 Occupancy having an occupant load of 10 or more --- shall be of not less than one-hour fire -resistive construction and the ceilings shall be not less than that required for a one-hour fire -resistive floor or roof system." 14. -- Sec. 1213 -- Every room containing a boiler, central heating plant or hot-water supply boiler in Division 1 Occupancies shall be separated from the rest of the building by not less than a one-hour fire -resistive occupancy separation. This requirement pertains to both walls and floor/ceilings. 15. -- Throughout the apartment complex, some smoke detectors were battery operated and some were hardwired. Section 1210 (a) 3 states that: "In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source." Therefore, all smoke detectors should have been hard -wired into the building wiring system when they were originally installed. Some smoke detectors were not located in accordance with Sec. 1210 (a) 4. ( Also see Fire Marshal's comments) 16. -- Sec. 1211. -- Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 70 degrees F. at a point 3 feet above the floor in all habitable rooms. In these as in many of the other dwelling units, the stove oven and/ or portable electric heaters were being used to increase the temperature in the apartments. This review did not determine if the thermostats were not working properly or if the heating system was not capable of providing the required heat; whatever the reason, the heating facilities need to be repaired or upgraded so they meet the code requirements. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE. 17. -- SEC. 1202 (b) -- "Walls and floors separating dwelling units in the same building shall be of not less than one-hour fire -resistive construction." One-hour fire -resistive construction usually consists of one layer of 5/8 inch, Type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing and 1 layer of 5/8 inch, Type X gypsum wallboard on the bottom of the floor/ceiling assembly. The walls and ceilings throughout the building appear to be of 1/2 inch gypsum wallboard; therefore additional layers of gypsum wallboard are required over the existing "walls and floors separating dwelling units " or "walls and floors separating dwelling units from other uses." (such as furnace rooms or storage rooms as was required in the 1985 UBC.) Apartment # 208 had 5/8" gypsum wallboad on the east apartment wall and 1/2" gypsum wallboard on the ceiling. The west wall of Apartments 108 and 208 had 2 layers of 5/8" gypsum wallboad . The rest of the gypsum wall boards in the apartments were 1/2" thick. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 18. -- Smoke Detectors. Sec. 1210 (a) 4 (or Sec. 310.9.1.4 in 94 UBC) now states that: " In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area." 19. -- Guardrail opening dimensions. Sec. 1712 (a) (or Sec. 509.3 in 94 UBC) now states that: " Open guardrails shall have intermediate rails or an ornamental pattern such that a sphere 4 inches in diameter cannot pass through." NOTE: THIS INSPECTION WAS GENERALLY LIMITED TO ITEMS IN PLAIN AND FULL VIEW OF THE INSPECTOR. ATTICS WERE INSPECTED FROM THE ATTIC ACCESS OPENING. GYPSUM WALLBOAD THICKNESSES WERE MEASURED AT WT -1 AN M «�] ELECTRICAL OUTLET FIXTURES AND LIGHT FIXTURES OR WHERE OPENINGS IN THE EXTERIOR SIDING MADE THE GYPSUM WALLBOAD VISIBLE AND MEASUREABLE. NO ATTEMPT WAS MADE TO ASCERTAIN THE STRUCTURAL SOUNDNESS OF THE BUILDINGS OR RELATED FACILITIES. THIS INSPECTION AND REPORT DO NOT PROFESS TO HAVE COVERED ALL OF THE ITEMS INCLUDED IN THE UNIFORM BUILDING CODE. Date: 2-9-96 Joseph A. Laird, P.E. CITY ENGINEER & BUILDING OFFICIAL STEVE CLARK APARTMENTS 151 SO. 1ST. EAST ST. BLDG. NO.2 — APTS. NUMBERS 110, 111,112, 210, & 211. AT THE JOINT REQUEST OF STEVE CLARK, RICKS COLLEGE AND THE CITY OF REXBURG, THE SUBJECT BUILDING AND APARTMENTS WERE INSPECTED FOR ANY SAFETY VIOLATIONS OF THE UNIFORM BUILDING CODE. THIS INSPECTION WAS CONDUCTED ON FEBRUARY 2, 1996. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1985, 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 1. -- Apartment # 110 -Bedroom windows ( 4'8" x 1'8") do not meet the requirements for escape or rescue windows as set forth in UBC Sec. 1204. 2. -- Apartment # 111 - Bedroom windows (4'0" x 2'6") do not meet the requirements for escape or rescue windows as set forth in UBC Sec. 1204. 3.-- Apartment # 210 - Bedroom windows (2'8" x2'10" H.S., 4'0" x 2'8" H.S. & 3'8" x 3'4"H.S.) do not meet the requirements for escape or rescue windows as set forth in UBC Sec. 1204. 4. -- Apartment # 110 - Stairway between 1 st floor living area and 2nd floor bedrooms. Measured stairway head room is 5' 10" at 1 st floor entryway to winding stairway. Measured stairway headroom at top of stairway is 6' V. Required headroom is 6' 6" in Sec 3306 (p) of the 1985 UBC. Required headroom is 68" in 1988, 1991, & 1994 UBC. Measured width of stairway is 2'- 4 1/2" at 1st floor entryway to winding stairway. Required stairway width is T- 0" as set forth in Sec. 3306 (b) . Measured rise = 7 I/2 inch and run = 8 1/2 inch. Required rise = 8 -inch maximum and run =9 - inch minimum in Sec. 3306 (c), Exception 1. Measurements were not made to determine whether or not the stairs met the requirements of Sec 3306 (d) Winding Stairways or Section 3306 (f) Spiral Stairways. 5. -- The attic area did not have draft stops " in line with the walls separating tenant spaces from each other and from other uses " as is required in Sec. 2516 (f) 4 B (ii). (pg. 204 of 1985 UBC) 6. -- The 2nd story (Apartments 210 & 211) has an occupant load of 12. Sec. 3303 (a), Exception 2 states that: "Two or more dwelling units on the second story may have access to only one common exit when the total occupant load does not exceed 10." The occupant load of 12 for this story is larger than the allowed occupant load of 10. Therefore a second stairway is required from the 2nd story exterior exit balcony. 7. -- Main stairway to 2nd story apartments. Speaking generally regarding all the main stairway units, the tread rise was usually around 7 1/2 inches with the top rise usually being 9 to 10 inches in height. The tread run was found to be usually around 10 to 10 1/2 inches; however some tread runs were as small as 8 3/4 inches. These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. B. - The run shall be not less than 11 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. The interior edge of the stairway runner is approximately 5 inches from the side of the building. This leaves a potentially dangerous gap between stair and building where someone could fall and be injured. A guardrail is required along this interior edge of the stairway to bring it into conformance with Sec. 1711. The wire mesh stairway treads seem to be breaking loose from the perimeter bracing and need to be rewelded, replaced or repaired in some other manner so that they are safe and capable of carrying the required load set forth in Table 16A of the UBC , namely that: "Individual stair treads shall be designed to support a 300 pound concentrated load placed in a position which would cause maximim stress." Maintenance needs to be accomplished as is required in Sec.104 (d). 8. -- That portion of the exterior building wall adjacent to the 2nd floor exterior exit balcony and that portion of the roof above the exterior exit balcony were not, but should have been, constructed to one-hour fire -resistive standards. See Sec. 3305 (g) which states that: " Walls of corridors and exterior exit balconies serving a Group R, Division 1 Occupancy having an occupant load of 10 or more --- shall be of not less than one-hour fire -resistive construction and the ceilings shall be not less than that required for a one-hour fire -resistive floor or roof system." 9. -- See. 1202(b) -- Storage and laundry rooms--- shall be separated from the rest of the building by not less than one-hour fire -resistive occupancy separations. This requirement pertains to both walls and floor/ceilings. 10. -- Sec. 1213 -- Every room containing a boiler, central heating plant or hot-water supply boiler in Division 1 Occupancies shall be separated from the rest of the building by not less than a one-hour fire -resistive occupancy separation. This requirement pertains to both walls and floor/ceilings. 11. -- Throughout the apartment complex, some smoke detectors were battery operated and some were hardwired. Section 1210 (a) 3 states that: "In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source." Therefore, all smoke detectors should have been hard -wired into the building wiring system when they were originally installed. Some smoke detectors were not located in accordance with See. 1210 (a) 4. ( Also see Fire Marshal's comments) 12. -- Sec. 1211. -- Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 70 degrees F. at a point 3 feet above the floor in all habitable rooms. In these as in many of the other dwelling units, the stove oven and/ or portable electric heaters were being used to increase the temperature in the apartments. This review did not determine if the thermostats were not working properly or if the heating system was not capable of providing the required heat; whatever the reason, the heating facilities need to be repaired or upgraded so they meet the code requirements. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE. 13. -- SEC. 1202 (b) -- "Walls and floors separating dwelling units in the same building shall be of not less than one-hour fire -resistive construction." One-hour fire -resistive construction usually consists of one layer of 5/8 inch, Type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing and 1 layer of 5/8 inch, Type X gypsum wallboard on the bottom of the floor/ceiling assembly. The walls and ceilings throughout the building appear to be of 1/2 inch gypsum wallboard; therefore additional layers of gypsum wallboard are required over the existing "walls and floors separating dwelling units " or "walls and floors separating dwelling units from other uses." (such as furnace rooms or storage rooms as was required in the 1985 UBC.) THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 14. -- Smoke Detectors. Sec. 1210 (a) 4 (or Sec. 310.9.1.4 in 94 UBC) now states that: " In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area." 15. -- Guardrail opening dimensions. Sec. 1712 (a) (or Sec. 509.3 in 94 UBC) now states that: " Open guardrails shall have intermediate rails or an ornamental pattern such that a sphere 4 inches in diameter cannot pass through." PQ. 3- Bldg. 2. GENERAL SAFETY ITEMS 16. -- The slope of the walkway approach to Apt. # 110 is very steep and could be a hazard, especially under icy conditions. 17. -- A refrigerator stored outside of the building was set so close to the building that it would block egress from the lower story bedroom windows. NOTE: THIS INSPECTION WAS GENERALLY LIMITED TO ITEMS IN PLAIN AND FULL VIEW OF THE INSPECTOR. ATTICS WERE INSPECTED FROM THE ATTIC ACCESS OPENING. GYPSUM WALLBOAD THICKNESSES WERE MEASURED AT ELECTRICAL OUTLET FIXTURES AND LIGHT FIXTURES OR WHERE OPENINGS IN THE EXTERIOR SIDING MADE THE GYPSUM WALLBOAD VISIBLE AND MEASUREABLE. NO ATTEMPT WAS MADE TO ASCERTAIN THE STRUCTURAL SOUNDNESS OF THE BUILDINGS OR RELATED FACILITIES. THIS INSPECTION AND REPORT DO NOT PROFESS TO HAVE COVERED ALL OF THE ITEMS INCLUDED IN THE UNIFORM BUILDING CODE. Date 2-9-96 Joseph A. Laird, P.E. CITY ENGINEER & BUILDING OFFICIAL w!x,=!jrir!AR STEVE CLARK APARTMENTS 151 SO. I ST. EAST ST. BLDG. NO.3 -- APTS. NUMBERS 113, 114, 212 & 213. AT THE JOINT REQUEST OF STEVE CLARK, RICKS COLLEGE AND THE CITY OF REXBURG, THE SUBJECT BUILDING AND APARTMENTS WERE INSPECTED FOR ANY SAFETY VIOLATIONS OF THE UNIFORM BUILDING CODE. THIS INSPECTION WAS CONDUCTED ON FEBRUARY 2, 1996. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1985, 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 1. -- Apartment # 213 -Bedroom windows (4'0" x 1'8") do not meet the requirements for escape or rescue windows as set forth in UBC Sec. 1204. The covered walkway area south of Apartment # 213 must be kept free of stored couches, beds, refrigerators, etc. as this area serves as the escape route from the bedroom escape -rescue windows. If the east end of the area is going to be used for enclosed storage, it's walls and ceiling will have to have a 1 -hour fire -resistive rating as set forth in Table 5A and Sec. 310.2.2 of the 1994 UBC. 2. -- The attic area did not have draft stops " in line with the walls separating tenant spaces from each other and from other uses "( such as storage room from dwelling units) as is required in Sec. 2516 (f) 4 B (ii). (pg. 204 of 1985 UBC) An attic access opening will need to be added above Apt. 212 after the attic draft stops are in place. Minimum opening size is 22 inches by 30 inches. [See Sec. 3205 (a)] Additional roof vents may be needed after the attic area is compartmentalized by the required draft stops. 3. -- The 2nd story (Apartments 212 & 213) has an occupant load of 12. Sec. 3303 (a), Exception 2 states that: "Two or more dwelling units on the second story may have access to only one common exit when the total occupant load does not exceed 10." The occupant load of 12 for this story is larger than the allowed occupant load of 10. Therefore a second stairway is required from the 2nd story exterior exit balcony. 4. -- Main stairway to 2nd story apartments. Speaking generally regarding all the main stairway units, the tread rise was usually around 7 1/2 inches with the top rise usually being 9 to 10 inches in height. The tread run was found to be usually around 10 to 10 1/2 inches; however some tread runs were as small as 8 3/4 inches. These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. B. - The run shall be not less than 1 I inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. The interior edge of the stairway runner is approximately 7 inches from the side of the building. This leaves a potentially dangerous gap between stair and building where someone could fall and be injured. A guardrail is required along this interior edge of the stairway to bring it into conformance with Sec. 1711. The wire mesh stairway treads seem to be breaking loose from the perimeter bracing and need to be rewelded, replaced or repaired in some other manner so that they are safe and capable of carrying the required load set forth in Table 16A of the UBC , namely that: "Individual stair treads shall be designed to support a 300 pound concentrated load placed in a position which would cause maximim stress." Maintenance needs to be accomplished as is required in Sec. 104 (d). 5. -- That portion of the exterior building wall adjacent to the 2nd floor exterior exit balcony and that portion of the roof above the exterior exit balcony were not, but should have been, constructed to one-hour fire -resistive standards. See Sec. 3305 (g) which states that: " Walls of corridors and exterior exit balconies serving a Group It, Division 1 Occupancy having an occupant load of 10 or more --- shall be of not less than one-hour fire -resistive construction and the ceilings shall be not less than that required for a one-hour fire -resistive floor or roof system." 6. -- The double 2 x 6 beam supporting the exterior exit balcony showed excessive deflection and should be checked to see if it needs to have stronger beam members or more closely spaced support columns. 7. -- The 2nd story storage room does not have the required 1 -hour fire -resistive walls. (See Sec. 1202(b) which states that: " Storage and laundry rooms--- shall be separated from the rest of the building by not less than one-hour fire -resistive occupancy separations. " This requirement pertains to both walls and floor/ceilings.) There was no fire -blocking at the rafter tie-in between the storage room and the adjacent apartment unit. The exhaust vent going from the heating unit through the floor and ceiling did not have the required 1" clearance between it and the adjacent floor and ceiling materials. 8. -- The 1 at story furnace room/storage room does not have the required 1 -hour fire -resistive walls and floor/ceiling above it. (See Sec. 1213 -- Every room containing a boiler, central heating plant or hot-water supply boiler in Division 1 Occupancies shall be separated from the rest of the building by not less than a one-hour fire -resistive occupancy separation. This requirement pertains to both walls and floor/ceilings.) There were some open drain lines that needed to be plugged -off. 9. -- Throughout the apartment complex, some smoke detectors were battery operated and some were hardwired. Section 1210 (a) 3 states that: "In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source." Therefore, all smoke detectors should have been hard -wired into the building wiring system when they were originally installed. Some smoke detectors were not located in accordance with Sec. 1210 (a) 4. ( Also see Fire Marshal's comments) 10. -- See. 1211. -- Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 70 degrees F. at a point 3 feet above the floor in all habitable rooms. The thermometer in one of these dwellings indicated a room temperature of 60 degrees F. In these as in many of the other dwelling units, the stove oven and/ or portable electric heaters were being used to increase the temperature in the apartments. This review did not determine if the thermostats were not working properly or if the heating system was not capable of providing the required heat; whatever the reason, the heating facilities need to be repaired or upgraded so they meet the code requirements. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE. 11. -- SEC. 1202 (b) -- "Walls and floors separating dwelling units in the same building shall be of not less than one-hour fire -resistive construction." One-hour fire -resistive construction usually consists of one layer of 5/8 inch, Type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing and 1 layer of 5/8 inch, Type X gypsum wallboard on the bottom of the floor/ceiling assembly. The walls and ceilings throughout the building appear to be of 1/2 inch gypsum wallboard; therefore additional layers of gypsum wallboard are required over the existing "walls and floors separating dwelling units " or "walls and floors separating dwelling units from other uses." (such as furnace rooms or storage rooms as was required in the 1985 UBC.) THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 12. -- Smoke Detectors. Sec. 1210 (a) 4 (or Sec. 310.9.1.4 in 94 UBC) now states that: " In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area." 13. -- Guardrail opening dimensions. Sec. 1712 (a) (or Sec. 509.3 in 94 UBC) now states that: " Open guardrails shall have intermediate rails or an ornamental pattern such that a sphere 4 inches in diameter cannot pass through." GENERAL SAFETY ITEMS: 14. -- The steeply sloped concrete area immediately north of the sidewalk near the stair landing is very steep and poses a dangerous slipping problem during icy weather. NOTE: THIS INSPECTION WAS GENERALLY LIMITED TO ITEMS IN PLAIN AND FULL VIEW OF THE INSPECTOR. ATTICS WERE INSPECTED FROM THE ATTIC ACCESS OPENING. GYPSUM WALLBOAD THICKNESSES WERE MEASURED AT ELECTRICAL OUTLET FIXTURES AND LIGHT FIXTURES OR WHERE OPENINGS IN THE EXTERIOR SIDING MADE THE GYPSUM WALLBOAD VISIBLE AND MEASUREABLE. NO ATTEMPT WAS MADE TO ASCERTAIN THE STRUCTURAL SOUNDNESS OF THE BUILDINGS OR RELATED FACILITIES. THIS INSPECTION AND REPORT DO NOT PROFESS TO HAVE COVERED ALL OF THE ITEMS INCLUDED IN THE UNIFORM BUILDING CODE. Date: 2-9-96 Joseph A. Laird, P.E. CITY ENGINEER & BUILDING OFFICIAL Pe, 4. Bldg. 3 STEVE CLARK APARTMENTS IS 1 SO. I ST. EAST ST. BLDG. NO.4 -- APTS. NUMBERS 115, 116, 214, & 215. AT THE JOINT REQUEST OF STEVE CLARK, RICKS COLLEGE AND THE CITY OF REXBURG, THE SUBJECT BUILDING AND APARTMENTS WERE INSPECTED FOR ANY SAFETY VIOLATIONS OF THE UNIFORM BUILDING CODE. THIS INSPECTION WAS CONDUCTED ON FEBRUARY 2, 1996. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1985, 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 1. -- Stairways to laundry room and lounge/TV room do not meet code requirements. Headroom is as low as 5'4". Stair tread rise of 9". Stair tread run too narrow. Sec. 3304 (h) required that: "Regardless of occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall not be more than I inch lower than the threshold of the doorway." Therefore the doorway/stair arrangement will need to be greatly revised to meet the requirements for a landing on both sides of the doorway, for stairway width, stairway headroom and stairway tread rise and nm. Sec. 3306 (b) requires a stairway width of not less than 36 inches. See Sec. 3306 (c) for stairway tread rise and run dimensions. See Sec. 3306 (o) for stairway headroom. See Sec. 3304 (i) for floor level at doors. See Sec. 3304 0) for required landing width and length. Landing length measured in the direction of travel shall not be less than 44 inches. 2. -- The laundry room and the lounge/TV room are both Group B, Division 2 type occupancies. With a 9 ft. distance to property line on the south and a 10 ft. distance to the existing building on the east, both the south and east exterior walls of these rooms have to have a 1 hr. fire -resistive rating. The lounge/TV room had 5/8 " gypsum wallboard on the walls and 1/2" gypsum wallboard on the ceiling. 5/8" gypsum wallboard will have to be installed on the dwelling unit side of the wall to give this wall the required Ihr. fire -resistive rating. Where the existing 1/2" gypsum wallboard is still useable, it can be covered by a second layer of 1/2" gypsum wallboard, type X, to provide the equvalent 5/8" thickness necessary for the required I hr. fire rating. The laundry room had 5/8" gypsum wallboad on the south, west and north walls and the ceiling. Gypsum wallboard thickness was not measured on the east side. The exterior side of the south wall had 5/8" gypsum wallboard covered with 1/2" wood siding. The dwelling unit side of the common wall will also have to be covered with 5/8" gypsum wallboard, type X, to provide the required Ihr. fire rating. There was no indication on the existing doors and windows that they were fire -rated facilities. Any openings within the south and east walls have to have a three-fourths hour fire -protection rating. Therefore the doors on the east side (referenced above in No. 1) will have to have a 3/4 hr. fire protection rating. The windows on the south will also have to have a 3/4 hr. fire - protection rating. (See Table 5A of UBC for wall and window protection requirements). See Sec. 4304 (e) "Penetrations" for pipes penetrating the exterior wall and the firestopping required around such pipe penetrations. 3. -- This building was damaged so extensively by the fire that it will need to be reconstructed so it meets the 94 UBC requirements. Plans will need to be submitted showing how this work will be accomplished. The following referenced items identify some of the corrections that will need to be addressed. 4. -- The attic area does not have draft stops " in line with the walls separating tenant spaces from each other and from other uses "(i.e. draft stops required above the common wall ling between the lounge/TV room and the adjacent dwelling unit). See Sec. 2516 (1) 4 B (ii), pg. 204 of 1985 UBC and Sec. 708.3.1.2.1 of the 1994 UBC. Attic access openings will need to be added above the apartments and lounge/TV room after the attic draft stops are installed. Minimum opening size is 22inches by 30 inches.(See Sec. 1505.1 of 1994 UBC) Additional roof vents may be needed after the attic area is compartmentalized by the required draft stops. 5. -- The 2nd story (Apartments 214 & 215) has an occupant load of 12. Sec. 3303 (a), Exception 2 states that: "Two or more dwelling units on the second story may have access to only one common exit when the total occupant load does not exceed 10." The occupant load of 12 for this story is larger than the allowed occupant load of 10. Therefore a second stairway is required from the 2nd story exterior exit balcony. (See Sec. 1003.1, Exception 2 , pg 174 in 1994 UBC) 6. -- Main stairway to 2nd story apartments. Speaking generally regarding all the main stairway units, the tread rise was usually around 7 1/2 inches with the top rise usually being 9 to 10 inches in height. The tread run was found to be usually around 10 to 10 1/2 inches; however some tread runs were as small as 8 3/4 inches. These measured rise and run values do not meet the requirements of Sec. 3306 (c) which states that: A. - The rise of every step in a stairway shall be not less than 4 inches nor greater than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. B. - The run shall be not less than 11 inches. The largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. The interior edge of the stairway runner is approximately 2 inches from the side of the building Pe.. 2 _Bldg # 4. This is probably not a large enough opening to require a guardrail, but it should be covered or closed up in some manner so it is not a hazard of any sort. The wire mesh stairway treads seem to be breaking loose from the perimeter bracing and need to be rewelded, replaced or repaired in some other manner so that they are safe and capable of carrying the required load set forth in Table 16A of the UBC , namely that: "Individual stair treads shall be designed to support a 300 pound concentrated load placed in a position which would cause maximim stress." Maintenance needs to be accomplished as is required in Sec. 104 (d). 7. -- That portion of the exterior building wall adjacent to the 2nd floor exterior exit balcony and that portion of the roof above the exterior exit balcony were not, but should have been, constructed to one-hour fire -resistive standards. See Sec. 3305 (g) which states that: " Walls of corridors and exterior exit balconies serving a Group It, Division 1 Occupancy having an occupant load of 10 or more --- shall be of not less than one-hour fire -resistive construction and the ceilings shall be not less than that required for a one-hour fire -resistive floor or roof system." (See Sec. 1005.7 - "Construction" in the 1994 UBC) 8. -- Sec. 1202(b) -- Storage and laundry rooms--- shall be separated from the rest of the building by not less than one-hour fire -resistive occupancy separations. This requirement pertains to both walls and floor/ceilings. (See Sec. 310.2.2 in 1994 UBC) 9. -- Sec. 1213 -- Every room containing a boiler, central heating plant or hot-water supply boiler in Division 1 Occupancies shall be separated from the rest of the building by not less than a one- hour fire -resistive occupancy separation. This requirement pertains to both walls and floor/ceilings. (See Sec. 302.5 in 1994 UBC) 10. -- Throughout the apartment complex, some smoke detectors were battery operated and some were hardwired. Section 1210 (a) 3 states that: "In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source." Therefore, all smoke detectors should have been hard -wired into the building wiring system when they were originally installed. Some smoke detectors were not located in accordance with Sec. 1210 (a) 4. ( Also see Fire Marshal's comments) 11. -- Sec. 1211. -- Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 70 degrees F. at a point 3 feet above the floor in all habitable rooms. (See Sec. 310.11 - "Heating" in the 1994 UBC) In many of the other dwelling units, the stove oven and/ or portable electric heaters were being used to increase the temperature in the apartments. This review did not determine if the thermostats were not working properly or if the heating system was not capable of providing the required heat; whatever the reason, the heating facilities need to be repaired or upgraded so they meet the code requirements. 12. -- The ground area between the south side of the building and the adjacent property to the south is being eroded away by storm drainage runoff. This erosion is undermining the building footing and needs to be corrected. Storm drainage cannot go onto the neighbor's property without his consent. THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1988, 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE. 13. -- SEC. 1202 (b) -- "Walls and floors separating dwelling units in the same building shall be of not less than one-hour fire -resistive construction." (See Sec. 310.2.2 in the 1994 UBC) One-hour fire -resistive construction usually consists of one layer of 5/8 inch, Type X, gypsum wallboard on each side of the 2 x 4 or 2 x 6 wall framing and 1 layer of 5/8 inch, Type X gypsum wallboard on the bottom of the floor/ceiling assembly. The walls and ceilings throughout the building appear to be of 1/2 inch gypsum wallboard; therefore additional layers of gypsum wallboard are required over the existing "walls and floors separating dwelling units " or "walls and floors separating dwelling units from other uses." (such as furnace rooms or storage rooms as was required in the 1985 UBC.) THE FOLLOWING LISTED ITEMS WERE FOUND TO BE NOT IN COMPLIANCE WITH THE 1991 & 1994 EDITIONS OF THE UNIFORM BUILDING CODE: 14. -- Smoke Detectors. Sec. 1210 (a) 4 (or Sec. 310.9.1.4 in 94 UBC) now states that: " In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area." 15. -- Guardrail opening dimensions. Sec. 1712 (a) (or Sec. 509.3 in 94 UBC) now states that: ' Open guardrails shall have intermediate rails or an ornamental pattern such that a sphere 4 inches in diameter cannot pass through." NOTE: THIS INSPECTION WAS GENERALLY LIMITED TO ITEMS IN PLAIN AND FULL VIEW OF THE INSPECTOR. ATTICS WERE INSPECTED FROM THE ATTIC ACCESS OPENING. GYPSUM WALLBOAD THICKNESSES WERE MEASURED AT ELECTRICAL OUTLET FIXTURES AND LIGHT FIXTURES OR WHERE OPENINGS IN THE EXTERIOR SIDING MADE THE GYPSUM WALLBOAD VISIBLE AND MEASUREABLE. NO ATTEMPT WAS MADE TO ASCERTAIN THE STRUCTURAL SOUNDNESS OF THE BUILDINGS OR RELATED FACILITIES. THIS INSPECTION AND REPORT DO NOT PROFESS TO HAVE COVERED ALL OF THE ITEMS INCLUDED IN THE UNIFORM BUILDING CODE. Joseph A. Laird, P. E. CITY ENGINEER & BUILDING OFFICIAL pg.4, Bldg.4 2-9-96 Date U 23-A UNIFORM BUILDING CODE TABLE NO.23-A—UNIFORM AND CONCENTRATFn i nanc USEOROCCUPANCY CATEGORY DESCRIPTION UNIFORM LOAM CONCEN- MATED LOAD I. Access fluor systems Office use 50 20002 Computer use 100 20002 2. Annorics 150 0 3. Assembly areas5 mrd auditoriums and balcuuics therewith Fixed seating areas 50 0 Movable scaling and other areas too 0 Stage areas and enclosed platforms 125 0 4. Cornices, marquees and residential balconies 60 0 5. Exit facilities' too 05 6. Garages - General storage and/or repair 100 6 Private or pleasure -type motor vehicle storage 50 6 7. Hospitals Wards and rooms 40 10002 8. Libraries Reading rooms 60 10002 Stack rooms 125 15002 9. Manufacturing Light 75 20002 Heavy _ 125 30002 10. Offices 50 20002 11, Printing plants Press rooms 150 25002 Composing and lino) pe rooms 100 20002 12. RcsidenliaF 40 05 13. Rest moms" 14. Reviewing stands, grandstands and bleachers 100 0 15. Roof deck Same as area served or for the type of occupancy accommodated 16. Schools Classrooms 40 10002 17. Sidewalks and driveways _ Public access 250 6 18. Storage Light 125 Heavy 250 19. Stores — Retail 75 20002 Wholesale 100 30002 1985 EDITION 23-A ISee Section 2306 for live load reductions. 2See Section 2304 (c), first paragraph, for area of load application. aAssembly areas include such occupancies as dance halls, drill rooms, gymnasiums, playgrounds, plazas, terraces and similar occupancies which are generally accessible to the public. 4Exit facilities shall include such uses as corridors serving an occupant load of 10 or more persons, exterior exit balconies, stairways, fire escapes and similar uses. slndividual stair treads shall be designed to support a 300 -pound concentrated load placed in a position which would cause maximum stress. Stair stringers may be designed for the uniform load set forth in the table. 6See Section 2304(c), second paragraph, for concentrated loads. 211esidential occupancies include private dwellings, apartments and hotel guest rooms. 6Rest room loads shall be not less than the load for the occupancy with which they are associated, but need not exceed 50 pounds per square foot. 104 UNIFORM BUILDING CODE structure to become structurally unsafe or overloaded; will not provide adequate egress in compliance with the provisions of this code or will obstruct existing exits; will create a fire hazard; will reduce required fire resistance or will other- wise create conditions dangerous to human life. Any building so altered, which involves a change in use or occupancy, shall not exceed the height, number of stories and area permitted for new buildings. Any building plus new additions shall not exceed the height, number of stories and area specified for new build- ings. Additions or alterations shall not be made to an existing building or structure when such existing building or structure is not in full compliance with the provisions of this code except when such addition or alteration will result in the existing building or structure being no more hazardous based on life safety, fire safety and sanitation, than before such additions or alterations are undertaken. [See also Section 911 (c) for Group H, Division 6 Occupancies. ] Alterations or repairs to an existing building or structure which are nonstruc- tural and do not adversely affect any structural member or any part of the building or structure having required fire resistance may be made with the same materials of which the building or structure is constructed. The installation or replacement of glass shall be as required for new installations. (c) Existing Installations. Buildings in existence at the time of the adoption of this code may have their existing use or occupancy continued, if such use or occupancy was legal at the time of the adoption of this code, provided such continued use is not dangerous to life. Any change in the use or occupancy of any existing building or structure shall comply with the provisions of Sections 307 and 502 of this code. For existing buildings, see Appendix Chapter 1. (d) Maintenance. All buildings and structures, both existing and new, and all parts thereof, shall be maintained in a safe and sanitary condition. All devices or safeguards which are required by this code shall be maintained in conformance with the code edition under which installed. The owner or his designated agent shall be responsible for the maintenance of buildings and structures. To determine compliance with this subsection, the building official may cause any structure to be reinspected. (e) Moved Buildings and Temporary Buildings. Buildings or structures moved into or within the jurisdiction shall comply with the provisions of this code for new buildings or structures. Temporary structures such as reviewing stands and other miscellaneous struc- tures, sheds, canopies or fences used for the protection of the public around and in conjunction with construction work may be erected by special permit from the building official for a limited period of time. Such buildings or structures need not comply with the type of construction or fire -resistive time periods required by this code. Temporary buildings or structures shall be completely removed upon the expiration of the time limit stated in the permit. (f) Historic Buildings. Repairs, alterations and additions necessary for the preservation, restoration, rehabilitation or continued use of a building or structure may be made without conformance to all the requirements of this code when authorized by the building official, provided: 302.4-303.1.1 1994 UNIFORM BUILDING CODE may be further reduced to one hour where the area of such Group S, Division 3 Occupancy does not exceed 3,000 square feet (279 m'-). 3. 1n the one-hour occupancy separation between Group R, Division 3 and Group U Occupancies, the sepa- ration may be limited to the installation of materials approved for one-hour fire -resistive construction on the garage side and a self-closing, tight -fitting solid -wood door 13/8 inches (35 man in thickness, or a self-closing, tight -fitting door having a fire -protection rating of not less than 20 minutes when tested in accordance with Part 11 of U.B.C. Standard 7-2, which is a part of this code, is permitted in lieu of a one-hour fire assembly. Fire dampers need not be installed in air ducts passing through the wall, Floor or ceiling separating a Group R, Division 3 Occupancy from a Group U Occupancy, provided such ducts within the Group U Occupancy are constructed of steel having a thickness not less than 0.019 inch (0.48 mm) (No. 26 galvanized sheet gage) and have no openings into the Group U Occupancy. - 4. Group H, Division 2 and Group H, Division 3 Occupancies need not be separated from Group 11, Divi- sion 7 Occupancies when such occupancies also comply with the requirements for a Group H, Division 7 Oc- cupancy. 302.5 Heating Equipment Room Occupancy Separation. In Groups A; B; E; F; I; M; R, Divi- sion l; and S Occupancies, rooms containing a boiler, central heating plant or hot-water supply boil- i er shall be separated from the rest of the building by not less than a one-hour occupancy separation. EXCEPTIONS: 1. In Groups A, B, E, F, 1, M and S Occupancies, boilers, central heating plants or hot- water supply boilers where the largest piece of fuel equipment does not exceed 400,000 Btu per hour (117.2 kW) input 2. In Group R, Division I Occupancies, a separation need not be provided for such rooms with equipment serving only one dwelling unit. In Group E Occupancies, when the opening for a heater or equipment room is protected by a pair of fire doors, the inactive leaf shall be normally secured in the closed position and shall be openable only by the use of a tool. An astragal shall be provided and the active leaf shall be self-closing. In Group H Occupancies, rooms containing a boiler, central heating plant or hot-water supply boiler shall be separated from the rest of the building by not less than a two-hour occupancy separa- tion. In Divisions l and 2, there shall be no openings in such occupancy separation except for neces- sary ducts and piping. For opening in exterior walls of equipment rooms in Groups A, E or I Occupancies, see Section 303.8. 302.6 Water Closet Room Separation. A room in which a water closet is located shall be sepa- rated from food preparation or storage rooms by a tight -fitting door. SECTION 303 — REQUIREMENTS FOR GROUP A OCCUPANCIES 303.1 General. 303.1.1 Group A Occupancies defined. Group A Occupancies include the use of a building or structure, or a portion thereof, for the gathering together of 50 or more persons for purposes such as – civic, social or religious functions, recreation, education or instruction, food or drink consumption, or awaiting transportation. A room or space used for assembly purposes by less than 50 persons and — accessory to another occupancy shall be included as a part of that major occupancy. Assembly occu- pancies shall include the following: Division 1. A building or portion of a building having an assembly room with an occupant load of 1,000 or more and a legitimate stage. Division 2. A building or portion of a building having an assembly room with an occupant load of less than 1,000 and a legitimate stage. Division 2.1. A building or portion of a building having an assembly room with an occupant load of 300 or more without a legitimate stage, including such buildings used for educational purposes and not classed as Group B or E Occupancies. Division 3. A building orportion of a building having an assembly room with an occupant load of less than 300 without a legitimate stage, including such buildings used foreducational purposes and not classed as Group B or E Occupancies. 1-26 310-310.4 1994 UNIFORM BUILDING CODE SECTION 310 — REQUIREMENTS FOR GROUP R OCCUPANCIES 310.1 Group R Occupancies Defined. Group R Occupancies shall be: Division 1. 1lotels and apartment houses. Congregate residences (each accommodating more than 10 persons). Division 2. Not used. Division 3. Dwellings and lodging houses. Congregate residences (each accommodating 10 persons or less). For occupancy separations, see Table 3-13. A complete code for construction of detached one- and two-family dwellings is in Appendix Chapter 3, Division 111, of this code. When adopted, as set forth in Section 101.3, it will take prece- dence over the other requirements set forth in Chapter 35 of this code. 310.2 Construction, Height and Allowable Area. 310.2.1 General. Buildings or parts of buildings classed it) Group R because Of the use orcharac- ter of the occupancy shall be limited to the types of construction set forth in Table 5-B and shall not exceed, in area or height, the limits specified in Sections 504, 505 and 506. 310.2.2 Special provisions. Walls and floors separating dwelling units in the same building, or guest rooms in Group R, Division l hotel occupancies, shall not be of less than one-hour fire-resis- live construction. Group R, Division I Occupancies more than two stories in height or having more than 3,000 square feet (279 m2) of floor area above the first story shall not be of less than one-hour fire -resistive construction throughout except as provided in Section 601.5.2.2. Storage or laundry rooms that are within Group R, Division I Occupancies that are used in com- mon by tenants shall be separated from the rest of the building by not less than one-hour fire-resis- live occupancy separation. For Group R, Division I Occupancies with a Group S, Division 3 parking garage in the basement or first story, see Section 311.2.2. For attic space partitions and craft stops, see Section 708. 310.3 Location on Property. For fire -resistive protection of exterior walls and openings, as de- termined by location on property, see Section 503 mut Chapter 6. 310.4 Access and Exit Facilities and Emergency Escapes. Exits shall be provided as specified in Chapter 10. (See also Section 1013 for exit markings.) Access to, and egress from, buildings required to be accessible shall be provided as specified in Chapter 11. Basements in dwelling units and every sleeping room below the fourth story shall have at least one operable window or door approved for emergency escape or rescue which shall open directly into a public street, public alley, yard or exit court. The emergency dooror window shall be operable from the inside to provide it full, clear opening without the use of separate tools. EXCEPTION: The window or door may open into an atrium complying with Section 402 provided the window or door opens onto an exit balcony and the dwelling unit or guest room has an exit which does not Opel] into the atrium. Escape or rescue windows shall have a minimum net clear openable area of 5.7 square feel (0.53 1112). The minimum net clear openable height dimension shall be 24 inches (6 10 nun). The mini - muni netclearopenublewidth dimension shall be20inches (508nun). When windows are provided i as a means of escape or rescue, they shall have a finished sill height not more than 44 inches (1118 nun) above the floor. 1-48 310.7-310.9.2 1994 UNIFORM BUILDING CODE 4. The unit shall be provided wish a separate bathroom containing a water closet, lavatory and bathtub or shower. 310.8 Shaft and Exit Enclosures. Exits shall be enclosed as specified in Chapter 10. Elevator shafts, vent shafts, dumbwaiter shafts, clothes chutes and other vertical openings shall be enclosed and the enclosure shall be as specified in Section 711. In nonsprinklered Group R, Division 1 Occupancies, corridors serving an occupant load of 10 or more shall be separated from corridors and other areas on adjacent floors by not less than approved fixed wired glass set in steel frames or by 20 -minute smoke- and draft -control assemblies which are automatic closing by smoke detection. 310.9 Smoke Detectors and Sprinkler Systems. 310.9.1 Smoke detectors. 310.9.1.1 General. Dwelling units, congregate residences and hotel or lodging house guest rooms that are used for sleeping put -poses shall be provided with smoke detectors. Detectors shall be installed in accordance with the approved manufacturer's instructions. 310.9.1.2 Additions, alterations or repairs to Group R Occupancies. When the valuation of an addition, alteration or repair to a Group R Occupancy exceeds $1,000 and a permit is required, or when one or more sleeping rooms are added or created in existing Group R Occupancies, smoke detectors shall be installed in accordance with Sections 310.9.1.3, 310.9.1.4 and 310.9.1.5 of this section, EXCEPTION: Repairs to the exterior surfaces of a Group R Occupancy are exempt from the require- ments of this section. 310.9.1.3 Power source. In new construction, required smoke detectors shall receive their pri- mary power from the building wiring when such wiring is served from a commercial source and shall be equipped with a battery backup. The detector shall emit a signal when the batteries are low. _ Wiring shall be permanent and without it disconnecting switch other than those required for over - current protection. Smoke detectors may be solely battery operated when installed in existing buildings; or in buildings without commercial power; or in buildings which undergo alterations, repairs or additions regulated by Section 310.9.1.2. 310.9.1.4 Location within dwelling units. In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area. When the dwelling unit has more than one story and in dwellings with basements, a detector shall be installed on each story and in the basement. In dwelling units where a story or base- ment is split into two or more levels, the smoke detector shall be installed on the upper level, except that when the lower level contains a sleeping area, a detector shall be installed on each level. When sleeping rooms are on an upper level, the detector shall be placed at the ceiling of the upper level in close proximity to the stairway. In dwelling units where the ceiling height of a room open to the hallway serving the bedrooms exceeds that of the hallway by 24 inches (6 10 mm) or more, smoke detectors shall be installed in the hallway and in the adjacent room. Detectors shall sound an alarm audible in all sleeping areas of the dwelling unit in which they are located. 310.9.1.5 Location in efficiency dwelling units, congregate residences and hotels. In efficien- cy dwelling units, hotel suites and in hotel and congregate residence sleeping rooms, detectors shall be located on the ceiling or wall of the main room or each sleeping room. When sleeping rooms within an efficiency dwelling unit or hotel suite are on an upper level, the detector shall be placed at the ceiling of the upper level in close proximity to the stairway. When actuated, the detector shall sound all alarm audible within the sleeping area of the dwelling unit or congregate residence, hotel suite, or sleeping room in which it is located. 310.9.2 Sprinkler and standpipe systems. When required by Section 904.2.1 or other provi- sions of this code, automatic sprinkler systems and standpipes shall be designed and installed as — specified in Chapter 9. 1-50 1994 UNIFORM BUILDING CODE 310.10-311.1 310.10 Fire Alarm Systems. Group R, Division I Occupancies shall be provided with an ap- proved manual and automatic fire alarm system in apartment houses three or more stories in height or containing 16 or more dwelling units, in hotels three or more stories in height or containing 20 or more guest rooms and in congregate residences three or more stories in height or having an occu- pant load of 20 or more. A fire alarm and connnunication system shall be provided in Group R, Division t Occupancies located in a high-rise building. EXCEPTIONS: I. A manual fire alarm system need not be provided in buildings not over two stories in height when all individual dwelling units and contiguous attic and crawl spaces are separated from each other and public or common areas by at least one-hour fire -resistive occupancy separations and each individual dwelling unit or guest room has an exit directly to a public way, exit court or yard. 2. A separate fire alarm system need not be provided in buildings which are protected throughout by an approved supervised fire sprinkler system having a local alarm to notify all occupants. The local alarm shall provide ,in alarm signal with a sound pressure level of 15 dBA above the F F average ambient sound level in every occupied space within the building. The minimum sound F pressure level shall be 70 dBA. The maximum sound pressure level for audible alarm -indicating F appliances shall not exceed 110 dBA at the minimum hearing distance from the audible appliance. I F For the purposes of this section, area separation walls shall not define separate buildings. F 310.11 heating. Dwelling units, guest rooms and congregate residences shall be provided with heating facilities capable of maintaining a room temperature of 70°F. (21'C.) at a point 3 feet (914 nun) above the floor in all habitable rooms. 310.12 Special Hazards. Chimneys and heating apparatus shall conform to the requirements of Chapter 31 and the Mechanical Code. The storage, use and handling of flammable and combustible liquids in Division I Occupancies shall be in accordance with the Fire Code. In Division I Occupancies, doors leading into rooms in which Class I flammable liquids are stored or used shall be protected by a fire assembly having a one-hour fire -protection rating. Such fire assembly shall be self-closing and shall be posted with a sign on each side of the door in 1 -inch (25.4 nun) block letters stating: FIRE DOOR—KEEP CLOSED. SECTION 311 — REQUIREMENTS FOR GROUP S OCCUPANCIES 311.1 Group S Occupancies Defined. Group S Occupancies shall include the use of a building or structure, or a portion thereof, for storage not classified as a hazardous occupancy. Storage occu- pancies shall include the following: Division 1. Moderate hazard storage occupancies shall include buildings or portions of buildings used for storage of combustible materials that are not classified as a Group S, Division 2 or as a Group H Occupancy. Division 2. Low -hazard storage occupancies shall include buildings, structures, or portions thereof, used for storage of noncombustible materials, such as products on wood pallets or in paper cartons with or without single -thickness divisions, or in paper wrappings and shall include ice plants, power plants and pumping plants. Such products may have a negligible amount of plastic trim such as knobs, handles or film wrapping. Low -hazard storage occupancies shall include, but are not limited to, storage of the following items: 1. Beer or wine (in metal, glass or ceramic containers). 2. Cement in bags. 3. Cold storage and creameries. 4. Dairy products in nonwax-coated paper containers. 5. Dry -cell batteries. 1-51 407-408 UNIFORM BUILDING CODE j ' I FAMILY is an individual or two or more persons related by blood or marriage or a group of not more than five persons (excluding servants) who need not be related by blood or marriage living together in a dwelling unit. FIRE ASSEMBLY. See Section 4306 (b). FIRE CODE is the Uniform Fire Code promulgated jointly by the Western Fire Chiefs Association and the International Conference of Building Officials, as adopted by this jurisdiction. FIRE RESISTANCE or FIRE -RESISTIVE CONSTRUCTION is con- struction to resist the spread of fire, details of which are specified in this code. FIRE -RETARDANT TREATED WOOD is lumber or plywood impregnated with chemicals and which, when tested in accordance with U.B.C. Standard No. 42-1 for a period of 30 minutes, shall have a flame spread of not over 25 and show no evidence of progressive combustion. Materials which may be exposed to the weather shall maintain this fire -retardant classification when tested in accordance with the rain and weathering tests of U.B.C. Standard No. 32-7. All materials shall bear identification showing the fire performance rating thereof and, if intended for exterior use, shall be further identified to indicate suitability for exposure to the weather. Such identifications shall be issued by an approved agency having a service for inspection of materials at the factory. FLAMMABLE LIQUID. See Fire Code. FLOOR AREA is the area included within the surrounding exterior walls of a building or portion thereof, exclusive of vent shafts and courts. The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall be _ the usable area under the horizontal projection of the roof or floor above. FOOTING is that portion of the foundation of a structure which spreads and transmits loads directly to the soil or the piles. FRONT OF LOT is the front boundary line of a lot bordering on the street and, in the case of a corner lot, may be either frontage. G See. 408. GARAGE is a building or portion thereof in which a motor vehicle containing flammable or combustible liquids or gas in its tank is stored, repaired or kept. GARAGE, PRIVATE, is a building or a portion of a building, not more than 1000 square feet in area, in which only motor vehicles used by the tenants of the building or buildings on the premises are stored or kept. (See Section 1101.) GARAGE, PUBLIC, is any garage other than a private garage. GRADE (Adjacent Ground Elevation) is the lowest point of elevation of the finished surface of the ground, paving or sidewalk within the area between the building and the property line or, when the property line is more than 5 feet from the building, between the building and a line 5 feet from the building. GRADE (Lumber) is the classification of lumber in regard to strength and utility. 20 417-420 UNIFORM BUILDING CODE greater than 75 when tested in the thickness intended for use by U. B.C. Standard No. 52-2. Approved plastics shall be classified as either CCI or CC2, in accord- ance with U.B.C. Standard No. 52-4. PLATFORM. See Chapter 39. PLUMBING CODE is the Uniform Plumbing Code promulgated by the International Association of Plumbing and Mechanical Officials as adopted by this jurisdiction. PUBLIC WAY. See Section 3301 (b). Q See. 418. No definitions. R Sec. 419. REPAIR is the reconstruction or renewal of any part of an existing building for the purpose of its maintenance. S € Sec. 420. SERVICE CORRIDOR is a fully enclosed passage used for trans- porting HPM and for purposes other than required exiting. SHAFT is a vertical opening through a building for elevators, dumbwaiters, mechanical equipment or similar purposes. SHALL, as used in this code, is mandatory. SMOKE DETECTOR is an approved detector which senses visible or invisi- ble particles of combustion. The detector shall bear a label or other identification issued by an approved testing agency having a service for inspection of materials and workmanship at the factory during fabrication and assembly. _> STAGE See Chapter 39. STORY is that portion of a building included between the upper surface of any floor and the upper surface of the floor next above, except that the topmost story _ shall be that portion of a building included between the tipper surface of the topmost floor and the ceiling or roof above. If the finished floor level directly above a usable or unused under -floor space is more than 6 feet above grade as defined herein for more than 50 percent of the total perimeter or is more than 12 feet above grade as defined herein at any point, such usable or unused under -floor space shall be considered as a story. STORY, FIRST, is the lowest story in a building which qualifies as a story, as defined herein, except that a floor level in a building having only one floor level shall be classified as a first story, provided such floor level is not more than 4 feet below grade, as defined herein, for more than 50 percent of the total perimeter, or not more than 8 feet below grade, as defined herein, at any point. STREET is any thoroughfare or public way not less than 16 feet in width which has been dedicated or deeded to the public for public use. STRUCTURE is that which is built or constructed, an edifice or building of any kind, or any piece of work artificially built up or composed of parts joined together in some definite manner. 24 504-505 UNIFORM BUILDING CODE 2. A point one third the distance from an assumed vertical plane located where fire -resistive protection of openings is first required due to location on property, whichever is the least restrictive. When openings in exterior walls are required to be protected due to distance from property line, the sum of the area of such openings shall not exceed 50 percent of the total area of the wall in each story. (c) Buildings on Same Property and Buildings Containing Courts. For the purposes of determining the required wall and opening protection and roof - covering requirements, buildings on the same property and court walls of build- ings over one story in height shall be assumed to have a property line between them. EXCEPTION: In court walls where opening protection is required such protec- tion may be omitted, provided (1) not more than two levels open into the court, (2) the aggregate areaof the building including the court is within the allowable area and (3) the building is not classified as a Group I Occupancy. When a new building is to be erected on the same property as an existing building, the location of the assumed property line with relation to the existing building shall be such that the exterior wall and opening protection of the existing building meet the criteria as set forth in Table No. 5-A and Part IV. EXCEPTION: Two or more buildings on the same property may be considered as portions of one building if the aggregate area of such buildings is within the limits specified in Section 505 for a single building. When the buildings so considered house different occupancies or are of different types of construction, the area shall be that allowed for the most restricted occupancy or construction. Allowable Floor Areas Sec. 505. (a) One-story Areas. The area of a one-story building shall not exceed the limits set forth in Table No. 5-C except as provided in Section 506. (b) Areas of Buildings Over One Story. The total combined floor area for multistory buildings may be twice that permitted by Table No. 5-C for one-story buildings, and the floor area of any single story shall not exceed that permitted for a one-story building. (c) Mezzanines. Unless considered as a separate story, the floor area of all mezzanines shall be included in calculating the allowable floor arca of the stories in which the mezzanines are located. (d) Basements. A basement need not be included in the total allowable area, provided such basement does not exceed the area permitted for a one-story building. (e) Area Separation Walls. Each portion of a building separated by one or more area separation walls may be considered a separate building, provided the area separation walls meet the following requirements: 1. Area separation walls shall be not less than four-hour fire -resistive construc- tion in Types I, II -FR., III and IV buildings and two-hour fire -resistive construc- tion in Types II One-hour, II -N or V buildings. The total width of all openings in such walls shall not exceed 25 percent of the length of the wall in each story. All 30 1985 EDITION 505 openings shall be protected by afire assembly having a three-hour fire -protection rating in four-hour fire -resistive walls and one and one -half-hour fire -protection rating in two-hour fire -resistive walls. 2. Area separation walls shall extend to the outer edges of horizontal projecting elements such as balconies, roof overhangs, canopies, marquees or architectural projections. EXCEPTION: When horizontal projecting elements do not contain concealed spaces, the area separation wall may terminate at the exterior wall. When the horizontal projecting elements contain concealed spaces, the area separation wall need only extend through the concealed space to the outer edges of the projecting elements. The exterior walls and the projecting elements above shall be of not less than one- hour fire -resistive construction for a distance not less than the depth of the projecting elements on both sides of the area separation wall. Openings within such widths shall be protected by fire assemblies having a fire -protection rating of not less than three- fourths hour. 3. Area separation walls shall extend from the foundation to a point at least 30 inches above the roof. EXCEPTIONS: 1. Area separation walls may terminate at the underside of the roof sheathing, deck or slab, provided the roof -ceiling assembly is of al least two- hour fire -resistive construction. 2. Two-hour area separation walls may terminate at the underside of the roof sheathing, deck or slab, provided: ,. A. Where the roof -ceiling framing elements are parallel to the walls, such training and elements supporting such framing shall be of not less than one -hoar fire - resistive construction for a width of not less than 5 feel on each side of the wall. B. Where roof -ceiling framing elements are perpendicular to the wall, the entire span of such framing and elements supporting such framing shall be of not less than one-hour fire -resistive construction. C. Openings in the roof shall not be located within 5 feet of the area separation wall. D. The entire building shall be provided with a fire -retardant roof covering or special purpose roof complying with Section 3203 (g). 3. Two-hour area separation walls may terminate at roofs of entirely noncombusti- ble construction. 4. Parapets of area separation walls shall have noncombustible faces for the uppermost 18 inches, including counterflashing and coping materials. 5. Where an area separation wall separates portions of a building having different heights, such wall may terminate at a point 30 inches above the lower roof level, provided the exterior wall for a height of 10 feet above the lower roof is of one-hour fire -resistive construction with openings protected by assemblies having a three -fourths -hour fire -protection rating. EXCEPTION: The area separation wall may terminate at the underside of the roof sheathing, deck or slab of the lower roof, provided: A. Where the roof -ceiling framing elements are parallel to the wall, such framing and elements supporting such framing shall be of not less than one-hour fire - resistive construction for a width of 10 feet along the wall at the lower roof. 31 1991 UNIFORM BUILDING CODE 505 than the basic area permitted in the occupancy by Table No. 5-C for such minor uses, for the purpose of determining allowable area, the major use of the building shall determine the occupancy classification, provided the uses are separated as specified in Section 503 (d). (d) Mezzanines. Unless considered as a separate story, the floorarea of all mez- zanines shall be included in calculating the allowable floor area of the stories in which the mezzanines are located. (e) Basements. A basement need not be included in the total allowable area, pro- vided such basement does not exceed the area permitted for a one-story building. (f) Area Separation Walls. 1. General. Each portion of a building separated by one or more area separation walls which comply with the provisions of this subsec- i>s to tion maybe considered a separate building. The extent and location of such area :•`•,` z separation walls shall provided a complete separation. f: �s When an area separation wall also separates occupancies that are required to be separated by an occupancy separation, the most restrictive requirements of each separation shall apply. 2. Fire -resistance. Area separation walls shall not be of less than four-hour fire -resistive construction in Types 1, II-F.R., III and IV buildings and two-hour fire -resistive construction in Type II One-hour, II -N or V buildings. The total width of all openings in such walls shall not exceed 25 percent of the length of the wall in each story. All openings shall be protected by a fire assembly having a three-hour fire -protection rating in four-hour fire -resistive walls and one- and one -half-hour fire -protection rating in two-hour fire -resistive walls. 3. Extensions beyond exterior walls. Area separation walls shall extend to the outer edges of horizontal projecting elements such as balconies, roof overhangs, canopies, marquees or architectural projections. EXCEPTION: When horizontal projecting elements do not contain concealed spaces, the area separation will may terminate at the exterior wall. When the horizontal projecting elements contain concealed spaces, the area sepa- ration wall need only extend through the concealed space to the outer edges of the projecting elements. The exterior walls and the projecting elements above shall not be of less than one-hour fire -resistive construction for a distance not less than the depth of the proj- ecting elements on both sides of the area separation wall. Openings within such widths shall be protected by fire assemblies having a fire -protection rating of not less than three-fourths hour. 4. Terminaling. Area separation walls shall extend from the foundation to a point at least 30 inches above the roof. EXCEPTIONS: I. Area separation walls may terminate at the underside of the roof sheathing, deck or slab, provided the roof -ceiling assembly is of at least two- .-. hour fire -resistive construction. 2. Two-hour area separation walls may terminate at the underside of the roof sheathing, deck or slab, provided: A. Where the roof -ceiling framing elements are parallel to the walls, such fram- ing and elements supporting such framing shall not be of less than one-hour �R7 505.506 1991 UNIFORM BUILDING CODE fire -resistive construction for a width of not less than 5 feet on each side of the wall. B. Where roof -ceiling training elements are perpendicular to the wall, the entire span of such framing and elements supporting such framing shall not be of 1. less than one-hour fire -resistive construction. % C. Openings in the roof shall not be located within 5 feet of the area separation wall. ` D. The entire building shall be provided with not less than a Class B roofing. Y. 3. Two-hour area separation walls may terminate at the underside of noncombus- tible roof sheathing, deck or slab of roofs of noncombustible construcfion provided: 3 A. Openings in the roof are not located within 5 feet of the area separation wall. si B. The entire building is provided with not less than a Class B roofing. 5. Parapet faces. Parapets of area separation walls shall have noncombustible faces for the uppermost 18 inches, including counterflashing and coping materials. 6. Buildings of different heights. Where an area separation wall separates por- tions of a building having different heights, such wall may terminate at a point 30 inches above the lower roof level, provided the exterior wall for a height of 10 feet above the lower roof is of one-hour fire -resistive construction with openings pro- tected by assemblies having a three -fourths -hour fire -protection rating. EXCEPTION: The area separation wall may tenninale at the underside of the roof sheathing, deck or slab of the lower roof, provided: A. Where the roof -ceiling framing elements are parallel to the wall, such framing and elements supporting such framing shall not be of less than one-hour fire -resistive construction for a width of 10 feet along the wall at the lower roof. —' B. Where the lower roof -ceiling framing elements are perpendicular to the wall, the entire span of such framing and elements supporting such framing shall not be of less than one-hour fire -resistive construction. C. Openings in the lower roof shall not be located within 10 feet of the area sepa- ration wall. See Chapters 6 through 12 for special occupancy provisions. Allowable Area Increases Sec. 506. (a) General. The floorareas specified in Section 505 may be increased by one of the following: 1. Separation on two sides. Where public ways or yards more than 20 feet in width extend along and adjoin two sides of the building, floor areas may be in- creased at a rate of 0/4 percent for each foot by which the minimum width exceeds 20 feet, but the increase shall not exceed 50 percent. 2. Separation on three sides. Where public ways or yards more than 20 feet in width extend along and adjoin three sides of the building, floor areas may be in- creased at a rate of 21/2 percent for each foot by which the minimum width exceeds 20 feet, but the increase shall not exceed 100 percent. 3. Separation on all sides. Where public ways or yards more than 20 feet in width extend on all sides of a building and adjoin the entire perimeter, floor areas may be increased at a rate of 5 percent for each foot by which the minimum ex - 40 1991 UNIFORM BUILDING CODE 505 I than the basic area permitted in the occupancy by Table No. 5-C for such minor uses, for the purpose of determining allowable area, the major use of the building shall determine the occupancy classification, provided the uses are separated as #s specified in Section 503 (d). € (d) Mezzanines. Unless considered as a separate story, the floor area of all mez- zanines shall be included in calculating the allowable floor area of the stories in which the mezzanines are located. (e) Basements. A basement need notbe included in the total allowablearea, pro- vided such basement does not exceed the area permitted for a one-story building. (f) Area Separation Walls. 1.General. Each portion of a building separated by one or more area separation walls which comply with the provisions of this subsec- tion may be considered a separate building. The extent and location of such area separation walls shall provided a complete separation. When an area separation wall also separates occupancies that are required to be separated by an occupancy separation, the most restrictive requirements of each separation shall apply. 2. Fire -resistance. Area separation walls shall not be of less than four -hoar fire -resistive construction in Types 1, II-F.R., III and IV buildings and two-hour fire -resistive construction in Type 11 One-hour, 11-N or V buildings. The total width of all openings in such walls shall not exceed 25 percent of the length of the wall in each story. All openings shall be protected by a fire assembly having a three-hour fire -protection rating in four-hour fire -resistive walls and one- and one -half-hour fire -protection rating in two-hour fire -resistive walls. 3. Extensions beyond exterior walls. Area separation walls shall extend to the outer edges of horizontal projecting elements such as balconies, roof overhangs, canopies, marquees or architectural projections. EXCEPTION: When horizontal projecting elements do not contain concealed - spaces, the area separation wall may terminate at the exterior wall When the horizontal projecting elements contain concealed spaces, the area sepa- ration wall need only extend through the concealed space to the outer edges of the projecting elements. The exterior walls and the projecting elements above shall not be of less than one-hour fire -resistive construction for a distance not less than the depth of the proj- ecting elements on both sides of the area separation wall. Openings within such widths shall be protected by fire assemblies having a lire -protection rating of not less than three-fourths hour. 4. Terminating. Area separation walls shall extend from the foundation to a point at least 30 inches above the roof. EXCEPTIONS: 1. Area separation walls may terminate at the underside of the roof sheathing, deck or slab, provided the roof -ceiling assembly is of at least two- hour fire -resistive construction. 2. Two-hour area separation walls may terminate at the underside of the roof sheathing, deck or slab, provided: A. Where the roof -ceiling framing elements are parallel to the walls, such fram- ing and elements supporting such framing shall not be of less than one-hour 39 509.1-509.3 1994 UNIFORM BUILDING CODE EXCEPTION: Guardrails need not be provided at the following locations: I. On the loading side of loading docks. 2. On the auditorium side of a stage, raised platforms and other raised floor areas such as runways, ramps I and side stages used for entertainment or presentation. Along the side of an elevated walking surface when used for the normal functioning of special lighting or for access and use of other special equipment. At vertical openings in the performance area of stages. 3. Along vehicle service pits not accessible to the public. 509.2 Height. The top of guardrails shall not be less than 42 inches (1067 mm) in height. t EXCEPTIONS: 1. The top of guardrails for Group R, Division 3 and Group M, Division I Occupancies and interior guardrails within individual dwelling units, Group R, Division 3 congregate residences and guest rooms of Group R, Division I Occupancies may be 36 inches (914 nun) in height. 2. The lop of guardrails on it balcony immediately in front of the first row of fixed seals and which are not at the end of an aisle may be 26 inches (660 mm) in height. 3. The lop of guardrails forstairways, exclusive of their landings, may have it height as specified in Section 1006.9 for handrails. i 509.3 Openings. Open guardrails shall have intermediate rails or an ornamental patient such that a sphere 4 inches (102 min) in diameter cannot pass through. EXCEPTIONS: L The open space between the intermediate rails or ornamental pattern of guardrails in areas of commercial and industrial -type occupancies which are not accessible to the public may be such that a sphere 12 inches (305 mm) in diameter cannot pass Through. 2. The triangular openings formed by the riser, tread and bottom element of a guardrail at the open side of a stairway may be of such size that a sphere 6 inches (152 mm) in diameter cannot pass through. For guardrail requirements at grandstands, bleachers or other elevated seating facilities, see Sec- tion 1021.5.7. 1-90 708.2.2-708.4 1994 UNIFORM BUILDING CODE Walls having parallel or staggered studs I'm sound -transmission control shall have fire blocks of mineral fiber or glass fiber or other approved nonrigid materials. 708.3 Draft Stops. 708.3.1 Where required. Draftstopping shall be provided in the locations set forth in this section. 708.3.1.1 Floor -ceiling assemblies. 708.3.1.1.1 Single-family dwellings. When there is usable space above and below the concealed space of a floor -ceiling assembly in a single-family dwelling, draft stops shall be installed so that J the area of the concealed space does not exceed 1,000 square feel (93 1112). Draftstopping shall di- vide the concealed space into approximately equal areas. 708.3.1.1.2 Two or more dwellingun its and hotels. Draft stops shall be installed in floor -ceiling assemblies of buildings having more than one dwelling unit and in hotels. Such draft stops shall be in line with walls separating individual dwelling units and guest rooms from each other and from other areas. 708.3.1.1.3 Other uses. Draft stops shall be installed in floor -ceiling assemblies of buildings or portions of buildings used for other than dwelling or hotel occupancies so that the area of the con- cealed space does not exceed 1,000 square feet (93 m2) and so that the horizontal dimension be- tween stops does not exceed 60 feet (18 288 mm). EXCEPTION: Where approved automatic sprinklers are installed within the concealed space, the area between draft stops may be 3,000 square feet (279 m2) and the horizontal dimension may be 100 feel (30 480 Mill). 708.3.1.2 Attics. 708.3.1.2.1 Two or more dwelling units and hotels. Draft stops shall be installed in the attics, mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings con- taining more than one dwelling unit and in hotels. Such draft stops shall be above and in line with the walls separating individual dwelling units and guest rooms from each other and from other uses. EXCEPTIONS: I. Draft stops may be omitted along one of the corridor walls, provided draft stops at walls separating individual dwelling units and guest rooms from each other and from other uses, extend to the remaining corridor draft slop. 2. Where approved sprinklers are installed, draastopping cony be as specified in the exception to Section 708.3.1.2.2 below. 708.3.1.2.2 Other uses. Draft stops shall be installed in attics, mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings having uses other than dwellings or hotels so that the area between draft stops does not exceed 3,000 square feet (279 1112) and the great- est horizontal dimension does not exceed 60 feet (18 288 nun). EXCEPTION: Where approved automatic sprinklers are installed, the area between draft stops may be 9,000 square feet (836 m2) and the greatest horizontal dimension nuty be 100 feel (30 480 mm). 708.3.1.3 Draft stow construction. Draftstopping materials shall not be less than 1/2 -inch (12.7 mm) gypsum board, /g -inch (9.5 mill) wood structural panel, 3/8 -inch (9.5 mm) Type 2-M particle- board or other approved materials adequately supported. Openings in the partitions shall be protected by self-closing doors with automatic latches con- structed as required for the partitions. Ventilation of concealed roof spaces shall be maintained in accordance with Section 1505. 708.4 Draft Stops or Fire Blocks in Other Locations. Fireblocking of veneer on nonconhbus- tible walls shall be in accordance with Section 708.2.1, Item 1, above. For fireblocking ceilings applied against noncombustible construction, see Section 803, hent I. 1-114 1002.1.2-1003.1 1994 UNIFORM BUILDING CODE The occupant load for buildings or areas containing two or more occupancies shall be determined by adding the occupmn loads of the various use areas as computed in accordance with the applicable provisions of this section. 1002.1.3 Fixed sealing. For areas having fixed seats and aisles, the occupant load shall be deter- mined by the number of fixed seats installed therein. The required width of aisles serving fixed seats shall not be used for any other purpose. For areas having fixed benches or pews, the occupant load shall not be less than the number of seats based on one person for each 18 inches (457 ntm)'of length of pew or bench. Where booths are used in dining areas, the occupant load shall be based on one person foreach 24 inches (6 10 nun) of booth length or major portion thereof. 1002.1.4 Reviewing stands, grandstands and bleachers. The occupant load for reviewing stands, grandstands and bleachers shall be calculated in accordance with this section and the specif- ic requirements contained in Section 1021. 1002.2 Maximum Occupant Load. 1002.2.1 Assembly occupancies. The maximum occupant load for assembly occupancies shall not exceed the occupant load determined in accordance with Section 1002.1. EXCEPTION: When approved by the building official, the occupant load for an assembly occupancy may be increased provided the maximum occupant load served does not exceed the capacity of the exit system for such increased number of persons. The building official may require an aisle, seating or fixed equipment dia- grain to substantiate such an increase, and may require that such diagram be posted. 1002.2.2 Other occupancies. For other than assembly occupancies, an occupant load greater than that determined in accordance with Section 1002.1 is permitted; however, the exit system shall comply with the provisions of this chapter for such increased number of persons. 1002.3 PostingofRoornCapacity. Anyioomhavinganoccupanlloa(lof50ortnoiewherefixerl seats are not installed, and which is used for assembly propose, shall have the capacity of the room posted in a conspicuous place on an approved sign near the main exit from the room. Such signs shall be maintained legible by the owner or the owner's authorized agent and shall indicate the num- ber of occupants permitted for each room use. 1002.4 Revised Occupant Load. After a building is occupied, any change in use or increase in occupant load shall comply with this chapter. See Section 3405. SECTION 1003 — EXITS REQUIRED 1003.1 Numberof Exits. Every buildingorusable porlion lhcieofshalIhave itleast one exit, not less than two exits where required by Table 10-A and additional exits as required by this section. For purposes of this section, basements and occupied roofs shall be provided with exits as re- quired for stories. EXCEPTION: Occupied roofs on Group R, Division 3 Occupancies may have one exit if such occupied areas are less than 500 square feet (46.45 in I and are located no higher than immediately above the second story. Floors complying with the provisions for mezzanines as specified in Section 506, Exception 3, shall be provided with exits as specified therein. Occupants on stories above the first and in basements shall have access to not less than two sepa- 1 rate exits from the story or basement. EXCEPTIONS: 1. Second stories having an occupant load less than 10 cony be provided with only one exit. 2. Two or more dwelling units on the second story or in a basement may have access u> only one common exit when the total occupant load served by that exit (Ines not exceed 10. 1-174 1994 UNIFORM BUILDING CODE 1004.9-1005.2 access is not required, such dimension shall not exceed I inch (25 mm). Landings shall be level except for exterior landings, which may have a slope not to exceed 1/4 unit vertical in 12 units hori- zontal (2% slope). EXCEPTIONS: I. In Group R, Division 3, and Group U Occupancies and within individual units of ' Group R, Division I Occupancies: 1.1 A door may open at the top step of an interior Right of stairs, provided the door does not swing over the top step. 1.2 A door may open at a landing that is not more than 8 inches (203 mm) lower than the floor level, provided the door does not swing over the landing. 1.3 Screen doors and storm doors may swing over stairs, steps or landings. 2. Doors serving building equipment rooms which are not normally occupied. 1004.10 Landings at Doors. Landings shall have a width not less than the width of the stairway or the width of the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches (178 mm). When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing dimension to less than one half its re- quired width. Landings shall have a length measured in the direction of travel of not less than 44 inches (1l l8 mm). EXCEPTION: In Group R, Division 3, and Group U Occupancies and within individual units of Group ' R, Division I Occupancies, such length need not exceed 36 inches (914 nun). A landing which has no adjoining door shall comply with Section 1006.7. 1004.11 Door Identification. Glass doors shall conform to the requirements specified in Section 2406. Exit doors shall be marked so that they are readily distinguishable from the adjacent construction. 1004.12 Additional Doors. When additional doors are provided for egress purposes, they shall conform to all provisions of this chapter. EXCEPTION: Approved revolving doors having leaves which will collapse under opposing pressures may be used in exit situations, provided: I. Such doors have a minimum width of 6 feel 6 inches (1981 nun). 2. At least one conforming exit door is located adjacent to each revolving door. 3. The revolving door shall not be considered to provide any exit width. SECTION 1005 — CORRIDORS AND EXTERIOR EXIT BALCONIES 1005.1 General. This section shall apply to every corridor serving as a required exit for an occu- pant load of 10 or more except that Section 1005.2 shall apply to all corridors. For the purpose of this section, the term "corridor" shall include exterior exit balconies and covered or enclosed walk- I ways, tunnels and malls. Partitions, rails, counters and similar space dividers not over 5 feet 9 inches (1753 mm) in height above the floor shall not be construed to form corridors. Exit corridors shall not be interrupted by intervening rooms. EXCEPTION: Foyers, lobbies or reception rooms constructed as required for corridors shall not be con- strued as intervening rooms. Corridors which are located within an accessible route of travel shall also comply with Chapter II. For Group I Occupancies see Section 1019.3. 1005.2 Width. The minimum corridor width shall be determined as specified in Section 1003.2, but shall not be less than 44 inches (1118 mm), except as specified herein. Corridors serving an oc- cupant load of 49 or less shall not be less than 36 inches (914 nun) in width. For special requirements for Groups E and I Occupancies, see Sections 1017 and 1019. 1-179 1005.3-1005.8.1 1994 UNIFORM BUILDING CODE 1005.3 Height. Corridors and exterior exit balconies shall have a clear height of not less than 7 feet (2134 min) measured to the lowest projection from the ceiling. 1005.4 Projections. The required width of corridors shall be unobstructed. EXCEPTION: I landrails and doors, when fully opened, shall not reduce the required width by more than 7 inches (178 film). Doors in any position shall not reduce the required width by more than one half. Other nonstructural projections such as trim and similar decorative features may project into the required width 11/2 inches (38 mm) on each side. 1005.5 Access to Exits. When more than one exit is required, they shall be so arranged that it is l possible to go in either direction from any point in a corridor to a separate exit, except fordead ends not exceeding 20 feet (6096 mm) in length. 1005.6 Changesin Elevation. When a corridor or exterior exit balcony is accessible tothe handi- capped, changes in elevation of the floor shall be made by means of a ramp, except as provided for doors by Section 1004.9. 1005.7 Construction. Walls of corridors serving a Group R, Division l or Group I Occupancy having an occupant load of 10 or more and walls of corridors serving other occupancies having all occupant load of 30 or more shall be of not less than one-hour fire -resistive construction and the ceilings shall not be less than that required for a one-hour fire -resistive floor or roof system. EXCEPTIONS: I. One-story buildings housing Group S, Division 2 Occupancies. 2. Corridors more than 30 feel (9144 mal) in width where occupancies served by such corridors have at least one exit independent from the corridor. (See Chapter 4 for covered malls.) 3. Exterior sides of exterior exit balconies. 4. In Group 1, Division 3 Occupancies such as jails, prisons, reformatories and similar buildings with open -barred cells forming corridor walls, the corridors and cell doors need not be fire resistive. - 5. Corridor walls and ceilings need not be of fire -resistive construction within office spaces having an occupant load of 100 or less when the entire story in which the space is located is equipped with an automatic - sprinkler system throughout and an automatic smoke -detection system installed willti n the corridor.The actua- lion of any detector shall activate almms audible in all areas served by the corridor. 6. In other than Type I or 11 construction, exterior exit balcony roof assemblies may be of heavy-liniber construction without concealed spaces. 7. Within office spaces occupied by a single tenant, partial height partitions which form corridors and which do not exceed 6 feet (1829 nun) in height need not be fire resistive, provided they are constructed in accordance with Section 601.5 and are not more than three fourths of the floor -lo -ceiling height 8. Corridor walls and ceilings need not be of fire -resistive construction within office spaces having an occu- pant load of 100or less when the building in which the space is located is equipped with an automatic sprinkler system throughout. _ When the ceiling of the entire story is an element of a one-hour fire -resistive flooror roof system, the corridor walls may terminate at the ceiling. When the room -side fire -resistive membrane of the corridor wall is carried through to the underside of a fire -resistive floor or roof above, the corridor side of the ceiling may be protected by the use of ceiling materials as required for one-hour floor or roof system construction or the corridor ceiling may be of the same construction as the corridor walls. Ceilings of noncombustible construction may be suspended below the fire -resistive ceiling. For wall and ceiling finish requirements, see Table 8-B. For restrictions on the use of corridors to convey air, see Chapter 10 of the Mechanical Code. 1005.8 Openings. 1005.8.1 Doors. When corridor walls are required to be of one-hour fire -resistive construction by Section 1005.7, every interior door opening shall be protected by a tight -fitting smoke- and draft -control assembly having a fire -protection rating of not less than 20 minutes when tested in accordance with U.Q.C. Standard 7-2. Said doors shall not have louvers. The door and frame shall 1-180 1991 UNIFORM BUILDING CODE 1201-1204 Chapter 12 REQUIREMENTS FOR GROUP R OCCUPANCIES Group R Occupancies Defined Sec. 1201. Group R Occupancies shall be: Division 1. Hotels and apartment houses. Congregate residences (each accommodating more than 10 persons). Division 2. Not used. Division 3. Dwellings and lodging houses. Congregate residences (each accommodating 10 persons or less). For occupancy separations, see Table No. 5-B. A complete code forconstruction of detached one- and two-family dwellings is in Appendix Chapter 12 of this code. When adopted, as set forth in Section 103, it will take precedence over the requirements set forth in Parts 1 through X and Chap- ter 60 of this code. Construction, Height and Allowable Area Sec. 1202. (a) General. Buildings or parts of buildings classed in Group R be- cause of the use or character of the occupancy shall be limited to the types of con- struction set forth in Tables Nos. 5-C and 5-D and shall not exceed, in area or height, the limits specified in Sections 505, 506 and 507. (b) Special Provisions. Walls and floors separating dwelling units in the same building shall not be of less than one-hour fire -resistive construction. GroupR,Division 1 Occupancies more than two stories inheightorhavingmore than 3,000 square feet of floor area above the first story shall not be of less than one-hour fire -resistive construction throughout except as provided in Section 1705 (b) 2. Storage or laundry rooms that are within Group R, Division 1 Occupancies that are used in common by tenants shall be separated from the rest of the building by not less than one-hour fire -resistive occupancy separation. For Group R, Division 1 Occupancies with a Group B, Division I parkinggarage in the basement or first floor, see Section 702 (b) I. For attic space partitions and draft stops, see Section 2516 (f). Location on Property Sec. 1203. For fire -resistive protection of exterior walls and openings, as deter- mined by location on property, see Section 504 and Part IV. Access and Exit Facilities and Emergency Escapes Sec. 1204. Exits shall be provided as specified in Chapter 33. (See also Section 3317 for special requirements and Section 3314 for exit markings.) Access to, and egress from, buildings required to be accessible shall be provided " as specified in Chapter 31. 103 1985 EDITION 1201-1204 Chapter 12 REQUIREMENTS FOR GROUP R OCCUPANCIES Group R Occupancies Defined Sec. 1201. GroupR Occupancies shall be: Division 1. Hotels andd'ap�artmerit houses" Convents and monasteries (each accommodating more than 10 persons). Division 2. Not used. Division 3. Dwellings and lodging houses. For occupancy separations, see Table No. 5-B. A complete code for construction of detached one- and two-family dwellings is in Appendix Chapter 12 of this code. When adopted, as set forth in Section 103, it will take precedence over the requirements set forth in Parts I through X and Chapter 60 of this code. Construction, Height and Allowable Area Sec. 1202. (a) General. Buildings or parts of buildings classed in Group R because of the use or character of the occupancy shall be limited to the types of construction set forth in Tables No. 5-C and No. 5-D and shall not exceed, in area or height, the limits specified in Sections 505, 506 and 507. (b) Special Provisions. Group R, Division I Occupancies more than two stories in height or having more than 3000 square feet of floor area above the first story shall be not less than one-hour fire -resistive construction throughout except as provided in Section 1705 (b) 2. Storage or laundry rooms that are within Group R, Division I Occupancies that are used in common by tenants shall be separated from the rest of the building by not less than one-hour fire -resistive occupancy separation. Every apartment house three stories or more in height or containing more than 15 dwelling units and every hotel three stories or more in height or containing 20 or more guest rooms shall have an approved fire alarm system as specified in the Fire Code. F EXCEPTION: An alarm system need not be installed in buildings not over two p stories in height when all individual dwelling units and contiguous attic and crawl spaces are separated from each other and from public or common areas by at least F one-hour fire -resistive occupancy separations and each individual dwelling unit has an exit direct to a yard or public way. F For Group R, Division I Occupancies with a Group B, Division I parking garage in the basement or first floor, see Section 702 (a). For attic space partitions and draft stops, see Section 2516 (f). Location on Property Sec. 1203. For fire -resistive protection of exterior walls and openings, as determined by location on property, see Section 504 and Part IV. Exits and Emergency Escapes Sec. 1204. Stairs, exits and smokeproof enclosures shall be as specified in Chapter 33. 71 1204.1205 UNIFORM BUILDING CODE Every sleeping room below the fourth story shall have at least one operable window or exterior door approved for emergency escape or rescue. The units shall be operable from the inside to provide a full clear opening without the use of separate tools. All escape or rescue windows from sleeping rooms shall havp.p minimum net clear opening of 5.7 square feet. The minimum net clear opening height dimen- sion shall be 24 inches. The minimum net clear opening width dimension shall be 20 inches. Where windows are provided as a means of escape or rescue they shall have a finished sill height not more than 44 inches above the floor. Bars, grilles, grates or similar devices may be installed on an emergency escape or rescue windows or doors, provided: 1. Such devices are equipped with approved release mechanisms which are openable from the inside without the use of a key or special knowledge or effort; and 2. The building is equipped with smoke detectors installed in accordance with Section 1210. Light, Ventilation and Sanitation Sec. 1205. (a) Light and Ventilation. All guest rooms, dormitories and habitable rooms within a dwelling unit shall be provided with natural light by means of exterior glazed openings with an area not less than one tenth of the floor area of such rooms with a minimum of 10 square feet. All bathrooms, water closet compartments, laundry rooms and similar rooms shall be provided with natural ventilation by means of openable exterior openings with an area not less than one twentieth of the floor area of such rooms with a minimum of 11/2 square feet. All guest rooms, dormitories and habitable rooms within a dwelling unit shall be provided with natural ventilation by means of openable exterior openings with an area of not less than one twentieth of the floor area of such rooms with a minimum of 5 square feet. In lieu of required exterior openings for natural ventilation, a mechanical ventilating system may be provided. Such system shall be capable of providing two air changes per hour in all guest rooms, dormitories, habitable rooms and in public corridors. One fifth of the air supply shall be taken from the outside. In bathrooms, water closet compartments, laundry rooms and similar rooms a mechanical ventilation system connected directly to the outside, capable of '— providing five air changes per hour, shall be provided. For the purpose of determining light and ventilation requirements, any room may be considered as a portion of an adjoining room when one half of the area of the common wall is open and unobstructed and provides an opening of not less than one tenth of the floor area of the interior room or 25 square feet, whichever is greater. Required exterior openings for natural light and ventilation shall open directly onto a street or public alley or a yard or court located on the same lot as the building. 72 1991 UNIFORM BUILDING CODE 1209-1210 In nonsprinklered Group R, Division I Occupancies, corridors serving an occu- pant load of 10 or more shall be separated from corridors and other areas on adja- cent floors by not less than approved fixed wired glass set in steel frames or by 20 -minute smoke- and draft -control assemblies which are automatic closing by smoke detection. Smoke Detectors and Sprinkler Systems Sec. 1210. (a) Smoke Detectors. I. General. Dwelling units, congregate resi- dences and hotel or lodging house guest rooms that are used for sleeping purposes shall be provided with smoke detectors. Detectors shall be installed in accordance with the approved manufacturer's instructions. 2. Additions, alterationsor repairs to Group R Occupancies. When the valu- ation of an addition, alteration or repair to a Group R Occupancy exceeds $1,000 and a permit is required, or when one or more sleeping rooms are added or created in existing Group R Occupancies, smoke detectors shall be installed in accordance with Subsections 3, 4 and 5 of this section. 3. Power source. In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source and shall be equipped with a battery backup. The detector shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection. Smoke detectors may be solely battery operated when installed in existing buildings; or in buildings without commercial power; or in buildings which undergo alterations, repairs or additions regulated by Subsection 2 of this section. 4. Location within dwelling units. In dwelling units, a detector shall be in- stalled in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area. When the dwelling unit has more than one story and in dwellings with basements, a detector shall be installed on each story and in the basement. In dwelling units where a story or basement is split into two or more levels, the smoke detector shall be installed on the upper level, except that when the lower level contains a sleeping area, a detector shall be installed on each level. When sleeping rooms are on an upper level, thedetector shall be placed at the ceiling of the upper level in close proximity to the stairway. In dwelling units where the ceiling height of a room open to the hallway serving the bedrooms ex- ceeds that of the hallway by 24 inches or more, smoke detectors shall be instal led in the hallway and in the adjacent room. Detectors shall sound an alarm audible in all sleeping areas of the dwelling unit in which they are located. 5. Location in efficiency dwelling units, congregate residences and hotels. In efficiency dwelling units, hotel suites and in hotel and congregate residence sleep- ing rooms, detectors shall be located on the ceiling or wal I of the main room or each sleeping room. When sleeping rooms within an efficiency dwelling unit or hotel suite are on an upper level, the detector shall be placed at the ceiling of the upper level in close proximity to the stairway. When actuated, the detector shall sound an alarm audible within the sleeping area of the dwelling unit, hotel suite or sleeping room in which it is located. 107 1985 EDITION 1210-1212 sleeping rooms are on an upper level, the detector shall be placed at the center of the ceiling directly above the stairway. All detectors shall be located in accordance with approved manufacturer's instructions. When actuated, the detector shall provide an alarm in the dwelling unit or guest room. When the valuation of an addition or repair to a Group R, Division 3 Occupancy exceeds $1,000.00, or when one or more sleeping rooms are added or created in existing Group R, Division 3 Occupancies, the entire building shall be provided with smoke detectors located as required for new Group R, Division 3 Occupan- cies. In new construction, required smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection. Smoke detectors may be battery oper- ated when installed in existing buildings, or in buildings without commercial power, or in buildings which undergo alterations, repairs oradditions regulated by the second paragraph of this section. A smoke detector shall be installed in the basement of dwelling units having a stairway which opens from the basement into the dwelling. Such detector shall be connected to a sounding device or other detector to provide an alarm which will be audible in the sleeping area. (b) Sprinkler and Standpipe Systems. When required by other provisions of this code, automatic sprinkler systems and standpipes shall be installed as speci- fied in Chapter 38. Heating Sec. 1211. Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 70°F. at a point 3 feet above the floor in all habitable rooms. Special Hazards Sec. 1212. Chimneys and heating apparatus shall conform to the requirements of Chapter 37 and the Mechanical Code. The storage and handling of gasoline, fuel oil or other flammable liquids in Division 1 Occupancies shall be in accordance with the Fire Code. In Division 1 Occupancies, doors leading into rooms in which Class I flamma- ble liquids are stored or used shall be protected by a fire assembly having a one- hour fire -protection rating. Such fire assembly shall be self-closing and shall be posted with a sign on each side of the door in 1 -inch block letters stating: FIRE DOOR—KEEP CLOSED. Every room containing a boiler, central heating plant or hot-water supply boiler in Division I Occupancies shall be separated from the rest of the building by not less than a one-hour fire -resistive occupancy separation. EXCEPTION: A separation shall not be required for such rooms with equipment serving only one dwelling unit. 75 1991 UNIFORM BUILDING CODE (b) Sprinkler and Standpipe Systems. When required by other provisions of this code, automatic sprinkler systems and standpipes shall be installed as speci- fied in Chapter 38. Fire Alarm Systems Sec. 1211. Group R, Division I Occupancies shall be provided with an approved manual and automatic fire alarm system in apartment houses three or more stories in height or containing 16 or more dwelling units, in hotels three or more stories in height or containing 20 or more guest rooms and in congregate residences three or more stories in height or having an occupant load of 20 or more. A fire alarm and communication system shall be provided in Group R, Division 1 Occupancies lo- cated in a high-rise building. EXCEPTIONS: 1. A manual fire alarm system need not be provided in build- ings not over two stories in height when all individual dwelling units and contiguous attic and crawl spaces are separated from each other and public or common areas by at least one-hour fire -resistive occupancy separations and each individual dwelling unit or guest room has an exit directly to a public way, exit court or yard. 2. A separate fire alarm system need not be provided in buildings which are pro- tected throughout by an approved supervised fire sprinkler system having a local alarm to notify all occupants. Heating See. 1212. Dwelling units, guest rooms and congregate residences shall be pro- vided with heating facilities capable of maintaining a room temperature of 700F. at a point 3 feet above the floor in all habitable rooms. Special Hazards Sec. 1213. Chimneys and heating apparatus shall conform to the requirements of Chapter 37 and the Mechanical Code. The storage, use and handling of flammable and combustible liquids in Division 1 Occupancies shall be in accordance with the Fire Code. In Division 1 Occupancies, doors leading into rooms in which Class I flammable liquids are stored or used shall be protected by a fire assembly having a one-hour fire -protection rating. Such fire assembly shall be self-closing and shall be posted with a sign on each side of the door in I -inch block letters stating: FIRE DOOR— KEEP CLOSED. Every room containing a boiler, central heating plant or hot-water supply boiler in Division I Occupancies shall be separated from the rest of the building by not less than a one-hour fire -resistive occupancy separation. EXCEPTION: A separation shall not be required for such rooms with equip- ment serving only one dwelling unit. IU 108 Chapters 13-16 NO REQUIREMENTS 0 1710-1712 UNIFORM BUILDING CODE Projections from walls of Type 1I1, IV or V construction may be of noncombus- tible or combustible materials. Combustible projections located where openings are not permitted or where protection of openings is required shall be of one-hour fire -resistive or heavy timber construction conforming to Section 2106. Projections shall not extend more than 12 inches into the areas where openings are prohibited. For projections extending over public property, see Chapter 45. For combustible ornamentation, see Section 1705 (d). Guardrails Sec. 1711. All unenclosed floor and roof openings, open and glazed sides of landings and ramps, balconies or porches v}fh,alrri{prn 3- 0 jttcltes abnnuG de or floor _belowwa--n,d Goofs,used-forofher than service -of the-buildi_ng.sha(l_b rolt,�s1_by a guar4rat�1 Guardrails shall be not less than 42 inches in height. Open guardrail and stair railings shall have intermediate rails or an ornamental pattern such that a sphere 6 inches in diameter cannot pass through. The height of stair railings on open sides may be as specified in Section 3306 0) in lieu of providing a guardrail. Ramps shall, in addition, have handrails when required by Section 3307, EXCEPTIONS: 1. Guardrails need not be provided on the loading side of loading docks. 2. Guardrails for Group R, Division 3 and Group M, Division I Occupancies may be 36 inches in height. 3. Interior guardrails within individual dwelling units or guest rooms of Group R, Division I Occupancies may be 36 inches in height. 4. The open space between the intermediate rails or ornamental pattern of guard- rails in areas of commercial and industrial -type occupancies which are not accessible to the public may be increased such that a 12 -inch -diameter sphere cannot pass through. 5. Guardrails on a balcony immediately in front of the first row of fixed seats and which are not at the end of an aisle may be 26 inches in height. 6. Guardrails need not be provided on the auditorium side of a stage or enclosed platform. EpAguPlastIc Insulation Sec. 1712. (a) General. The provisions of this section shall govern the require- ments and uses of foam plastic in buildings and structures. For trim, see Section 1705 (e). Except where otherwise noted in this section, all foam plastics used in building construction shall have a flame -spread rating of not more than 75 and shall have a smoke -developed rating of not more than 450 when tested in the maximum thickness intended for use in accordance with U.B.C. Standard No. 42-1. All packages and containers of foam plastic and foam plastic ingredients shall bear the label of an approved agency showing either the flame -spread rating and smoke - developed rating of the product at the thickness tested or the use for which the product has been listed. The interior of the building shall be separated from the foam plastic by an approved thermal barrier having an index of 15 when tested in 82 1710-1712 1991 UNIFORM BUILDING CODE 3E (iv) The entire building shall be provided with not less than a Class B roof cov- ering. (b) Construction. Parapets shall have the same degree of fire resistance re- quired for the wall upon which they are erected, and on any side adjacent to a roof surface, shall have noncombustible faces for the uppermost 18 inches, including counterflashing and coping materials. The height of the parapet shall not be less than 30 inches above the point where the roof surface and the wall intersect. Where the roof slopes toward a parapet at slopes greater than 2:12, the parapet shall extend to the same height as any portion of the roof that is within the distance where protec- tion of wall openings would be required, but in no case shall the height be less than 30 inches. Projections See. 1711. Cornices, eave overhangs, exterior balconies and similar architectur- al appendages extending beyond the floor area as defined in Section 407 shall con- form to the requirements of this section. (See Sections 3305 and 3306 for additional requirements applicable to exterior exit balconies and stairways.) Projections from walls of Type I or II construction shall be of noncombustible materials. Projections from walls of Type III, IV or V construction may be of noncombus- tible or combustible materials. Combustible projections located where openings are not permitted or where protection of openings is required shall be of one-hour fire -resistive or heavy -tim- ber construction conforming to Section 2106. N For projections extending over public property, see Chapter 45. For combustible ornamentation, see Section 1705 (d). For fire -resistive requirements, see Section 504 (b). Guardrails and Vehicle Barriers Sec. 1712. (a) Guardrails. Unenclosed floor and roof openings, open and glazed sides of stairways, landings and ramps, balconies or porches, which are more than 30 inches above grade or floor below, and roofs used for other than ser- vice of the building shall be protected by a guardrail. EXCEPTION: Guardrails need not be provided at the following locations: A. On the loading side of loading docks. B. On the auditorium side of a stage or enclosed platform. C. Along vehicle service pits not accessible to the public. The top of guardrails shall not be less than 42 inches in height. EXCEPTIONS: I. The top of guardrails for Group R, Division 3 and Group K Division I Occupancies and interior guardrails within individual dwelling units, Group R, Division 3 congregate residences and guest rooms of Group R, Division 1 Occupancies may be 36 inches in height. 2. The top of guardrails on a balcony immediately in front of the first row of fixed seats and which are not at the end of an aisle may be 26 inches in height. 116 2516 UNIFORM BUILDING CODE (iii) Other uses. Draft stops shall be installed in floor -ceiling assemblies of buildings or portions of buildings used for other than dwelling or hotel occupan- cies so that the area of the concealed space does not exceed 1,000 square feet and so that the horizontal dimension between stops does not exceed 60 feet. EXCEPTION: Where approved automatic sprinklers are installed within the concealed space, the area between draft stops may be 3,000 square feet and the horizontal dimension maybe 100 feet. B. Attics. (i) Single-family dwellings. None required. (ii) Av.gocmore,dwelling unitsandhotelg, Draft stops shall be installed in the attics, mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings containing more than one dwelling unit and in hotels. Such draft stops shall be above and in line with the walls separating tenant spaces from each other and from other uses. EXCEPTIONS: 1. Draft stops may be omitted along one of the corridor walls, provided draft stops at tenant separation walls extend to the remaining corridor draft stop. . 2. Where approved sprinklers are installed, draftstopping may be as specified in the exception to Item (iii) below. (iii) Qjhel;,usm Draft stops shall be installed in attics, mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings having uses other than dwellings or hotels so that the area between draft stops does not exceed 3,000 square feet and the greatest horizontal dimension does not exceed 60 feet. EXCEPTION: Where approved automatic sprinklers are installed the area be- tween draft stops may be 9,000 square feet and the greatest horizontal dimension maybe 100 feet. 5. Draft stop construction. Draftstopping materials shall be not less than 1/2 - inch gypsum board, 3/8 -inch plywood or other approved materials adequately supported. Openings in the partitions shall be protected by self-closing doors with auto- matic latches constructed as required for the partitions. Ventilation of concealed roof spaces shall be maintained in accordance with Section 3205. 6. Draft or fire stops in other locations. Firestopping of veneer on noncom- bustible walls shall be in accordance with Item No. 2 A above. For firestopping of wood floors on masonry or concrete floors, see Sections 1804 and 1904. For firestopping ceilings applied against noncombustible construction, see Section 4203, Item No. 1. For firestopping penetrations in walls required to have protected openings, see Section 4304 (e). For firestopping penetrations through floors, see Section 4305 (a). (g) Exterior Wall Coverings. 1. General. Exterior wood stud walls shall be covered on the outside with the materials and in the manner specified in this section or elsewhere in this code. Studs or sheathing shall be covered on the 204 1985 EDITION Roof Insulation 3204-3206 Sec. 3204. The use of combustible roof insulation shall be permitted, provided it is covered with approved roof covering applied directly thereto. For foam plastic, see Section 1712. Insulation shall be of a rigid type suitable for application of a roof covering. Where fire -retardant roof coverings are required, insulations shall be a type approved for the type of deck and the built-up roofing applied. Where built-up roofing is to be applied, vapor barriers shall be installed between the deck and the insulation where the average January temperature is below 45T or where excessive moisture conditions are anticipated within the building. AtSed, 3205. a) Access. An attic access opening Aall be provided in the ceiling of the top floor of buildings with combustible ceiling or roof construction. The opening shall be located in a corridor or hallway of buildings of three or more stories in height and readily accessible in buildings of any height. The opening shall be not less than 22 inches by 30 inches. Thirty -inch minimum clear head room shall be provided above the access opening. Attics with a maximum vertical clear height of less than 30 inches need not be provided with access openings. (b) Draft Stops. Attics, mansards, overhangs and other concealed roof spaces formed of combustible construction shall be draft stopped as specified in Section 2516 (f). (c) Ventilation. Where determined necessary by the building official due to atmospheric or climatic conditions, enclosed attics and enclosed rafter spaces formed where ceilings are applied direct to the underside of roof rafters shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. The net free ventilating area shall be not less than 1/150of the area of the space ventilated, except that the area may be 1/3oo, provided at least 50 percent of the required ventilating area is provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet above eave or cornice vents with the balance of the required ventilation provided by eavepr cornice vents. The openings shall be covered with corrosion -resistant metal mesh with mesh openings of 'Minch in dimension. Smoke and Heat Venting Sec. 3206. (a) When Required. Smoke and heat vents shall be installed in accordance with the provisions of this section as follows: 1. In single -story Group B, Divisions 2 and 4 Occupancies having over 50,000 square feet in undivided area. EXCEPTIONS: 1. Office buildings and retail sales areas. 2. Group B, Division 4 Occupancies used for bulk frozen food storage when the building is protected by a complete automatic sprinkler system. 547 3302-3303 UNIFORM BUILDING CODE The maximum occupant load for an assembly use shall not exceed the occupant load as determined in accordance with Section 3302 (a). EXCEPTION: The occupant load for an assembly building or portion thereof may be increased, when approved by the building official, if all the requirements of this code are met for such increased number of persons. The building official may require an approved aisle, seating or fixed equipment diagram to substantiate such an increase, and may require that such diagram be posted. „ ( (c)sipg oltil�pQKn trORy. Any room having an occupant load of 50 or ore where fixed seats are not installed, and which is used for classroom, C l F f CS assembly or similar purpose, shall have the capacity of the room posted in a jl4t ` conspicuous place on an approved sign near the main exit from the room. Such signs shall be maintained legible by the owner or his authorized agent and shall indicate the number of occupants permitted for each room use. (d) Revised Occupant Load. After a building is occupied, any change in use or increase in occupant load shall comply with this chapter. See Section 502. � tw�s.,�.qui cL Sec. 3303. (a) Number of Exits. Every building or usable portion thereof shall have at least one exit, not less than two exits where required by Table No. 33-A ; and additional exits as required by this subsection. - For purposes of this section, basements and occupied roofs shall be provided with exits as required for stories. Floors complying with the provisions for mezzanines as specified in Section 1716 shall be provided with exits as specified therein. The second story shall be provided with not less than two exits when the occupant load is 10 or more. EXCEPTIONS: 1. Except as provided in Table No. 33-A, only one exit need be provided from the second story within an individual dwelling unit. Refer to Section 1204 for emergency escape or rescue requirements from sleeping rooms. 2. Two or more dwelling units on the second story may have access to only one common exit when the total occupant load does not exceed 10. Occupants on floors above the second story and in basements shall havgyccess to not less than two separate exits from the floor or basement. EXCEPTIONS: 1. Floors and basements used exclusively for service of the building may have one exit. For the purposes of this exception, storage rooms, laundry rooms, maintenance offices and similar uses shall not be considered as providing service to the building. 2. Basements within an individual dwelling unit having an occupant load of less than 10 may have one exit. 3. Storage rooms, laundry rooms and maintenance offices not exceeding 300 square feet in floor area may be provided with only one exit. 4. Occupied roofs on Group R, Division 3 Occupancies may have one exit if such occupied areas are less than 500 square feet located no higher than immediately above the second story. For special requirements see the following sections: Group A, Sections 3317 and 3318; Group E, Section 3319; Group H, Section 3320; Group I, Seciion 3321; Rooms Containing Fuel -fired Equipment and Cellulose Nitrate Handling Rooms, 556 3304 UNIFORM BUILDING CODE 3. Doors swinging toward flow of traffic shall not be permitted for use by untrained pedestrian traffic unless actuating devices start to function at least 8 feet I I inches beyond door in open position and guide rails extend 6 feet 5 inches beyond door in open position. Clearances for guide rails shall be as follows: I. Six inches maximum between rails and leading edge of door at the closest point in its arc of travel. 2. Six inches maximum between rails and the door in open position. 3. Two inches minimum between rail at hinge side and door in open position. 4. Two inches maximum between freestanding rails andjamb or other adjacent surface. (h) Floor Level at Door Regardless Regardless of the occupant load, there shall be a an ing floor or onch easide of a door. When access for the physically handi- capped is required by Section 3301 (e), the floor or landing shall be not more than 1/2 inch lower than the threshold of the doorway. When such access is not required, such dimension shall not exceed I inch. EXCEPTIONS: 1, In Groups R, Division 3 and M Occupancies and within individual units of Group R, Division I Occupancies: A. A door may open at the top step of a flight of stairs, provided the door does not — swing over the top step. B. A door may open at a landing that is not more than 71/2 inches lower than the floor level, provided the door does not swing over the landing. C. Screen doors and storm doors may swing over stairs, steps or landings. 2. Doors serving building equipment rooms which are not normally occupied. (i) .r_ ings atI)oors, Landings shall have a width not less than the width of the stairway or the width of the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing dimension to less than one half its required width. Landings shall have a length treasured in the direction of travel of not less than 44 inches. — EXCEPTION: In Group R, Division 3 and M Occupancies and within individual units of Group R, Division I Occupancies, such length need not exceed 36 inches. A landing which has no adjoining door shall comply with Section 3306 (g). Q) Door Identification. Glass doors shall conform to the requirements speci- fied in Section 5406. Exit doors shall be so marked that they are readily distinguishable from the adjacent construction. (k) Additional Doors. When additional doors are provided for egress pur- poses, they shall conform to all provisions of this chapter. EXCEPTION: Approved revolving doors having leaves which will collapse under opposing pressures may be used in exit situations, provided: 1. Such doors have a minimum width of 6 feet 6 inches. 2. Al least one conforming exit door is located adjacent to each revolving door. 3. The revolving door shall not be considered to provide any exit width. 560 1885 EDITION 3305 i Corridors and Exterior Exit Balconies Sec. 3305. (a) General. This section shall apply to every corridor serving as a required exit for an occupant load of 10 or more except as provided in Subsection (b) for Group R, Divisions 1 and 3 Occupancies. For the purposes of the section, the term "corridor" shall include "exterior exit balconies" and any covered or enclosed exit passageway, including walkways, tunnels and malls. Partitions, rails, counters and similar space dividers not over 5 feet 9 inches in height above the floor shalt not be construed to form corridors. Exit corridors shall not be interrupted by intervening rooms. EXCEPTION: Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms. (b ►d►dth. Every corridor serving an occi.ant 1 ad of, 1100 ,o,,r,,� g,�shall be not I than 44,nches in width. Regardless o the occupant Woad, corridors in Group R, Division 3 Occupancies and within dwelling units in Group R, Division 1 Occupancies shall have a %ewmuLw�f36,g. For special requirements for Groups E and I Occupancies,see Sections 3319 and 3321. (c) Height. Corridors and exterior exit balconies shall have a clear height of not less than 7 feet measured to the lowest projection from the ceiling. (d) Projections. The required width of corridors shall be unobstructed. EXCEPTION: Handrails and doors, when fully opened, shall not reduce the required width by more than 7 inches. Doors in any position shall not reduce the required width by more than one half. Other nonstructural projections such as trim and similar decorative features may project into the required width 11/2 inches on each side. (e) Access to Exits When more than one exit is required, they shall be so arranged ttha tt is possible to go in either direction from any point in a corridor to a separate exit, except for dead ends not exceeding 20 feet in length. (f) Changes in Elevation. When a corridor or exterior exit balcony is accessi- ble to the handicapped, changes in elevation of the floor shall be made by means of a ramp, except as provided for doors by Section 3304 (h). (g) Construction. Walls of corridors serving a Group R, Division I or Group I Occupancy having an occupant load of 10 or more and walls of corridors serving other occupancies having an occupant load of 30 or more shall be of not less than one-hour fire -resistive construction and the ceilings shall be not less than that required for a one-hour fire -resistive floor or roof system. EXCEPTIONS: 1. One-story buildings housing Group B, Division 4 Occupan- cies. 2. Corridors more than 30 feet in width where occupancies served by such +1 corridors have at least one exit independent from the corridor. (See Appendix Chapter 7, Division 1, for covered malls.) 3. Exterior sides of exterior exit balconies. 4. In Group 1, Division 3 Occupancies such as jails, prisons, reformatories and similar buildings with open -barred cells forming corridor walls, the corridors and cell doors need not be fire resistive. 561 1905 EDITION 3306 Stairways See. 3306. (a) General. Every stairway having two or more risers serving any building or portion thereof shall conform to the requirements of this section. EXCEPTION: Stairs or ladders used only to attend equipment are exempt from the requirements of this section. (b) Width. Stairways serving an occupant load of 50 or more shall be not less than 44 inches in width. Stairways serving an occupant load of 49 or less shall be not less than 36 inches in width. Handrails may project into the required width a distance of 31/2 inches from ,N each side of a stairway. Stringers and other projections such as trim and similar decorative features may project into the required width 11/2 inches on each side. 4,RI!n:The rise of every step in a stairway shall be not less than 4 } inches nor greater than 7 inches. Except as permited in Subsections (d) and (f), the R run shall be not less than l I inches as measured horizontally between the vertical f planes of the furthermost projection of adjacent treads. Except as permitted in Subsections (d), (e) and (f), the largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. EXCEPTIONS: 1. Private stairways serving an occupant load of less than 10 and stairways to unoccupied roofs may be constructed with an 8 -inch maximum rise and 9 -inch minimum run. 2. Where the bottom or top riser adjoins a sloping public way, walk or driveway having an established grade and serving as a landing, a variation in height of the '^ bottom or top riser of not more than 3 inches in every 3 feet of stairway width is permitted. (d) Winding Stairways. In Group R, Division 3 Occupancies and in private stairways in Group R, Division 1 Occupancies, winders may be used if the required width of run is provided at a point not more than 12 inches from the side of the stairway where the treads are the narrower, but in no case shall any width of run be less than 6 inches at any point. (e) Circular Stairways. Circular stairways may be used as an exit, provided the minimum width of run is not less than 10 inches and the smaller radius is not less than twice the width of the stairway. The largest tread width or riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. (f) Spiral Stairways. In Group R, Division 3 Occupancies and in private stairways within individual units of Group R, Division 1 Occupancies, spiral stairways may be installed. Such stairways may be used for required exits when the area served is limited to 400 square feet. The tread must provide a clear walking area measuring at least 26 inches from the outer edge of the supporting column to the inner edge of the handrail. A run of at least 71/2 inches is to be provided at a point 12 inches from where the tread is the narrowest. The rise must be sufficient to provide 6 -foot 6 -inch headroom. The rise shall not exceed 91/2 inches. (g) Landings. Every landing shall have a dimension measured in the direction of travel equal to the width of the stairway. Such dimension need not exceed 44 563 1985 EDITION 3306-3307 Except when enclosed usable space under stairs is prohibited by Section 3309 (f), the walls and soffits of the enclosed space shall be protected on the enclosed side as required for one-hour fire -resistive construction. All required interior stairways which extend to the top floor in any building four or more stories in height shall have, at the highest point of the stair shaft, an approved hatch openable to the exterior not less than 16 square feet in area with a minimum dimension of 2 feet. EXCEPTION: The hatch need not be provided on smokeproof enclosures or on stairways that extend to the roof with an opening onto that roof. (n) Exterior Stairway Construction. Exterior stairways shall be of noncom- bustible material except that on Types III and IV buildings not exceeding two stories in height, and on Type V buildings, they may be of wood not less thati 2 inches in nominal thickness. Exterior stairways shall not project into yards where protection of openings is required. Enclosed usable space under stairs shall have the walls and soffits protected on the enclosed side as required for one-hour fire -resistive construction. (o) Stairway to Roof. In every building four or more stories in height, one stairway shall extend to the roof surface, unless the roof has a slope greater than 4 in 12. See Subsection 3306 (m) for roof hatch requirements. (liLLIegAroom.Every stairway shall have a headroom clearance of not less than 6 feet V in diePs. Such clearances shall be measured vertically from a plane parallel and tangent to the stairway tread nosings to the soffit above at all points. i (q) Stairway Numbering System. An approved sign shall be located at each F floor level landing in all enclosed stairways of buildings four or more stories in height. The sign shall indicate the floor level, the terminus of the top and bottom F of the stairway and the identification of the stairway The sign shall be located approximately 5 feet above the floor landing in a position which is readily visible when the door is in the open or closed position. Signs shall comply with require- ments of U.B.C. Standard No. 33-2. F Ramos Sec. 3307. (a) General. Ramps used as exits shall conform to the provisions of this section. (b) Width. The width of ramps shall be as required for stairways. (c) Slope. The slope of ramps required by Table No. 33-A shall be not steeper than l vertical to 12 horizontal. The slope of other ramps shall not be steeper than 1 vertical to 8 horizontal. When provided with fixed seating, the main floor of the assembly room of a Group A, Division 1, 2, 2.1 or 3 Occupancy may have a slope not steeper than I vertical to 5 horizontal. (d) Landings. Ramps having slopes steeper than 1 vertical to 15 horizontal shall have landings at the top and bottom, and at least one intermediate landing shall be provided for each 5 feet of rise. Top landings and intermediate landings shall have a dimension measured in the direction of ramp run of not less than 5 565 i �• r' 4304-4305 UNIFORM BUILDING CODE assigned fire -resistive rating will be the shortest duration obtained from the two tests conducted in conformance with U.B.C. Standard No. 43-1. When evidence is furnished to show that the wall was tested with the least fire -resistive side exposed to the furnace, the building official may not require that the wall be subjected to tests from the opposite side. (e) Penetrations. Penetrations in walls requiring protected openings shall be fire -stopped. Firestopping shall be an approved material securely installed and capable of maintaining its integrity when subjected to test temperatures pre- scribed in U.B.C. Standard No. 43-1 for the specific wall or partition. Openings in walls and partitions shall be protected as specified in Section 4306. Where fire -rated walls and partitions require protected openings, the „ following penetrations into or through such construction are permitted: 1. Copper or ferrous pipes or conduits may penetrate the walls or partitions, provided firestopping is provided in accordance with the first paragraph of this section. 2. Openings for steel electrical outlet boxes not exceeding 16 square inches in area, provided the area of such openings does not aggregate more than 100 square inches for any 100 square feet of wall or partition area. Outlet boxes on opposite sides of walls orpartitions shall be separated by a horizontal distance of 24 inches. 3. Where walls are penetrated by other materials or where larger openings are required than permitted in Item No. 2 above, they shall be qualified by tests conducted in accordance with the provisions of Section 4302 (b). Floor -Ceilings or Roof -Ceilings Sec. 4305. (a) General. Fire -resistive floor -ceiling or roof -ceiling construc- tion systems shall be assumed to have the fire -resistance ratings set forth in Table No. 43-C. Penetrations in floors and ceilings requiring protected openings shall be fire -stopped. Firestopping shall be of an approved material, securely installed and capable of maintaining its integrity when subjected to the time -temperature curve of U.B.C. Standard No. 43-1 for the specific floor -ceiling or roof -ceiling construction. EXCEP'T'ION: Where penetrations are protected as shaft enclosures as required in Section 1706. When materials are incorporated into an otherwise fire -resistive assembly which may change the capacity for heat dissipation, fire test results or other substantiating data shall be made available to the building official to show that the required fire -resistive time period is not reduced. (b) Floors. Fire -resistive floors shall be continuous and all openings for me- chanical and electrical equipment shall be enclosed as specified in Section 1706. EXCEPTIONS: 1. Occasional pipes, conduits, sleeves and electrical outlets of copper, sheet steel or ferrous construction may be installed within or through fire - resistive floorsystems, provided such installations do not unduly impair the required fire resistance of the assembly. 2. The provisions of this section shall not apply when such openings are in —' accordance with the results of tests conducted pursuant to the provisions of Section 4302 (b). 614 i REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 THIS IS TO GIVE NOTICE THAT: An inspection of the Applewood Apartments located at 151 South 1st East in Rexburg, Idaho was conducted on this date and that as nearly as could be determined, was found to be in compliance with the Uniform Fire Code and ordinances of the City of Rexburg that are presently in effect, with the following exceptions: Sec. 901.4.4 Post address on the front of the building. Sec. 903 Water supply needs t0 be_fiUure_C1 and iy_ rants installer_ within the complex_ asregui_red. egress window. Some balconies onit, have one way_off_ Sec_ 1103.3.2.1 Storage shall be orderly__in Storage ,1_eas, General housecleaning needs to be done in these areas. t,ible materialsshal_1not_hesl;uredin boiler Note: This inspection was necessarily limited to items and areas in plain and full view of the inspector. This inspection cannot ensure or verify the compliance of the items or areas that are destructed from the inspector's view by construction or access. The City of Rexburg can accept no responsibility for verification of code compliance in such areas. Such verification becomes the sole responsibility and liability of the property owner. persons preformitng corrective action should contact the Rexburg Madison County Fire Department at (20i�) 359-3010 for specifics or questions regarding these requiremaits. Any observable deficiencies which are a distinct hazard to life and/or property are subject to criminal enforcemenr if they are not remedied immediately. Dee Owens Fire Inspector February 2, 1996 Date REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 Fire Extinguishers Inspection and Maintenance Fire extinguishers require an inspeeii.on eves 30clays. If circumstances require it may need to be more frequent. Inspection shall include at least the following items: (a) Located in designated place. (b) No obstruction to access or visibility. (c) Operating instructions on nameplate legible and facing outward. (d) Seals and tamper indicators not broken or missing. (e) Determine fullness by weighing or "hefting." (f) Examine for obvious physical damage, corrosion, leakage, or clogged nozzle. (g) Pressure gage reading or i.ntlicator-in the operable range or position. Any problems need to be corrected immediately or a replacement extinguisher provided until it can be. Fire extinguishers require ma int enance_not mo re.than__one __.�ear apart. Maintenance shall include a through examination of the three basic elements of an extinguisher: (a) Mechanical parts, (b) extinguishing agent, and (c) expelling means. Stored pressure extinguishers require a hydrostatic test every 12 years and need to be emptied every six years and subjected to maintenance procedures. The owner could preform the inspection procedure with proper training. I would recommend that you have an outside source preform the maintenance of your extinguishers. REXBURC MADISON COUNTY FIRE DEPARTMENT • P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 Smoke Detectors and Locations Smoke detectors shall be installed in accordance with the approved manufacture's instructions. The 1994 UBC states in Sec. 310.9.1.4 Location within dwelling units. In dwelling units, a detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area. When the dwelling unit has more than one story and in the dwellings with basements, a det.rctor shall be installed on each story and in the l:asernent. Iu dwelI ing ui its where a story or basement is split into two or more levels, the smoke detector shall be installed on the upper level, except that when the lower level contains the sleeping area, a detector shall be installed on each level. When sleeping rooms are on an upper level, the detector shall be placed at the ceiling of the upper level in close proximity to the stairway. In dwelling units where the ceiling height of a room open to the hallway serving the bedrooms exceeds that of the hallway by 24 inches or more, smoke detectors shall be installed in the hallway and in the adjacent room. Detectors shall sound an alarm audible in all sleeping areas of the dwelling unit in which they a;:e located. Some of your smoke detectors are very poorly located, I would recommend that you relocate them using the UBC section to provide better warning. Avoid the dead air spaces that we discussed (six inches clown or out). The smoke detectors need to be tested at least monthly. Ycu should use a test smoke and not just tl,e test button. Batteries need to be replaced yearly. I realize that the smoke detectors were not required in the sleeping rooms at the time of constriction but would recommend that you install them if possible. tLH-N6-'at. WE 14:tjN 1U: IEL N0: Rt134 PN3 PHILIP E. BATT Gavonyr Stare of Idaho DEPARTMENT OF LABOR AND INDUSTRIAL SERVICES PocA-ml-1-0 AREA OITICE February 6, 1996 Stephen E. Clark 625 S. 5000 W. Rexburg, ID 83440 Dear Mr. Clark: 611 Wll�n, sane 4C P.O. Box 4969 Pooet6110, ID 83206-4969 (208) 238-6086 FAX (206) 236-6227 After reviewing and inspecting the apartments located at 151 S. First E. in Rexburg, I found that a good portion of the electrical installation was inadequate and in poor workmanship. I was only able to see the finished product and have no idea of what lies behind the walls. In any case, the requested inspections indicate a large amount of redundancy and repeat violations (please see enclosed findings). If I can be of further assistance, please feel free to contact me at (208) 359-3025. Sincerely, Scott Richter Electrical Inspector rlm Enclosures c: Terry L. Coumerilh Equal Opporruniry Employer Tib: REXBURG FED -06-'06 TUE 14:54 ID: TEL NO: EF -411 STATE OF IDAHO 2/20/02R DEPARTHENT 0# LABOR AND INDUSTRIAL SERVICES ELECTRICAL DIVISION 27T NORTH SIXTH - STATEHOUSE MAIL Bow, ID 53720•G000 (208) 334.2183 NAME: Stephen E. Clark ADDRESS:625 S. 5000 W. Rexburg, ID 83440 PERMIT NUMBER: REo1)ESTED. INSPECTION FINDINGS APPLICANT; NAME, Stephen E. Clark "136 F01 ADDRESS: 625 S. 5000 W. Rexburg, ID 83440 TYPE OF BUILDING: Student Apartments LOCATION OF BUILDING: 151 S. First E. , Rexburg, ID 83440 .............................................................................................................................. THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS BEEN INSPECTED AND UAS FOUND TO BE ESSENTIALLY IN ACCORD WITH THE MINIMUM REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSTALLATION EXCEPT AS FOLLOWS: N)C REFERENCE ! FINDINGS 336-]-0-b i jam. — Outside_ i Addition I 336-15 i Romex riot secured along framing members. Scott Richter ELECTRICAL INSPECTOR 2/6/06 DATE TO: RE x -MI_ RG — -----FEU-6E-'96 FUE 14:51 It: TEL N0: N135 P01 EF•411 STATE OF IDAHO 2/20/92R DEPARTMENT OF LABOR ANO INDUSTRIAL SERVICES ELECTRICAL DIVISION 27? NORTH SIATN • STATEHOUSE MAIL BOISE. 10 83720.6000 (208) 714.218.3 NAME: Stephen E. Clark ADDREss:625 S. 5000 W. Rexburg, ID 83440 PERMIT NUMBER: REOVE$TED INSPECTION FINDIw9s `4pPi1 CANT: NAME: Stephen E. Clark ADDRESS: 625 S. 5000 W. E ex urg, TYPE OFBUILOINO: Student Anartmenis LOCATION OF BUILDING: 151 2. First & . Rexburg. ID 83440 THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS BEEN INSPECTED AND WAS FOUND TO BE ESSENTIALLY IN ACCORD WITH THF MINIMum REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSTALLATION EXCEPT AS FOLLOVS: Laundry Room 1 Surface mounted fluorescent fixture over dryer #4 hanging on 410_-15-a _ I On One side not Rf�rllrpri +n rail ins. 370-25 ` 1 Behind dryer #15 and washer #8 outlet has no Inver nlw+u Scott Richter ELECTRICAL INSPECTOR AA 2/6/96 DALE TUE 14:45 ID: TEL NO: Pb_j ET 411 STATE OF IDAHO 2/20/92R DEPARTMENT Of LABOR ANO INDUSTRIAL SERVICES ELeCTAICAL Div)sIDN 277 NORTH SIXTH • STATEHOUSE MAIL BOISE, IO 83720-6000 (208) 334-2183 PROPERTY OWNER: NAME; Stephen E. Clark AoDREss; 625 S. 50.0 w Rexburg, ID 83440 PERMIT NUMBER, REQUESfED INspecyiny FiwDiNGs APPLICANT: w NAME, Stephen E. Clark ADDRessf25 S. 5000 W. Rexburg, ID 83440 TYPE OF BUILDING;tit11fient Abartm Pnts Low ION OFBUILDINB- bur' ID 83440 ....,.....a.aw..af...a...A...................................................................................... THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS SEEN INSPECTED AND WAS FOUND TO BE ESSENTIALLY IN ACCORD WITH THE MINIMUM REOUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSTALLATION EXCEPT AS FOLLOWS. NEC REFERENCE ' Unit H-- Unit 114 I Panel labeling circuit not Complete, Scott Richter .LECTRICAL INSPECTOR ka 2/6/96 OAT( IEP! I E1J-0b-' Jb TOE 14: b6 I U: IEL NO: EF -611 STATE OF IDAHO 2/20/02R DEPARTMENT OF LABOR AND INDUSTRIAL SERVICES ELECTRICAL DIVISION 277 NORTH SIXTH - STATEHOUSE MAIL BOISE, ID 83720.6000 (Z0a) 334.2193 PROPERTY QWNER: NAME: Stephen E. Clark ADDRESS: 625 S. 5000 W. Rexburg, ID 83440 PERMIT NUMBER: REDOE5TED INSPECtIQN FINDINGS . I " 1. APPLICANT: NAME: Stephen E. Clark ADDRESS: 625 S. 5000 W. ex urg, 11) bJ44U H136 P03 TYPE OF BUILDING: Student Apartments LOCATION Of BUILDING: 151 S. First E., Rexburg, ID 83440 •..... A b......A O.taNrttr..00Yv.*.I.*.... ..A ................ t.Ay..•.....*.*0*....A.•........... a.......a•............ THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS BEEN INSPECTED AND WAS FOUND TO BE ESSENTIALLY IN ACCORD WITH THE MINIMUM REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSTALLATION EXCEPT A$ FOLLOWS: 110=12-a In panel there are open splices not closed. 210-8-a_ f In bathroom opposite vanity, outlets not GFIC protected. 410-4 In shower room, light fixture not approved for damp location. Unit 211 GFIC protected. 4 11/0111:1 410-4 Shower room fixture not apnrnvPd for damn lo.ation 410 -R -r Tight i x lrP in rin ata not agproyed I ,Scott Richter 2/6/96 ELECTRICAL INSPECTOR DACE kB T0: REXBURG FEEL -06-'96 TUE 14:52 ID: TEL NO: 14135 P02 IF -411 STATE OF IDAHO 2/20/92* DEPARTMENT OF LABOR AND INDUSTRIAL SERVICES ELECTRICAL DIVISION 271 NORTH SIXTH - STATEHOUSE MAIL Boise, ID 83720.6000 (208) 334.2183 RUVISYEO INsPectioN FINOIN6S PROPERTY OWNER_: APPLICANT: NAME: Stephen E. Clark NAME: Stephen E. Clark ADDRESS:_ Rexburg, ID 83440 PERMIT NUMBER: ADDRESSAi2e.5 S. 5000 W, Rexburg, ID 83440 TYPE OFBUILDINQ: Student Apartments LOCATION Of BUILDING: 151 S. First E., Rexburg, ID 83440 ..........0 .................... .Y..I.......................... ............................................................... THE ELECTRICAL INSTALLATION OESCRIIIED ABOVE HAS BEEN INSPECTED AND UAS FOUND TO BE ESSENTIALLY IN ACCORD NIMH THE MINIMUM REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSTALLATION EXCEPT AS FOLLOWS: for tion. zLu-rs-a-t ' Outlets opposite vanity are not GFIC protected in bathroom 90-4 ; In living room veil fixture flickers. unus in panel Scott Richter 2/6/96 ELECTRICAL INSPECTOR DATE RA v I �' • I %L.f •,u1 -JI %,-A FEU -06-196 TUE 14:56 ID: TEL N0: "136 PO4 EF•411 STATE Of IDAHO 2/20/928 DEPARTMENT OFI-IRDR AMO INDUSTRIAL SERVICES ELECTRICAL DIVISION 277 NORTH SIXTH • STATEHOUSE MAIL BOISE, IO 827206000 (208) 33L•2183 REOUESTEO INSPECTS FINDINGS ROPERTY OWNER: APPLICANT: NAME; Stephen E. Clark NAME: Stephen E. Clark ADDRESS: 625 S. 5000 W. Rexburg, ID 83440 PERMIT NUMBER: ADDRESS. 625 S. 5000 W. Rexburg, 115 83440 Type OFBUILDIwG:Student Apartments LOCATION Of BUILDING: 151 S. First E., Rexburg, ID 83440 ..............v...........................................................•................................................... THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS BEEN INSPECTED AND WASFOUNO TO BE ESSENTIALLY IN ACCORD WITH THE MINIMUM REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT TME TIME OF INSTALLATION EXCEPT AS FOLLOWS. 300-4 300-15-b Romex in npilin+�Emnlira_d with no box. I E location. 210-8-a-1 .: In bathroora opposite vanity, outlets not GFIC protected. 410-4 In shower room, light fixture not approved for damp location. Scott Richter 2/6/96 ELECTRICAL INSPECTOR DATE AR