HomeMy WebLinkAboutREVIEWS - 03-00025 - Cambridge Court Apartments - Two Building 79 Units5/19/2003 Scott Spaulding Design Intelligence 3685 E Hwy. 33 Rexburg, Idaho 83440 Dear Scott, P.O. Box 280 12 North Center Street 7 Rexburg, Idaho 83440 Phone (208) 359-3020 STATE OF IDAHO Fax (208) 359-3022 www.c1.rexburg.Id.us e-mail rexburg@ci.rexburg.1d.us I have finished the review of the Sainsbury Construction Cambridge Court Apartment drawings that you have provided for me and have identified the following discrepancies: 1. The stair enclosures must be open on one side as per the definition of exterior stairway as defined in Section 1002 of the 2000 International Building Code (IBC). The exterior doors of the units must be 20 minute rated doors and assemblies. 2. Be aware that plumbing in party walls can cause many problems with the integrity of fire walls. Plastic pipes can not penetrate the membrane of the 1 - hour firewall unless they are properly constructed to do so. Special fire resistive rings are required or special details that show metal parts entering the membrane and all plastic remaining within the wall. The unit separation walls must be built continuous from the foundation to the roof sheathing. We have details for many different options that I can provide for you if you want to come down to the office. 3. The door into the bathroom on a "Type B" adaptable unit can not open into the space in front of the bathtub. The bathroom that you used to create the existing design has a wall hung sink that allows a wheel chair to move under it. The current configuration will not allow a space large enough so that a person in a wheelchair would have room to close the door. I have attached a drawing to the back of this document that identifies how the door must not swing into the space in front of the tub. 4. "Type A" accessible units are required to have lowered work and sink areas in the kitchens. 5. The footings which were poured previously are not 36" below grade. Please provide a detail showing how the error can be fixed. 6. Bolts were left out for shear walls and bearing walls when the slab was poured. Please identify how to connect these walls. Under some of these walls there is only 4" of concrete. 7. The Fire Department has reviewed the plans. I have attached a copy of there report. Please provide the necessary information they have requested. Please return two sets of revised plans. Let me know if I can be of any further assistance. If you have any questions, please give me a call at 359-3020 east. 324. Sincerely Val Christensen Building Official cc John Millar Chris Huskinson USABLE KITCHENS AND BATHROOMS ■ PART B: USABLE BATHROOMS "B" Bathroom with Bathtub Only 19 inches of the required 30 -inch x 48 -inch clear floor space can go under a lavatory. A deeper lavatory would require that the clear floor space he positioned away from the plumbing wall and closer to the tub, causing it to overlap with the door swing. If a deeper lavatory is desired the room must belengthene' 19" maximum d wallhung lavato with knee spac< :tear floor space for naneuvering outside wing of door i file not required, access improved if door swings t and on.auxiliary door ndle is installed > /?L d,55 A CJAL� rAjT�p .5-/A/ jC SSS grab bars ,......,,.,,.. reinforcing in walls or _ _ min. clear floor space min. clear floor space Legend: floors for g �����, at each fixture ._________J outside swing of door 7.67 USABLE KITCHENS AND BATHROOMS ■ PART B: USABLE BATHROOMS reinforced wall areas for specifically designated future installation of grab bars clear floor space at bath - around toilet and bathtub tub allows greater access to the bathtub and its additional inaccessible _ controls, see page 7.55 receptacle permitted - required in an accessible location lever handles— not required, but recommended fixed base cabinet acceptable since parallel approach centered on basin is possible 30" X 48" clear fl space for parallel approach Example "B" Bathroom Greater Access to Bathtub 6•_10•• X 7'•9" (Similar to Plan on Page 7.67) clear floor space at each fixture required — 30" X 48" min. clear Floor space outside swing of door required Notes in italic type are recommendations only and are not required by the Guidelines. 7.37 L� REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 1997 Uniform Fire Code Plan Date: 7-1-02 Plan Review Review Date: 4-22-03 Building Name: CELESTIAL VILLAGE APARTMENTS Building Address: PORTER ROAD AND CASPER AVENUE Stories: 2.5 Type of Construction: V -i i Occupancy Classification: R-1 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 7200 SQUARE FEET/BUILDING 1).Required Fire Flow (Appendix III -A): 2250 GPM/TWO HOURS Comments: FIRE FLOW MAY BE REDUCED UP TO 50 PERCENT IF BUILDINGS ARE PROVIDED WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: TWO WITHIN COMPLEX Fire Hydrant Flows: UNKNOWN Fire Flow Test Location: N/A Fire Flow Supplied By: NOT SHOWN Other Approved Water Source: NONE Water Supply Acceptable: SEE COMMENTS Fire Hydrant Location Acceptable: SEE COMMENTS Water Supply Comments: PLANS INDICATE TWO HYDRANTS WITHIN COMPLEX. ONE ADDITIONAL HYDRANT IS REQUIRED. FIRE HYDRANTS MUST BE WITHIN 450 FEET OF BUILDINGS. FD REQUESTS HYDRANT FLOW FROM THE ENGINEERS PRIOR TO CONSTRUCTION FOR VERIFICATION. 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: YES Length: YES Surface: YES Turning Radius: Grade: Vehicle Vertical: Clearance: Turn Arounds: Complete Road Acceptable: YES Comments: A MEANS TO TURN AROUND A FIRE APPARTUS IS REQUIRED. 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NEED TO PROVIDE MINIMUM OF 2A10BC EXTINGUISHER PER UNIT. Comments: 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: NO Type Of System Being Installed: Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: NO Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8) Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: NO Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments: 9).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: Both: Type Of System Being Provided: Manual: Automatic: Both: Components Of System Shown: Smoke Detectors: X Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: C Door Holders: Duct Detectors: Flow Alarm: Sprinkler valve Monitoring: Comments: ALL COMMON AREAS SHALL BE EQUIPPED WITH SMOKE DETECTORS INCLUDING LAUNDRY AREA IN ADDITON TO BEDROOMS AND CORRIDORS ADJANCENT TO BEDROOMS. HANDICAPPED AREAS SHALL BE PROVIDED WITH HORN/STROBE UNITS AS PER FIRE CODE AND ADA REQUIREMENTS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: NO Plans As Submitted Are Acceptable: YES, WITH COMMENTS ADDRESSED r Plans Checked By: CHRIS HUSKINSON nares• a-��_nz Please furnish comments back to the plan reviewer in the following manner: Written Comments: New Plans: i OQP�URGiO c° v ° a y 9eCISHED 0/ ,{'I ex lllllr STATE OF IDAHO P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@srv.net REXBURG MADISON COUNTY EMERGENCYSERWICES 26 NORTH CENTER STREET REX9VRG, IDAHO 83440 208-359-3010 208-359-3006 FAX 2000 International Fire Code Plan Date: 4-14-03 Plan Review Review Date: 5-4-03 Building Name: CAMBRIDGE COURT APARTMENTS Building Address: CORNER OF MAIN STREET AND FOURTH WEST Stories: THREE Type of Construction: V -B Occupancy Classification: R-2 Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 57,000 TOTAL SQ. FEET 1. Required Fire Flow (Appendix B): 4,500 GPM/FOUR HOURS Comments: REQUIRED FIRE FLOW MAY BE REDUCE BY 50% WHEN BUILDINGS ARE EQUIPPED WITH AUTOMATIC FIRE SPRINKLER SYSTEMS. (REQUIRED FLOW WOULD BE 2,250 GPM) 2. Water Supply (Section 508, Appendix C) Required: YES Fire Hydrant Location: FOURTH WEST AND MAIN STREET Fire Hydrant Flows: OK Fire Flow Test Location: FOURTH WEST AND MAIN STREET Fire Flow Supplied By: FD Other Approved Water Source: NONE Water Supply Acceptable: NO Fire Hydrant Location Acceptable: SEE COMMENTS Water Supply Comments: PLANS SUBMITTED DO NOT SHOW FIRE HYDRANT ON SITE. A MROMUM OF ONE HYDRANT WILL BE REQUIRED TO BE INSTALLED. 3. Fire Apparatus Access Roads (Section 503, Appendix D) Required: YES Acceptable Width: YES Length: YES Surface: YES Complete Road Acceptable: NO, SEE COMMENTS Comments: BUILDER HAS NOT SUBMITTED PLANS FOR REQUIRED ACCESS TO ENTIRE BUILDINGS. REVIEWER UNSURE IF PROJECT WILL HAVE ADDITIONAL ACCESS OR BE COMPENSATED FOR BY SPRINKLER SYSTEM. 4. Access Roads and Water Supply, including fire hydrants are required to be installed and made serviceable prior to and during time of construction (Section 501): Comments: IF NOT INSTALLED PRIOR TO CONSTRUCTION AND MADE OPERATIONAL, A STOP WORK ORDER WILL BE ISSUED. 5. Installation of portable fire extinguishers (Section 906) Required: YES Location shown: YES Comments: LOCATION OF FIRE Type provided acceptable: YES, 2A-10BC NOT ACCEPTABLE. LOCATION PUTS THEM UNDER CABINETS IN KITCHEN. FIRE EXTINGUISHER MUST HAVE CLEAR AND UN -IMPEDED ACCESS. 6. Automatic fire extinguishing systems (Section 903) Required: YES Type of system being installed: UNKNOWN Sprinkler system monitoring (Section 907) required: YES Comments: SEE SECTION #9. 7. Standpipes (Section 905) required: NO Type required: Comments: 8. Ventilating hood and duct fire extinguisher system (Section 609) required: Type being provided: Automatic fuel shut-off required: Portable fire extinguisher shown: Commbnts: 9. Fire alarm systems (Section 907) required: YES Type of system required: Manual: Automatic: Both: X Type of system being provided: Manual: Automatic: Both: Components of system shown: Smoke Detectors: X Heat Detectors: Manual Pull Station: Sounding Devices: Visual Devices: Door Holders: Duct Detectors: Flow Alarm: Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO, PLANS NOT SUBMITTED FOR ALARM SYSTEM. SUBMITTALS SHALL INCLUDE LOCATIONS OF ALARM_ INITIATINGAND NOTIFICATION APPLIANCES, ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS, MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND MATIERIALS, AND INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS. 10. Other corrections that are required by special occupancy or conditions: SEE ALL PREVIOUS COMMENTS Plans as submitted are acceptable: NO Plans checked by: CHRIS HUSE INSON Date: 5-4-03 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: X MEMO: cify 0/ 5?eMs"ry STATE OF IDAHO TO: TO WHOM IT MAY CONCERN FROM: CHRIS HUSKINSON, FIRE INSPECTOR DATE: MAY 5, 2003 s RE: CAMBRIDGE COURT APARTMENTS TO WHOM IT MAY CONCERN: P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@srv.net Upon review of the site plan drawings submitted the following items need to be addressed: 1. WATER SUPPLY: The proposed hydrant located on the property, in addition to existing hydrants, will suffice for this project as long as it meets the minimum flow requirements of 2,250GPM/two hours and the entire project is fire sprinklered. Additional plans are required to complete an accurate plan review of this project in regard to access, fire alarms, and fire suppression systems. If there are any questions please feel free to contact me. �i Chris Huskinson Fire Inspector