HomeMy WebLinkAboutREVIEWS - 03-00005 - BYUI - Sturdent Health & Counseling Building10/21/2002 edy 012exiar 7 Mike Condie Jensen Haslem Architects 2180 South 1300 East, Suite 300 Salt sake City, UT 84106 Dear Mike, STATE OF IDAHO www,d.rexburg.id.us P.O. Box 280 12 North Center Street Rexburg, Idaho 83440 Phone (208) 359-3020 Fax (208) 359-3022 e-mail rexburg@ci.rexburg.id.us I have reviewed the drawings for the BYU Idaho Student Health and Counseling Center and have identified the following discrepancies: The parking plan includes two handicapped accessible spaces, one with an aisle along side and one without. The ADA guidelines for Accessible Design requires that a 5 foot aisle be included along side each handicapped accessible space. Additionally, the amount of required handicapped spaces (by my calculations) should be 3, not 2. If we identify the number of required parking spaces using the Rexburg Zoning Ordinance requirement of spaces per 1000 sq. ft. of building space, the result is 61 required spaces for the 20296 sq. ft. building. The ADA Standard for Accessible design identifies that 3 handicapped spaces are to be provided. "I feel that these numbers are conservative for a building that will have an occupancy of over 200 people. The waiting area is of a size that will require 2 exits as per Table 1004.2.1 of the 2000 International Building Code (IBC). Exit signs will need to be added to the other entrance(s) that connects to the exit hallway. Please provide cut sheets for all HVAC Units. The Fire Department has reviewed the drawings and I have attached a copy of their report to the back -of this document. Please address their concerns. Please address the above items and return two copies of any changes to me at City Hall. Thank you for your cooperation in this matter. If you have any questions please give me a call at 359-3020 ext. 324. Sincerely, Val Christensen Building Official cc: John Millar Chris Huskinson Rulon Neilsen REXBURG MADISON COUNTY FIRE DEPARTMENT P.O. Box 280 26 North Center Rexburg, Idaho 83440 (208) 359-3010 2000 INTERNATIONAL FIRE CODE Plan Date: 9-20-02 Plan Review Review Date: 10-6-02 Building Name: BYU-I STUDENT HEALTH CENTER Building Address: BYU-I CAMPUS, VIKING DRIVE Stories: TWO Type of Construction: 5-A Occupancy Classification: B Existing Floor Area: N/A New Construction Floor Area: APPROXIMATELY 22,472 SQUARE FEET 1).Required Fire Flow (Appendix III -A): 2750 GPM/TWO HOURS Comments: FIRE FLOW REQUIREMENT SHALL BE 1500 GPM/TWO HOURS AS BUILDING IS EQUIPPED WITH AN AUTOMATIC FIRE SUPPRESSION SYSTEM. 2).Water Supply (Article 9, Section 903) Required: YES Fire Hydrant Location: CLOSEST IS D-38 CENTRAL HIGH SCHOOL AND BYU- I CAMPUS (VIKING DRIVE) Fire Hydrant Flows: OKAY Fire Flow Test Location: SAME AS ABOVE Fire Flow Supplied By: FD AND BYU-I Other Approved Water Source: NONE Water Supply Acceptable: YES Fire Hydrant Location Acceptable: YES Water Supply Comments: NONE 3.)Fire Apparatus Access Roads (Article 9 Section 902) Required: YES Acceptable: Width: X Length: X Surface: X Complete Road Acceptable: YES Comments: NONE 4).Access Roads and Water Supply, Including Fire Hydrants Are Required To Be Installed And Made Serviceable Prior To And During Time Of Construction (Article 9 Section 901.3): YES Comments: IF NOT INSTALLED AND MADE OPERATIONAL PRIOR TO CONSTRUCTION A STOP WORK ORDER WILL BE ISSUED. 5),Installation Of Portable Fire Extinguisher (Article 10 Section 1002) Required: YES Location Acceptable: NOT SHOWN Type Provided Acceptable: NOT SHOWN Comments: MINIMUM SIZE OF 2A10BC REQUIRED WITHIN TRAVEL DISTANCES 6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003 Required: YES Type Of System Being Installed: WET, SUBMIT PLANS TO STATE FIRE MARSHAL Sprinkler System Monitoring Required (Article 10 Section 1003.3) Required: YES Comments: 7).Standpipes (Article 10 Section 1004) Required: NO Type Required: Comments: 8).Ventilating Hood And Duct Fire Extinguishing System (Article 10 Section 1006.2) Required: NO Type Being Provided: Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4): Portable Fire Extinguisher Shown (Article 10 section 1006.2.7): Comments: 9).Fire Alarm Systems (Article 10 Section 1007)Required: YES Type Of System Required: Manual: Automatic: Both: X Type Of System Being Provided: Manual: Automatic: Both: X Components Of System Shown: Smoke Detectors: X Heat Detectors: X Manual Pull Station: X Sounding Devices: X Visual Devices: X Door Holders: Duct Detectors: Flow Alarm: X Sprinkler Valve Monitoring: X Fire Alarm System Acceptable: SEE COMMENTS. 10).Other Corrections That Are Required By Special Occupancy Or Conditions: SEE COMMENTS Comments: PLEASE PROVIDE THE FOLLOWING IN REGARDS TO THE ALARM SYSTEM: ALARM CONTROL AND SIGNALLING EQUIPMENT, ANNUNCIATION, POWER CONNECTION, BATTERY CALCULATIONS, CONDUCTOR TYPE AND SIZES, VOLTAGE DROP CALCULATIONS, MANUFACTURERS, MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES AND MATERIALS, AND THE INTERFACE FOR SAFETY CONTROL FUNCTIONS. SEE BELOW FOR MISSING HORN/STROBES, PULL STATIONS, ETC. THAT NEED TO BE ADDED TO SYSTEM. ARE MAGNETIC DOOR HOLDERS GOING TO BE USED THROUGHOUT THE BUILDING? IF S0, PLEASE ADDRESS. Plans As Submitted Are Acceptable: NO, PLEASE ADDRESS NOTED ITEMS Plans Checked By: CHRIS HUSRINSON Date: 10-6-02 Please furnish comments back to the plan reviewer in the following manner: Written Comments: X New Plans: X ALARM SYSTEM ITEMS• FIRST FLOOR: 1. ADD PULL STATION AT REAR GARAGE DOOR EXIT 2. ADD HORN/STOBE UNIT IN ROOMS 136, 131, 134, 164, 172, AND 116. 3. MOVE HORN/STROBE IN ROOM 179 TO MORE CENTRAL LOCATION. 4. ADD HORN STROBE UNITS IN CORRIDOR 126. SECOND FLOOR: 1. ADD HORN/STROBE UNIT IN ROOM 282.