I have reviewed the plans for Brighton Apartments and have identified the following
discrepancies:
1. Provide road construction details as per the City of Rexburg Standard
Specifications.
2. Get with John Millar and obtain a Development Agreement with the City of
Rexburg.
3. Finish the Plot Plan outside the property boundaries. Include dimensions,
landscaping, curb/gutter, driveway approach, sidewalk size and location. Include
details to identify all concrete in the approach as 6" reinforced over gravel as per
City of Rexburg Standard Specifications.
4. Provide storm calculations for retention area.
5. Identify dumpster location and screening.
6. Show fencing or suitable buffer between parking area and the property to the
South.
7. Manager's unit must be accessible and can't be located on the second floor.
8. Maintain 2 -hour firewall assembly between units from foundation to bottom of
roof sheathing.
9. Terminate area separation walls as per the 1997 Uniform Building Code (UBC)
Section 504.6.3.
10. One ground floor unit must be constructed as -a Type "A" handicap accessible unit.
Provide grab bar details, cabinet details and fixture descriptions. Include horn
strobes as per the Fire Department request.
11. Identify handicap details for grab bars and fixtures in the bathroom located in
recreation room.
12. Provide fire extinguishers as per the Fire Departments request. I have attached a
copy of the Fire Department review to the back of this document.
Please make the above changes and return two complete sets of plans to me. If you have
any questions, I can be reached during the day at 359-3020 Ext. 324.
Sincerely,
.0
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date:2-7-01
Plan Review Review Date:3-25-02
Building Name: BRIGHTON APARTMENTS
Building Address: SECOND WEST AND SIXTH SOUTH
Stories: TWO Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: 12,792 SQ. FEET
1).Required Fire Flow (Appendix III -A): 3,000 GPM/THREE HOURS
Comments: A REDUCTION OF FIRE FLOW IS ALLOWED UP TO 75% IF AN
APPROVED AUTOMATIC SPRINKLER SYSTEM IS INSTALLED.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: C-62, C-63, C-81
Fire Hydrant Flows: OKAY
Fire Flow Test Location: SAME AS ABOVE
Fire Flow Supplied By: FD
Other Approved Water Source: NO
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: YES
Water Supply Comments:
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: OKAY Length: OKAY Surface: OKAY
Turning Radius: OKAY Grade: OKAY
Clearance: OKAY Turn Arounds: N/A
Complete Road Acceptable: YES
Comments:
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made. Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: HYDRANTS AND ACCESS MUST BE PROVIDED PRIOR TO AND DURING
CONSTRUCTION OR A STOP WORK ORDER WILL BE ISSUED.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: MINIMUM OF ONE 2A10BC FIRE EXTINGUISHER
REQUIRED IN EACH UNIT.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required: Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: NO
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments:
9).Fire Alarm Systems (Article 10 Section 1007)Required: NO
Type Of System Required: Manual: Automatic: Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System Shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable:
0
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: AS NOTED ABOVE
Plans As Submitted Are Acceptable: YES
Plans Checked By: CHRIS HUSKINSON Date: 3-25-02
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: New Plans: