I have reviewed the plans for the Breckenridge apartments and have identified the
following discrepancies:
1. Provide handicap ramp at corner of I" West and 2nd South.
2. Screen the garbage dumpster and place in an area where a side -loading truck can
access it.
3. Provide 28' radius for fire truck at South entrance. Also create wider driveway by
eliminating the sidewalk on the South side of the building in the Southeast corner
of the project.
4. Provide fire hydrant as per Rexburg Fire Department.
5. Sidewalk and driveway at street approaches will need to be constructed of 6"
reinforced concrete.
6. Provide details of handicap ramp.
7. Provide sprinkler plan.
8. Show the fire sprinkler system mechanical room inside of the building. It can not
be in a setback.
9. Provide draftstop details.
10. Provide floor details for 1-hr.fire resistance.
11. Identify smoke detectors.
12. Provide door details.
13. Provide mechanical information.
14. Provide electrical plan.
15. Provide detail showing pipe penetrations into firewalls.
16. Provide Type "A" Accessible Unit. Provide details such as grab bar, cabinet,
toilet, sink, shower, etc.
17. Address any items identified by the Fire Department. I have attached a copy of
their review to the back of this document.
Please make the necessary corrections and return two sets of drawings as soon as possible.
If you have any questions please give me a call at 359-3020 ext. 314.
Sincerely,
Val Christensen
Assistant Engineer
cc: John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 02-01
Plan Review Review Date: 06-05-01
Building Name: Breckenridge Apartments
Building Address: Corner of First West and Second South
Stories: 3 Type of Construction: V-1
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: @ 13,535 square feet
1).Required Fire Flow (Appendix III -A): 1,500 GPM
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: C18, C25
Fire Hydrant Flows: OK
Fire Flow Test Location: C18, C25
Fire Flow Supplied By: FD
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: Existing OK, provide one hydrant
on site
Water Supply Comments: Need to add one hydrant on site to comply
with UFC. Best location would be on the sidewalk near the south end
of proposed building (Between new and old structures).
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: NO
Turning Radius: NO
Clearance: U/K
Length: NO Surface: OK
Grade: OK Vehicle Vertical:U/K
Turn Arounds: NONE
Complete Road Acceptable: NO
Comments: Corners in parking lot need to have minimum of 28 foot
radius (around parking stalls) and the southwest stall at rear of
managers building. There shall be no parking (Signed and marked
with paint) along the sidewalk on the east side of new building to
allow for fire apparatus access. Existing driveway to the south of
proposed manager's building too narrow. Needs to be a minimum of 20
feet wide with no parking (Signed and marked with paint). Parking
along southern edge of property doesn't allow fire apparatus to
fully access old building.
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES
Location Acceptable: Not Shown
Type Provided Acceptable: Minimum of 2A-10BC required
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: YES Type Of System Being Installed: Unknown
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required: U/K Comments: Have not been provided with
sprinkler plans.
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: Automatic: Both: YES
Type Of System Being Provided: Manual: Automatic: Unknown what
type of system to be provided, no plans submitted.
Components Of System Shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: NO
Plans Checked By: Chris Huskinson
Date: 6-05-01
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES
ugG
'0/�/�,o, P.o. Box 280
YS
edy 01ea�°�(//ary 12 North Center Street
Rexburg, Idaho 93440
Phone (209) 359-3020
STATE OF IDAHO Fax (209) 359-3022
e<IsHF www.c1.rexburg.id.us e-mail rexburg®ci,rexburg.id.us
8/20/2001
Scott Spaulding
Design Intelligence
135 East Main
Rexburg, Idaho 83440
Dear Scott,
On 8/17/01,1 completed framing inspection on the Erickson Pontiac Building.
Below is a list of items that I have identified as incomplete, incorrect or unexplained:
1. The front wall and the side.walls of the show room were not engineered
for seismic or wind loads. Please provide details and calculations.
2. The boiler room has been moved to the mezzanine area. A beam is
carrying part of the load from the boiler room floor. This beam transmits
its load to the walls below. The walls transfer the load to the floor slab
that has not been designed for this purpose. Please provide me with the
calculations showing that the unreinforced slab will be adequate to support
the loads from the newly created bearing wall and especially the point load
generated from the column carrying the end of the beam.
3. The original plans call out for the interior wood framed walls to be sheeted
with 5/8" o.s.b. for shear purposes. It has come to my understanding that
the contractor wants to substitute angle bracing in place of the o.s.b.
panels. Please provide me with details and calculations required to make
the change.
4. We had requested a fist and the times of the special inspections required as
per the 1997 Uniform Building Code (UBC) Section 1701.5. Concrete,
Bolting and Field Welding all require special inspections. At this time we
have not received any information concerning these inspections.
5. I am a little concerned about the headroom in the mezzanine area. The
fire sprinkler pipe is at "head banging" level on one side and a steel beam
in the boiler room is definitely a safety concern for the same reason.
Please make some provisions for clearly identifying these potential safety
concerns.
Please let me know if there will be any problems making the above changes. If
you have any questions, please give me a call at 359-3020 ext. 324.
Sincerely,.
G ��
Val Christensen
Assistant Engineer