HomeMy WebLinkAboutAPPLEWOOD APTS FRIRE INSPECTION - 03-00021 - American Manor Apartments - RemodelREXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
,T1IIS IS TO GIVE NOTICE THAT:
An inspection of the Applewood Apartments located at 151 South 1st
East in Rexburg, Idaho was conducted on this date and that as
nearly as could be determined, was found to be in compliance with
the Uniform Fire Code and ordinances of the City of Rexburg that
are presently in effect, with the following exceptions:
Sec. 901.4.4 Post address on the front of the building,
wrong areas. The at
correct the problem.
occupants.
Sec. 1107.1 The venting from gas appliances needs to be checked.
Some pipes were dented and some pulled loose with screws missing.
of ,.
tha
egress window. Some balconies_ only hate one_ way off_
Sec_ 1103.3.2.1 Storage shall be orderlyin storage areas. Ceneral
housecleaning needs to be done in these areas.
Sec._ 1103.3.2.4 Combustible materials ,..shall -_not bestured in boiler
rooms, mechanical rooms or electrical equipinent. rooms.
Note: This inspection was necessarily limited to items and areae in plain and full view of the
inspector. This inspection cannot ensure or verify the compliance of the items or areas that are
obstructed from the inspector's view by construction or access. The City of Rexburg can accept no
responsibility for verification of code compliance in such areas. Such verification becomes the sole
responsibility and liability of the property owner. Persons preforming corrective action should
contact the Rexburg Madison County Fire Department at (20a) 359-3010 for specifics or questions
regarding these regriremetts. Any observable deficiencies which are a distinct hazard to life and/or
property are subject to criminal enforcement if they are not remedied immediately.
February 2, 1996
Dee Owens Date
Fire Inspector
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
Fire Extinguishers Inspection and Maintenance
Fire extinguishers require an inspection ever_ 30 days. If
circumstances require it may need to be more frequent.
Inspection shall include at least the following items: (a)
Located in designated place. (b) No obstruction to access or
visibility. (c) Operating instructions on nameplate legible and
facing outward. (d) Seals and tamper indicators not broken or
missing. (e) Determine fullness by weighing or "hefting." (f)
Examine for obvious physical damage, corrosion, leakage, or
clogged nozzle. (g) Pressure gage reading or indicator in the
operable range or position. Any problems need to be corrected
immediately or a replacement extinguisher provided until it can
be.
Fire extinguishers require maintenance not more than _one Year
apart. Maintenance shall include a through examination of the
three basic elements of an extinguisher: (a) Mechanical parts,
(b) extinguishing agent, and (c) expelling means. Stored
pressure extinguishers require a hydrostatic test every 12 years
and need to be emptied every six years and subjected to
maintenance procedures.
The owner could preform the inspection procedure with proper
training.
I would recommend that you have an outside source preform the
maintenance of your extinguishers.
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
Smoke Detectors and Locations
Smoke detectors shall be installed in accordance with the
approved manufacture's instructions. The 1994 UBC states in Sec.
310.9.1.4 Location within dwelling units. In dwelling units, a
detector shall be installed in each sleeping room and at a point
centrally located in the corridor or area giving access to each
;,separate sleeping area. When the dwelling unit has more than one
story and in the dwellings with basements, a detector shall be
'installed on each story and in the basement. In dwelling units
where a story or basement is split into two or more levels, the
smoke detector shall be installed on the upper level, except that
when the lower level contains the sleeping area, a detector shall
be installed on each level. When sleeping rooms are on an upper
level, the detector shall be placed at the ceiling of the upper
level in close proximity to the stairway. In dwelling units
where the ceiling height of a room open to the hallway serving
the bedrooms exceeds that of the hallway by 24 inches or more,
smoke detectors shall be installed in the hallway and in the
adjacent room. Detectors shall sound an alarm audible in all
sleeping areas of the dwelling unit in which they are located.
Some of your smoke detectors are very poorly located, I would
recommend that you relocate them using the UBC section to provide
better warning. Avoid the dead air spaces that we discussed (six
inches.down or out). The smoke detectors need to be tested at
least monthly. You should use a test smoke and not just the test
button. Batteries need to be replaced yearly.
I realize that the smoke detectors were not required in the
sleeping rooms at the time of construction but would recommend
that you install them if possible.
CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS
February 20, 1996
Joe Laird, PE
City of Rexburg Building Official
PO Box 280
Rexburg, ID 83440
RE: Stephen Clark Development - Board of Appeals Recommendations
Dear Joe:
.,.sVeb-96W,d2-2.20
Under separate cover we gave formal response to Mr. Clark's appeal of your building inspections
on the subject property. As a related action to that appeal, we members of the Board of Appeals
desire to convey to the City some additional concerns and recommendations we have concerning
the subject property and our function as a review board:
1) We were able to tour the facilities at the express invitation of Mr. Clark. Based on our
observations, it is strongly felt by Board members that the manner and workmanship of
construction is not at all representative of what we feel should be the community standard
for building practices.
2) As a result of the inspection, we are concerned that there may be further issues with
regard to the building codes, particularly in the area of structural aspects.
3) We concur with the building official's determination that the newest structure (Building 1A)
is indeed a three-story structure. However, Mr. Clark claims that at the time the building
was proposed the City Council made the determination that it was a two-story structure
with a basement which, as coming from the highest building authority in Rexburg, may
constitute a waiver of code requirements by definition. We request clarification from the
City with regard to this matter.
4) We strongly recommend the Owner(s) hire their own professionals (structural engineers,
mechanical engineers, electrical engineers, architects, etc.) to review all buildings and all
construction with respect to the Code and that reports of their inspections or recommen-
dations be filed with the City. We recommend that any further consideration of the
Certificate of Occupancy be wholly conditional on this recommendation as a minimum.
5) We are struggling with the definition of our responsibilities with respect to duties of the
Appeals Board and the Code, and also with respect to providing recommendations and
suggestions to the City and Building Official. In short, how far can or should be go in
response to appeals made? We would appreciate the opportunity to meet with you, the
Mayor, and the City Attorney to help clarify these concerns.
Joe Laird, PE
February 20, 1996
Page 2
We are appreciative of the opportunity to provide community service and trust that our efforts are
in accordance with the City's vision of our function and that our input is helpful. We would
appreciate your consideration of the foregoing and look forward to receiving clarification of our
duties and responsibilities in order for us to more effectively serve you.
Sincerely,
CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS
Charles Cartmill
Winston Dyer
Ted Hill
Bart Stevens
John Watson
II IJ Lit,- If, ILIE 14: 'Jo IL: ILL Nu: IIIA=1 I -'N_;
PHILIP E. BATT"
u,,.on"
,Stare of Idaho
DEPARTMFNT OF LABOR AND INDUSTRIAL ,SERVICFS
POCAfELLO AREA OFFICE
February 6, 1996
Stephen E. Clark
625 S. 5000 W.
Rexburg, ID 83440
Dear Mr. Clark:
611 Wllaon, SUlla 4C
P.O. BOX 4963
Pocatello. ID a320rr4963
(206) 236-6060 FAX (206) 236-6221
After reviewing and inspecting the apartments located at 151 S. First F. in Rexburg, I found that a
good portion of the electrical installation was inadequate and in poor workmanship. I was only
able to see the finished product and have no idea of what lies behind the walls. In any case, the
requested inspections indicate a large amount of redundancy and repeat violations (please gee
enclosed findings).
If I can he of further assistance, please feel free to contact me at (208) 359-3025.
Sincerely,
Scott Richter
Electrical Inspector
rlm
Enclosures
c: Terry L. Coumerilh
Equal Opportunity Employer
TO: EIE'd-�;F�iJRG
FED -06-'9E. TUE 14:54 Ill: TEL NO: U136 P01
Ef.411 STATE OF IDAHO
2/20/92R DEPARTMENT O)LABOR ANO INDUSTRIAL SERVICES
ELECTRICAL DIVISION
277 NORTH SIXTH - STATEHOUSE MAIL
BOISE, 10 83720.6000
(208) 314.21133
NAME: Stephen E. Clark
ADDRESS! 625 S. 5000 W.
Rexburg, ID 83440
PERMIT NUMBER:
REDUESTED INSPECTION FINBINOS
APPLICANT;
NAME, Stephen E. Clark
ADDRESS: 625 S. 5000 W.
Rexburg, ID 83440
TYPE OF BUILDING: Student Apartments
LocAT1oN OF BUILDING: 151 S. First E. , Rexburg, ID 83440
.............................................................................................................................
THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS BEEN INSPECTED AND WAS FOUND TO BE ESSENTIALLY IN ACCORD WITH THE MINIMUM
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT (HE TIME OF INSTALLATION EXCEPT AS FOLLOWS:
._�.0 f{EFENENCE _! FINOIN •;__
L ndry Room
336-]0-b jam.
Addition
1
Scott Richter
ELECTRICAL INSPECTOR
Ea
not secured along framing members
e
2/6/96
DATe -�
TCS : REXBLIRG
--- --------f Eli-bf,-'S6 EIJE 11:51 Ili: TEL NO: .—H135 Pol
EF -411 STATE OF IDAHO
2120/92R DEPARTMENT Of LABOR AND INDUSTRIAL SERVICES
ELECTRICAL DIvIs10N
277 NORTH SIXTH - STATEHOUSE MAIL
BOISE, ID 8372D-6000
(208) 314.2187
NAME: Stephen E. Clark
Ammaess:625 S. 5000 W.
Rexburg, ID 83440
PERMIT NUMBER:
REDUE$TED INSPECTION FINDINGS
&PLT CANT:
NAME: Stephen E. Clark
ADDRESS1625 S. 5000 W.
egg ;
TYPE OFBUILDINO: Student Apartment-
LOCATION
l ar men
LOCATION OF BUILDING: y s1 S. Flrst F RexburE ID 83440
..............................................................................................................................
THE ELECTRICAL INSTALLATION DESCRIBED ASOvE FAS SEEN INSPECTED AND WAS FOUND TO BE ESSENTIALLY IN ACCORD WITH TMt MINIMUM
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME Of INSTALLATION EACEPT AS 70LLOv6:
NEC REfERENCE rINO IW
Laundry Room Surface mounted fluorescent fixture over dryer #4 hanging on
41�.-15-a I on one side not secured to ceiling.
370-25 ' 1 Behind dryer #15 and washer #8 outlet has no cover plate.
300-4 j In unfinished_ bathroom romex and ceiling box hanging from
-.Lo-n. I ouriace mounteu iluorescent fixtures not grounded
Scott Richter 2/6/96
ELECTRICAL INSPECTOR DALE
A■
I I. i; - lc, • jb WE 14:4`.) I D: "FEL NO:-
q133 F'6.
EF -41 I STATE OF IDAHO
2/20/92R DEPARTMENT OF LABOR AND INDUSTRIAL SERVICES
ELECTA(CAL DIvISIDN
277 NORTH SIXTH - STATEHEIUSE MAIL
BOISE, 10 83720-6000
(208) 334.2183
REQUESTED INSPECTION FINDINGSEUUt
iT , APPL(CANT-
NANE; Stephen E. Clark NAME, Stephen E. Clark
ADDRESS:
Rexburg, ID 83440
PERMIT NUMBER,
ADDRESS:625 S. 5000 W.
Rexburg, ID 83440
TYPE OF 8UILOINC:tit11jjent ADA tMe1C
ts
L-OCA7IDNOF8UILOIN0:_j5L S. First F. Rexburg.—ID 83440
...wrv..ru..rvvrtrfroA........A. vv....... ............. ur. I..... ............. r v..............................
THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS BEEN INSPECTED AND WAS FOUND TO BE ESSENT(ALLT IN ACCORD WITH THE MINIMUM
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSTALLATION EXCEPT AS FOLLOW5:
DREFEgElcrFIND 5
Unit 114
410-4 In shower room light fixture not approved for damp locations.
Scott Richter
ELECTRICAL INSPECTOR
Its
in natnroom o os t outlets not GFIC protected.
oved for damp location.
2/6/96
DATE
FED -06—'96 TUE 14:56 ID: TEL NO; H136 P03
EF -411 STATE OF IDAHO
2/20/92A DEPARTMENT OF L.AROR AMD INDUSTRIAL SERVICES
ELECTRICAL DIVISION
277 NORTH SIXTH - STATEHOUSE MAIL
BOISE, ID 83720.6000
12081 334.2183
PROPERTY OWNER:
NAME: Stephen E. Clark
ADaNEss: 625 S. 5000 W.
Rexburg, ID 83440
PERMIT NUMBER:
REOUESTED IMSPECtIQN FINDINGS
APPLICANT:
NAME: Stephen E. Clark
AwREss: 625 S. 5000 W•
Rexburg,
TTPEOPBUILDING: Student Apartments
LOCATION OF BUILDINOc 151 S. First E., Rexburg, ID 83440
.............1.it....f.atf....Y.........................,....,.....I...,.......*............... ............. .................
THE ELECTRICAL INSTALLATION DESCRIBED ABOVE WAS BEEN INSPECTED AND WAS FOUND TO BE ESSENTIALLY IN ACCORD WITH THE MINIMUM
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSTALLATION EXCEPT AS FOLLOWS:
NEC REFERENCE FINDINGS
In panel there are open splices not closed.
210 -8 -LF In bathroom opposite vanity, outlets not GFIC protected.
41.0-4 j In shower room, light fixture not approved for damp location.
1
,Scott Richter
ELECTRICAL INSPECTOR
k.
'16/96
DATE
FED -06-'96 TUE 14:52 Ill: TEL NO: 0135 F'O2
EF0 STATE OF IDAHO
2/20/99 2R DEPARTMENT OF LABOR AND INDUSTRIAL SERVICES
ELECTRICAL DIVISION
277 NORTn SIxTH • .SIAIEHOUSE MAIL
BOISE, ID 83720.6000
(208) 334.2183
REOUESTEO kEEC110N FINDINGS !%
PROPERTT OWNER:
APPLICANT:
NAME: Stephen E. Clark NAME: Stephen E. Clark
ADDRESS: R .5 5000 W.
Rexburg, ID 83440
PERMIT NUMBER•
ADDRE5SF25 S, 5000 W,
Rexburg, ID 83440
TYPE OF BUILDING: Student Apartments
LOCATION OF BUILDING: 151 S. First E., Itexburg, ID 83440
..........n..................................................................
..........................................
THE ELECTRICAL INSTALLATION DESCRIIILD ABOVE HAS BEEN INSPECTED AND VAS FOUND TO DE ESSENTIALLY IN ACCORD WITH THE MINIMUM
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME OF INSIALLATION EXCEPT AS FOLLOWS:
-In shower r!2!2nl lightfixture. not approved for dam locaiion,
:
-a-x->_ ' y----'- o,)osite vanit are not GFIC
protected in bathroom
1
90-4 In living room ceiling fixture flickers.
Scott Richter
ELECTRICAL INSPECTOR
ka
2/6/96
DATE
net
I -Ell 06-'9F TUE 14:56 1[i:
TEL N0:
EP -4)1 STATE Of IDAHO
2/20/928 DEPARIMENT OF LAUOR AND INDUSTRIAL SERVICES
ELECTRICAL DIVISIoN
277 NORTH SIXTH - STATEHOUSE MAIL
BOISE, ID 83720-6000
(208) SSL -2183
NAME: Stephen E. Clark
ADDRESS: 625 S. 5000 W.
Rexburg, ID 53440
PERMIT NUMBEk:
REOUESiED INSPECTION FINDINGS
APPLICANT;
NAME: Stephen S. Clark
4136 604
ADDRESS: 625 S. 5000 W,
Rexburg, ID '83440
TYPE OF BUILDING:Student Apartments
LOCATION OF BUILDING: 151 S. First E., Rexburg, ID 83440
..............e............................................................•..................................................
THE ELECTRICAL INSTALLATION DESCRIBED ABOVE HAS BEEN INSPECTED AND WAS FOUND TO BE ESSENTIALLY IN ACCORD WITH THE MINIMUM
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AT THE TIME Of INSTALLATION EXCEPT AS FOLLOWS:
r
3$Rnmox rimn-ng alone wdllg and ceiliniz Sur.iaces. _�
300-4
2
tlets
336-15 Oven romex not nr staoled.
300-15-b Hornox in cellincr np1jt,.PA with no box,
Unit 112 ;
210-8-a-1 In bathroom onno,ite manity nnriers not FFTr, prnt + .i
410-4 ; In shower room, light fixture not approved for damp location.
Scott Richter
ELECTRICAL INSPECTOR
Ye
2/6/96
DATE
CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS
February 20, 1996
Mr. Stephen Clark, et al.
625 S 5000 W
Rexburg, ID 83440
RE: Building Inspection Appeal for Applewood Apartments
Dear Mr. Clark, et al.:
96-999
W11esUeb-8(Va1rd2.20
The Uniform Building Code Board of Appeals, duly established by action of the Rexburg City
Council, has met to consider your appeal over the Building Inspection Report of the Applewood
Apartment located at 151 S 1st E in Rexburg.
We have considered the Building Inspector's reports of February 9, 1996 for buildings 1A, 1B,
iC, 2, 3, and 4 in accordance with our authority as we understand it from the Code and have
made the following determinations:
1) The Building Official's reports appear to be in compliance with applicable provisions of the
Uniform Building Code and the inspections were not completed in an arbitrary nor
capricious manner.
2) Previous actions by the Building Inspector(s), the Inspection process, the issuance of
permits, and the issuance of a certificate of occupancy do not absolve the building
owner(s) of the responsibilities to meet all applicable provisions of the Code. Specifically,
Section 307(f) gives specific authority to suspend or revoke a certificate of occupancy
issued under the provision of the Code whenever '...it is determined that the building or
structure, orporlion thereof, is in violation of any ordinance orregulation oranyprovisions
of this (UBC) code".
If further information is required, please advise.
Sincerely,
CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS
Charles Cartmill
Ted Hill
John Watson
cc: City of Rexburg
Winston Dyer
Bart Stevens
14
T
23-A UNIFORM BUILDING CODE
TABLE NO.23-A—UNIFORM AND CONCENTRATPn I nano
USE OR OCCUPANCY
CATEGORY DESCRIPTION
UNIFORM
LOADI
CONCEN.
TRAINED
LOAD
I. Access fluor systems
Office use
50
20002
Computer use
100
20002
2. Armories
150
0
3. Assembly areas) and
auditoriums and
balconies therewith
Fixed scaling arens
50
0
Movable scaling and
other areas
100
0
Stage areas and
enclosed platforms
125
0
4. Cornices, marquees and
residential balconies
60
0
5. Exit facililicsb
100
0$
6. Garages
General storage and/or repair
100
6
Private or pleasure -type
motor vehicle slot age
50
6
7. hospitals
Wards and rooms
40
10002
8. Libraries
Reading rooms
60
10002
Stack rooms
125
15002
9. Manufacturing
Light
75
20002
I lcnvy
125
30002
10. Offices
50
20002
11. Printing plants
Press rooms
150
25002
Composing and linty pe rooms
100
20002
12. Residential'
40
05
13. Rest rooms$
14. Reviewing stands,
grandstands and
bleachers
100
0
15. Roof deck
Same as arca served or for the
type of occupancy
accommodated
16. Schools
Classrooms
40
10002
17. Sidewalks and
driveways
Public access
250
6
18. Storage
Light
125
Ileavy
250
19. Stores
Retail
75
20002
Wholesale
100
30002
1985 EDITION
23-A
ISee Section 2306 for live load reductions.
2See Section 2304 (c), first paragraph, for area of load application.
$Assembly areas include such occupancies as dance halls, drill rooms, gymnasiums, playgrounds,
plazas, terraces and similar occupancies which are generally accessible to the public.
^Exit facilities shall include such uses as corridors serving an occupant load of 10 or more persons,
exterior exit balconies, stairways, fire escapes and similar uses.
slndividual stair treads shall be designed to support a 300 -pound concentrated load placed in a position
which would cause maximum stress. Stair stringers may be designed for the uniform load set forth in
the table.
$See Section 2304(c), second paragraph, for concentrated loads.
)Residential occupancies include private dwellings, apartments and hotel guest rooms.
$Rest room loads shall be not less !hall the load for the occupancy with which they are associated, but need
not exceed 50 pounds per square foot.
104 UNIFORM BUILDING CODE
structure to become structurally unsafe or overloaded; will not provide adequate
egress in compliance with the provisions of this code or will obstruct existing
exits; will create a fire hazard; will reduce required fire resistance or will other-
wise create conditions dangerous to human life. Any building so altered, which
involves a change in use or occupancy, shall not exceed the height, number of
stories and area permitted for new buildings. Any building plus new additions
shall not exceed the height, number of stories and area specified for new build-
ings. Additions or alterations shall not be made to an existing building or structure
when such existing building or structure is not in full compliance with the
provisions of this code except when such addition or alteration will result in the
existing building or structure being no more hazardous based on life safety, fire
safety and sanitation, than before such additions or alterations are undertaken.
[See also Section 911 (c) for Group H, Division 6 Occupancies.]
Alterations or repairs to an existing building or structure which are nonstruc-
tural and do not adversely affect any structural member or any part of the building
or structure having required fire resistance may be made with the same materials
of which the building or structure is constructed. The installation or replacement
of glass shall be as required for new installations.
(c) Existing Installations. Buildings in existence at the time of the adoption of
this code may have their existing use or occupancy continued, if such use or
occupancy was legal at the time of the adoption of this code, provided such
continued use is not dangerous to life.
Any change in the use or occupancy of any existing building or structure shall
comply with the provisions of Sections 307 and 502 of this code.
For existing buildings, see Appendix Chapter 1.
(d) Maintenance. All buildings and structures, both existing and new, and all
parts thereof, shall be maintained in a safe and sanitary condition. All devices or
safeguards which are required by this code shall be maintained in conformance
with the code edition under which installed. The owner or his designated agent
shall be responsible for the maintenance of buildings and structures. To determine
compliance with this subsection, the building official may cause any structure to
be reinspected.
(e) Moved Buildings and Temporary Buildings. Buildings or structures
moved into or within the jurisdiction shall comply with the provisions of this code
for new buildings or structures.
Temporary structures such as reviewing stands and other miscellaneous struc-
tures, sheds, canopies or fences used for the protection of the public around and in
conjunction with construction work may be erected by special permit from the
building official for a limited period of time. Such buildings or structures need not
comply with the type of construction or fire -resistive time periods required by this
code. Temporary buildings or strictures shall be completely removed upon the
expiration of the time limit stated in the permit.
(f) Historic Buildings. Repairs, alterations and additions necessary for the
preservation, restoration, rehabilitation or continued use of a building or structure
may be made without conformance to all the requirements of this code when
authorized by the building official, provided:
302.4-303.1.1 1994 UNIFORM BUILDING CODE
may be further reduced to one hour where the area of such Group S, Division 3 Occupancy does not exceed
3,000 square feel (279 m).
3. In the one-hour occupancy separation between Group R, Div ision 3 and Group U Occupancies, the sepa-
ration may be limited to the installation of materials approved for one-hour fire -resistive construction on the
garage side and it self-closing, tight -fitting solid -wood door 11/8 inches (35 mm) in thickness, ora self-closing,
tighl-fitting door having a fire -protection rating of not less than 20 minutes when tested in accordance with
Part 11 of U.B.C. Standard 7-2, which is a part of this code, is permitted in lieu of a one-hour fire assembly.
Fire dampers need not be installed in air ducts passing through the wall, floor or ceiling separating a Group
R, Division 3 Occupancy from a Group U Occupancy, provided such duels within the Group U Occupancy
are constructed of steel having a thickness not less than 0.019 inch (0.48 mm) (No. 26 galvanized sheet gage)
and have no openings into the Group U Occupancy.
4. Group H, Division 2 and Group H, Division 3 Occupancies need not be separated from Group H, Divi-
sion 7 Occupancies when such occupancies also comply with the requirements fora Group H, Division 7 Oc-
cupancy.
302.5 Heating Equipment Room Occupancy Separation. In Groups A; B; E; F; I; M; R, Divi-
sion 1; and S Occupancies, rooms containing a boiler, central heating plant or hot-water supply boil-
er shall be separated from the rest of the building by not less than a one-hour occupancy separation.
EXCEPTIONS: I. In Groups A, B, E, F,1, M and S Occupancies, boilers, central healing plants or hot-
water supply boilers where the largest piece of fuel equipment does not exceed 400,000 Btu per hour (1117.2
kw) input.
2. In Group R, Division I Occupancies, a separation need not be provided for such rooms will] equipment
serving only one dwelling unit.
In Group E Occupancies, when the opening for a heater or equipment room is protected by a pair
of fire doors, the inactive leaf shall be normally secured in the closed position and shall be openable
only by the use of a tool. An astragal shall be provided and the active leaf shall be self-closing.
In Group H Occupancies, rooms containing a boiler, central heating plant or hot-water supply
boiler shall be separated from the rest of the building by not less than a two-hour occupancy separa-
tion. In Divisions I and 2, there shall be no openings in such occupancy separation except for neces-
sary ducts and piping.
For opening in exterior walls of equipment rooms in Groups A, E or I Occupancies, see Section
303.8.
302.6 Water Closet Room Separation. A room in which a water closet is located shall be sepa-
rated from food preparation or storage rooms by a tight -fitting door.
SECTION 303 — REQUIREMENTS FOR GROUP A OCCUPANCIES
303.1 General.
303.1.1 Group A Occupancies defined. Group A Occupancies include the use of a building or
structure, or a portion thereof, for the gathering together of 50 or more persons for purposes such as
civic, social or religious functions, recreation, education or instruction, food or drink consumption,
or awaiting transportation. A room or space used for assembly purposes by less than 50 persons and
accessory to another occupancy shall be included as it part of that major occupancy. Assembly occu-
pancies shall include the following:
Division 1. A building or portion of a building having an assembly room with an occupant load of
1,000 or more and a legitimate stage.
Division 2. A building or portion of a building having an assembly room with an occupant load of
less than 1,000 and a legitimate stage.
Division 2.1. A building or portion of a building having an assembly room with an occupant load
of 300 or more without a legitimate stage, including such buildings used for educational purposes
and not classed as Group B or E Occupancies.
Division 3. A building or portion of a building having an assembly room with an occupant load of 1
less than 300 without a legitimate stage, including such buildings used for educational purposes and
not classed as Group B or E Occupancies.
1-26
011IN1U1[1
1994 UNIFORM BUILDING CODE
SECTION 310 — REQUIREMENTS FOR GROUP R OCCUPANCIES
310.1 Group R Occupancies Defined. Group R Occupancies shall be:
Division 1. hotels and apartment houses.
Congregate residences (each accommodating more than 10 persons).
Division 2. Not used.
Division 3. Dwellings and lodging houses.
Congregate residences (each accommodating 10 persons or less).
For occupancy separations, see Table 3-13.
A complete code for construction of detached one- and two-family dwellings is in Appendix
Chapler 3, Division III, of this code. When adopted, as set forth in Section 101.3, it will take prece-
dence over the other requirements set forth in Chapter 35 of this code.
310.2 Construction, Height and Allowable Area.
310.2.1 General. Buildings or parts of buildings classed in Group R because of the use or charac-
ler of the occupancy shall be limited to the types of construction set forth in Table 5-13 and shall not
exceed, in area or height, the limits specified in Sections 504, 505 and 506.
310.2.2 Special provisions. Walls and floors separating dwelling units in the same building, or
guest rooms in Group R, Division I hotel occupancies, shall not be of less than one-hour fire-resis-
live construction.
Group R, Division I Occupancies more than two stories in height or having more than 3,000
square feet (279 m) of floor area above the first story shall not be of less than one-hour fire -resistive
construction throughout except as provided in Section 601.5.2.2.
Storage or laundry rooms that are within Group R, Division I Occupancies that are used in com-
mon by tenants shall be separated from the rest of the building by not less than one-hour fire-resis-
live occupancy separation.
For Group R, Division I Occupancies with a Group S, Division 3 parking garage in the basement
or first story, see Section 311.2.2.
For attic space partitions and draft slops, see Section 708.
310.3 Location on Property. For fire -resistive protection of exterior walls and openings, as de-
termined by location on property, see Section 503 and Chapter 6.
310.4 Access and Exit Facilities and Emergency Escapes. Exits shall be provided as specified
in Chapter 10. (See also Section 1013 for exit markings.)
Access to, and egress from, buildings required to be accessible shall be provided as specified in
Chapter 11.
Basements in dwelling units and every sleeping room below the fourth story shall have at least
one operable window or door approved for emergency escape or rescue which shall open directly
into a public street, public alley, yard or exit court. The emergency dooror window shall be operable
from the inside to provide a full, clear opening without the use of separate tools.
EXCEPTION: The window or door may open into an atrium complying with Section 402 provided the
window or door opens onto an exit balcony and the dwelling unit or guest room has an exit which does not
open into lhC alriun7.
Escape or rescue windows shall have a minimum net clear openable area of 5.7 square feel (0.53
1112). The minimum net clear openable height dimension shall be 24 inches (610 nun). The mini-
mum net clearopenable width dimension shall be 20 inches (508 nun). When windows are provided
as a means of escape or rescue, they shall have a finished sill height not more than 44 inches (1118
nun) above the floor.
1-48
310.7-310.9.2
1994 UNIFORM BUILDING CODE
4. The unit shall be provided with a separate bathroom containing a water closet, lavatory and
bathtub or shower.
310.8 Shaft and Exit Enclosures. Exits shall be enclosed as specified in Chapter 10.
Elevator shafts, vent shafts, dumbwaiter shafts, clothes chutes and other vertical openings shall
be enclosed and the enclosure shall be as specified in Section 711.
In nonsprinklered Group R, Division 1 Occupancies, corridors serving an occupant load of 10 or
more shall be separated from corridors and other areas on adjacent floors by not less than approved
fixed wired glass set in steel frames or by 20 -minute smoke- and draft -control assemblies which are
automatic closing by smoke detection.
310.9 Smoke Detectors and Sprinkler Systems.
310.9.1 Smoke detectors.
310.9.1.1 General. Dwelling units, congregate residences and hotel or lodging house guest
rooms that are used for sleeping proposes shall be provided with smoke detectors. Detectors shall be
installed in accordance with the approved manufacturer's instructions.
310.9.1.2 Additions, alterations or repairs to Group R Occupancies. When the valuation of an
addition, alteration or repair to a Group R Occupancy exceeds $1,000 and a permit is required, or
when one or more sleeping rooms are added or created in existing Group R Occupancies, smoke
detectors shall be installed in accordance with Sections 310.9.1.3, 310.9.1.4 and 310.9.1.5 of this
section.
I EXCEPTION: Repairs to the exterior surfaces of a Group R Occupancy are exempt from the require-
ments of this section.
310.9.1.3 Power source. In new construction, required smoke detectors shall receive their pri-
mary power from the building wiring when such wiring is served from a commercial source and
shall be equipped with a battery backup. The detector shall emit a signal when the batteries are low.
Wiring shall be permanent and without a disconnecting switch other than those required for over -
current protection. Smoke detectors may be solely battery operated when installed in existing
buildings; or in buildings without commercial power; or in buildings which undergo alterations,
repairs or additions regulated by Section 310.9.1.2.
310.9.1.4 Location within dwelling units. In dwelling units, a detector shall be installed in each
sleeping room and at a point centrally located in the corridor or area giving access to each separate
sleeping area. When the dwelling unit has more than one story and in dwellings with basements, a
detector shall be installed on each story and in the basement. In dwelling units where a story or base-
ment is split into two or more levels, the smoke detector shall be installed on the upper level, except
that when the lower level contains a sleeping area, a detector shall be installed on each level. When
sleeping rooms are on an upper level, the detector shall be placed at the ceiling of the upper level in
close proximity to the stairway. In dwelling units where the ceiling height of a room open to the
hallway serving the bedrooms exceeds that of the hallway by 24 inches (6 10 mm) or more, smoke
detectors shall be installed in the hallway and in the adjacent room. Detectors shall sound an alarm
audible in all sleeping areas of the dwelling unit in which they are located.
310.9.1.5 Location in efficiency dwelling units, congregate residences and hotels. In efficien-
cy dwelling units, hotel suites and in hotel and congregate residence sleeping rooms, detectors shall
be located on the ceiling or wall of the main room or each sleeping room. When sleeping rooms
within an efficiency dwelling unit or hotel suite are on an upper level, file detector shall be placed at
the ceiling of the upper level in close proximity to the stairway. When actuated, the detector shall
' sound an alarm audible within the sleeping area of the dwelling unit or congregate residence, hotel
suite, or sleeping room in which it is located.
310.9.2 Sprinkler and standpipe systems. When required by Section 904.2.1 or other provi-
sions of this code, automatic sprinkler systems and standpipes shall be designed and installed as
specified in Chapter 9.
1-50
1994 UNIFORM BUILDING CODE 310.10-311.1
310.10 Fire Alai -in Systems. Group R, Division 1 Occupancies shall be provided with an ap-
proved manual and automatic fire alarm system in apartment houses three or more stories in height
or containing 16 or more dwelling units, in hotels three or more stories in height or containing 20 or
more guest rooms and in congregate residences three or more stories in height or having an occu-
pant load of 20 or more. A fire alarm and communication system shall be provided in Group R,
Division I Occupancies located in a high-rise building.
EXCEPTIONS: I. A manual fire alann system need not be provided in buildings not over two stories in
height when all individual dwelling units and contiguous altic and crawl spaces are separated from each other
and public or common areas by at least one-hour fire -resistive occupancy separations and each individual
dwelling unit or guest room has an exit directly to a public way, exit court or yard.
2. A separate fire alarm system need not be provided in buildings which are protected throughout by an
approved supervised fire sprinkler system having it local alarm to notify all occupants.
'Phe local alarm shall provide an alarm signal with a sound pressure level of 15 dBA above the
average ambient sound level in every occupied space within the building. The minimum sound
pressure level shall be 70 dBA. The maximum sound pressure level for audible alarm -indicating
appliances shall not exceed 110 dBA at the minimum hearing distance from the audible appliance.
For the purposes of this section, area separation walls shall not define separate buildings.
310.11 Heating. Dwelling unit%, guest rooms and congregate residences shall be provided with
heating facilities capable of maintaining a room temperature of 70°F. (2VC.) at a point 3 feet (914
mm) above the floor in all habitable rooms.
310.12 Special Hazards. Chimneys and healing apparatus shall conform to the requirements of
Chapter 31 and the Mechanical Code.
The storage, use and handling of flammable and combustible liquids in Division I Occupancies
shall be in accordance with the Fire Code.
In Division I Occupancies, doors leading into rooms in which Class 1 flammable liquids are
stored or used shall be protected by a fire assembly having a one-hour fire -protection rating. Such
fire assembly shall be self-closing and shall be posted with a sign on each side of the door in 1 -inch
(25.4 tum) block letters stating: FIRE DOOR—KEEP CLOSED.
SECTION 311 — REQUIREMENTS FOR GROUP S OCCUPANCIES
311.1 Group S Occupancies Defined. Group S Occupancies shall include the use of a building or
structure, or a portion thereof, for storage not classified as a hazardous occupancy. Storage occu-
pancies shall include the following:
Division 1. Moderate hazard storage occupancies shall include buildings or portions of buildings
used for storage of combustible materials that are not classified as a Group S, Division 2 or as a
Group H Occupancy.
Division 2. Low -hazard storage occupancies shall include buildings, structures, or portions
thereof, used for storage of noncombustible materials, such as products on wood pallets or in paper
cartons with or without single -thickness divisions, or in paper wrappings and shall include ice
plants, power plants and pumping plants. Such products may have a negligible amount of plastic
trim such as knobs, handles or film wrapping. Low -hazard storage occupancies shall include, but
are not limited to, storage of the following items:
L Beer or wine (in metal, glass or ceramic containers).
2. Cement in bags.
3. Cold storage and creameries.
4. Dairy products in nonwax-coated paper containers.
5. Dry -cell batteries.
1-51
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
407-408 UNIFORM BUILDING CODE
FAMILY is an individual or two or more persons related by blood or marriage
or a group of not more than five persons (excluding servants) who need not be
related by blood or marriage living together in a dwelling unit.
FIRE ASSEMBLY. See Section 4306 (b).
FIRE CODE is the Uniform Fire Code promulgated jointly by the Western Fire
Chiefs Association and the International Conference of Building Officials, as
adopted by this jurisdiction.
FIRE RESISTANCE or FIRE -RESISTIVE CONSTRUCTION is con-
struction to resist the spread of fire, details of which are specified in this code.
FIRE -RETARDANT TREATED WOOD is lumber or plywood impregnated
with chemicals and which, when tested in accordance with U.B.C. Standard No.
42-1 for a period of 30 minutes, shall have a flame spread of not over 25 and show
no evidence of progressive combustion. Materials which may be exposed to the
weather shall maintain this fire -retardant classification when tested in accordance
with the rain and weathering tests of U.B.C. Standard No. 32-7.
All materials shall bear identification showing the fire performance rating
thereof and, if intended for exterior use, shall be further identified to indicate
suitability for exposure to the weather. Such identifications shall be issued by an
approved agency having a service for inspection of materials at the factory.
FLAMMABLE LIQUID. See Fire Code.
FLOOR AREA is the area included within the surrounding exterior walls of a
building or portion thereof, exclusive of vent shafts and courts. The floor area of a
building, or portion thereof, not provided with surrounding exterior walls shall be
the usable area under the horizontal projection of the roof or floor above.
FOOTING is that portion of the foundation of a structure which spreads and
transmits loads directly to the soil or the piles.
FRONT OF LOT is the front boundary line of a lot bordering on the street and,
in the case of a corner lot, may be either frontage.
G
Sec. 408. GARAGE is a building or portion thereof in which a motor vehicle
containing flammable or combustible liquids or gas in its tank is stored, repaired
or kept.
GARAGE, PRIVATE, is a building or a portion of a building, not more than
1000 square feet in area, in which only motor vehicles used by the tenants of the
building or buildings on the premises are stored or kept. (See Section 1101.)
GARAGE, PUBLIC, is any garage other than a private garage.
GRADE (Adjacent Ground Elevation) is the lowest point of elevation of the
finished surface of the ground, paving or sidewalk within the area between the
building and the property line or, when the property line is more than 5 feet from
the building, between the building and a line 5 feet from the building.
GRADE (Lumber) is the classification of lumber in regard to strength and
utility.
20
417-420 UNIFORM BUILDING CODE
greater than 75 when tested in the thickness intended for use by U. B.C. Standard
No. 52-2. Approved plastics shall be classified as either CCI or CC2, in accord-
ance with U.B.C. Standard No. 52-4.
PLATFORM. See Chapter 39.
PLUMBING CODE is the Uniform Plumbing Code promulgated by the
International Association of Plumbing and Mechanical Officials as adopted by
this jurisdiction.
PUBLIC WAY. See Section 3301 (b).
Q
See. 418. No definitions.
R
Sec. 419. REPAIR is the reconstruction or renewal of any part of an existing
building for the purpose of its maintenance.
S
Sec. 420. SERVICE CORRIDOR is a fully enclosed passage used for
"
trans-
-poses other than required exiting. HPM and for put
SHAFT is a vertical opening through a building for elevators, dumbwaiters,
mechanical equipment or similar purposes.
SHALL, as used in this code, is mandatory.
SMOKE DETECTOR is an approved detector which senses visible or invisi-
ble particles of combustion. The detector shall bear a label or other identification
issued by an approved testing agency having a service for inspection of materials
and workmanship at the factory during fabrication and assembly.
STAGE See Chapter 39.
STORY is that portion of a building included between the upper surface of any
floor and the upper surface of the floor next above, except that the topmost story
shall be that portion of a building included between the tipper surface of the
topmost floor and the ceiling or roof above. If the finished floor level directly
above a usable or unused under -floor space is more than 6 feet above grade as
defined herein for more than 50 percent of the total perimeter or is more than 12
feet above grade as defined herein at any point, such usable or unused under -floor
space shall be considered as a story.
STORY, FIRST, is the lowest story in a building which qualifies as a story, as
defined herein, except that a floor level in a building having only one floor level
shall be classified as a first story, provided such floor level is not more than 4 feet _
below grade, as defined herein, for more than 50 percent of the total perimeter, or
not more than 8 feet below grade, as defined herein, at any point.
STREET is any thoroughfare or public way not less than 16 feet in width which
has been dedicated or deeded to the public for public use.
STRUCTURE is that which is built or constructed, an edifice or building of
any kind, or any piece of work artificially built up or composed of parts joined
together in some definite manner.
24
504-505
UNIFORM BUILDING CODE
2. A point one third the distance from an assumed vertical plane located
where fire -resistive protection of openings is first required due to location
on property, whichever is the least restrictive.
When openings in exterior walls are required to be protected due to distance
from property line, the sum of the area of such openings shall not exceed 50
percent of the total area of the wall in each story.
(c) Buildings on Same Property and Buildings Containing Courts. For the
purposes of determining the required wall and opening protection and roof -
covering requirements, buildings on the same property and court walls of build-
ings over one story in height shall be assumed to have a property line between
them.
EXCEPTION: In court walls where opening protection is required such protec-
tion may be omitted, provided (1) not more than two levels open into the court, (2)
the aggregate area of the building including the court is within the allowable area and
(3) the building is not classified as a Group I Occupancy.
When a new building is to be erected on the same property as an existing
building, the location of the assumed property line with relation to the existing
I building shall be such that the exterior wall and opening protection of the existing
building meet the criteria as set forth in Table No. 5-A and Part IV.
EXCEPTION: Two or more buildings on the same property may be considered
as portions of one building if the aggregate area of such buildings is within the limits
specified in Section 505 for a single building.
When the buildings so considered house different occupancies or are of different
types of construction, the area shall be that allowed for the most restricted occupancy
or construction.
Allowable Floor Areas
See. 505. (a) One-story Areas. The area of a one-story building shall not
exceed the limits set forth in Table No. 5-C except as provided in Section 506.
(b) Areas of Buildings Over One Story. The total combined floor area for
multistory buildings may be twice that permitted by Table No. 5-C for one-story
buildings, and the floor area of any single story shall not exceed that permitted for
a one-story building.
(c) Mezzanines. Unless considered as a separate story, the floor area of all
mezzanines shall be included in calculating the allowable floor area of the stories
in which the mezzanines are located.
(d) Basements. A basement need not be included in the total allowable area,
provided such basement does not exceed the area permitted for a one-story
building.
(e) Area Separation Walls. Each portion of a building separated by one or
more area separation walls may be considered a separate building, provided the
area separation walls meet the following requirements:
1. Area separation walls shall be not less than four-hour fire -resistive construc-
tion in Types I, II -ER., III and IV buildings and two-hour fire -resistive construc-
tion in Types II One-hour, lI-N or V buildings. The total width of all openings in
such walls shall not exceed 25 percent of the length of the wall in each story. All
30
1985 EDITION 505
i
openings shall be protected by afire assembly having a three-hour fire -protection
rating in four-hour fire -resistive walls and one and one -half-hour fire -protection
rating in two-hour fire -resistive walls.
2. Area separation walls shall extend to the outer edges of horizontal projecting
elements such as balconies, roof overhangs, canopies, marquees or architectural
projections.
EXCEPTION: When horizontal projecting elements do not contain concealed
spaces, the area separation wall may terminate at the exterior wall.
When the horizontal projecting elements contain concealed spaces, the area
separation wall need only extend through the concealed space to the outer edges of
the projecting elements.
The exterior walls and the projecting elements above shall be of not less than one-
hour fire -resistive construction for a distance not less than the depth of the projecting
elements on both sides of the area separation wall. Openings within such widths shall
be protected by fire assemblies having a fire -protection rating of not less than three-
fourths hour.
3. Area separation walls shall extend from the foundation to a point at least 30
cinches above the roof.
— EXCEPTIONS: 1. Area separation walls may terminate at the underside of the
roof sheathing, deck or slab, provided the roof -ceiling assembly is of at least two-
hour fire -resistive construction.
2. Two-hour area separation walls may terminate at the underside of the roof
sheathing, deck or slab, provided:
A. Where the roof -ceiling framing elements are parallel to the walls, such framing
and elements supporting such framing shall be of not less than one-hour fire -
resistive construction for a width of not less than 5 feet on each side of the wall.
B. Where roof -ceiling framing elements are perpendicular to the wall, the entire
span of such framing and elements supporting such framing shall be of not less
than one-hour fire -resistive construction.
C. Openings in the roof shall not be located within 5 feet of the area separation wall.
D. The entire building shall be provided with a fire -retardant roof covering or y
special purpose roof complying with Section 3203 (g).
3. Two-hour area separation walls may terminate at roofs of entirely noncombusti-
ble construction.
4. Parapets of area separation walls shall have noncombustible faces for the
uppermost 18 inches, including counterflashing and coping materials. t3
5. Where an area separation wall separates portions of a building having
different heights, such wall may terminate at a point 30 inches above the lower
roof level, provided the exterior wall for a height of 10 feet above the lower roof is
of one-hour fire -resistive construction with openings protected by assemblies
having a three -fourths -hour fire -protection rating.
EXCEPTION: The area separation wall may terminate at the underside of the
roof sheathing, deck or slab of the lower roof, provided:
A. Where the roof -ceiling framing elements are parallel to the wall, such framing
and elements supporting such framing shall be of not less than one-hour fire -
resistive construction for a width of 10 feet along the wall at the lower roof.
31
1991 UNIFORM BUILDING CODE
505
than the basic area permitted in the occupancy by Table No. 5-C for such minor f
uses, for the purpose of determining allowable area, the major use of the building
shall determine the occupancy classification, provided the uses are separated as
specified in Section 503 (d). 9
(d) Mezzanines. Unless considered as a separate story, the floor area of all mez-
zanines shall be included in calculating the allowable Floor area of the stories in
which the mezzanines are located.
(e) Basements. Abasement need not be included in the total allowable area, pro-
vided such basement does not exceed the area permitted for a one-story building.
(f) Area Separation Walls. 1.General. Each portionof abuilding separatedby
oneormoreareaseparationwalls whichcomplywiththeprovisionsofthissubsec-
tion may be considered a separate building. The extent and location of such area
separation walls shall provided a complete separation.
Ki
When an area separation wall also separates occupancies that are required to be0.
separated by an occupancy separation, the most restrictive requirements of each
?;
separation shall apply.
2. Fire -resistance. Area separation walls shall not be of less than four-hour
k:
fire -resistive construction in Types I, II -ER., III and IV buildings and two-hour
fire -resistive construction in Type II One-hour, 11-N or V buildings. The total width
of all openings in such walls shall not exceed 25 percent of the length of the wall in
each story. All openings shall be protected by a fire assembly having a three-hour
fire -protection rating in four-hour fire -resistive walls and one- and one -half-hour
fire -protection rating in two-hour fire -resistive walls.
3. Extensions beyond exterior walls. Area separation walls shall extend to the
outer edges of horizontal projecting elements such as balconies, roof overhangs,
canopies, marquees or architectural projections.
EXCEPTION: When horizontal projecting elements do not contain concealed
spaces, the area separation wall may terminate at the exterior wall.
When the horizontal projecting elements contain concealed spaces, the area sepa-
ration wall need only extend through the concealed space to the outer edges of the
projecting elements.
i
The exterior walls and the projecting elements above shall not be of less than
one-hour fire -resistive construction for a distance not less than the depth of the proj-
ecting elements on both sides of the area separation wall. Openings within such
widths shall be protected by fire assemblies having a fire -protection rating of not less
than Three-fourths hour.
4. Terminaling. Area separation walls shall extend from the foundation to a
point at least 30 inches above the roof.
EXCEPTIONS: 1. Area separation walls may terminate at the underside of the
roof sheathing, deck or slab, provided the roof -ceiling assembly is of at least two-
hour fire -resistive construction.
2. Two-hour area separation walls may terminate at the underside of the roof
sheathing, deck or slab, provided:
A. Where the roof -ceiling framing elements are parallel to the walls, such fram-
ing and elements supporting such training shall not be of less than one-hour
39
505-506
1991 UNIFORM BUILDING CODE
fire -resistive construction for a width of not less than 5 feet on each side of
the wall.
B. Where roof -ceiling training elements are perpendicular to the wall, the entire
span of such framing and elements supporting such framing shall not be of l..
less than one-hour fire -resistive construction.
C. Openings in the roof shall not be located within 5 feet of the area separation
wall.
D. The entire building shall be provided with not less than a Class B roofing.
3. Two-hour area separation walls may terminate at the underside of noncombus-
tible roof sheathing, deck or slab of roofs of noncombustible construction provided:
" A. Openings in the roof are not located within 5 feet of the area separation wall.
B. The entire building is provided with not less than a Class B roofing.
5. Parapet faces. Parapets of area separation walls shall have noncombustible
faces for the uppermost 18 inches, including counterflashing and coping materials.
6. Buildings of different heights. Where an area separation wall separates por-
tions of a building having different heights, such wall may terminate at a point 30
inches above the lower roof level, provided the exterior wall for a height of 10 feet
above the lower roof is of one-hour fire -resistive construction with openings pro-
tected by assemblies having a three -fourths -hour fire -protection rating.
EXCEPTION: The area separation wall may terminate at the underside of the
roof sheathing, deck or slab of the lower roof, provided:
A. Where the roof -ceiling framing elements are parallel to the wall, such framing
and elements supporting such framing shall not be of less than one-hour
fire -resistive construction for a width of 10 feet along the wall at the lower
roof.
B. Where the lower roof -ceiling framing elements are perpendicularto the wall,
the entire span of such framing and elements supporting such framing shall
not be of less than one-hour fire -resistive construction.
C. Openings in the lower roof shall not be located within 10 feet of the area sepa-
ration wall.
See Chapters 6 through 12 for special occupancy provisions.
Allowable Area Increases
Sec. 506. (a) General. The floor areas specified in Section 505 maybe increased
by one of the following:
1. Separation on two sides. Where public ways or yards more than 20 feet in
width extend along and adjoin two sides of the building, floor areas may be in-
creased at a rate of 11/4 percent for each foot by which the minimum width exceeds
20 feet, but the increase shall not exceed 50 percent.
2. Separation on three sides. Where public ways or yards more than 20 feet in
width extend along and adjoin three sides of the building, floor areas may be in-
creased at a rate of 21/2 percent for each foot by which the minimum width exceeds
20 feet, but the increase shall not exceed 100 percent.
3. Separation on all sides. Where public ways or yards more than 20 feet in
width extend on all sides of a building and adjoin the entire perimeter, floor areas
may be increased at a rate of 5 percent for each foot by which the minimum ex -
40
I -.
1991 UNIFORM BUILDING CODE
505
than the basic area permitted in the occupancy by Table No. 5-C for such minor
uses, for the purpose of determining allowable area, the major use of the building
shall determine the occupancy classification, provided the uses are separated as
specified in Section 503 (d). fv
(d) Mezzanines. Unless considered as a separate story, the floor area of all mez-
zanines shall be included in calculating the allowable floor area of the stories in
which the mezzanines are located.
(e) Basements. A basement need not be i ncluded in the total allowable area, pro-
vided such basement does not exceed the area permitted for a one-story building.
(t) Area Separation Walls. 1. General. Each portion of a building separated by
one or more area separation walls whichcomply with the provisions of this subsec-
tion may be considered a separate building. The extent and location of such area
separation walls shall provided a complete separation.
When an area separation wall also separates occupancies that are required to be R
separated by an occupancy separation, the most restrictive requirements of each $
separation shall apply.
2. Fire -resistance. Area separation walls shall not be of less than four-hour
fire -resistive construction in Types 1, II-F.R., III and IV buildings and two-hour
fire -resistive construction in Type II One-hour, lI-N or V buildings. The total width
of all openings in such walls shall not exceed 25 percent of the length of the wall in
each story. All openings shall be protected by a fire assembly having a three-hour
fire -protection rating in four-hour fire -resistive walls and one- and one -half-hour
fire -protection rating in two-hour fire -resistive walls.
3. Extensions beyond exterior walls. Area separation walls shall extend to the
outer edges of horizontal projecting elements such as balconies, roof overhangs,
canopies, marquees or architectural projections.
EXCEPTION: When horizontal projecting elements do not contain concealed
spaces, the area separation wall may terminate at the exterior wall.
When the horizontal projecting elements contain concealed spaces, the area sepa-
ration wall need only extend through the concealed space to the outer edges of the
projecting elements.
The exterior walls and the projecting elements above shall not be of less than
one-hour fire -resistive construction for a distance not less than the depth of the proj-
ecting elements on both sides of the area separation wall. Openings within such
widths shall be protected by fire assemblies having a fire -protection rating of not less
than three-fourths hour.
4. Terminating. Area separation walls shall extend from the foundation to a
point at least 30 inches above the roof.
EXCEPTIONS: I. Area separation walls may terminate at the underside of the
i roof sheathing, deck or slab, provided the roof -ceiling assembly is of at least two-
hour fire -resistive construction.
2. Two-hour area separation walls may terminate at the underside of the roof
sheathing, deck or slab, provided:
A. Where the roof -ceiling framing elements are parallel to the walls, such train-
ing and elements supporting such framing shall not be of less than one-hour
39
509.1-509.3 1994 UNIFORM BUILDING CODE
EXCEPTION: Guardrails need not be provided at the following locations:
I. On the loading side of loading docks.
2. On the auditorium side of a stage, raised platforms and other raised floor areas such as runways, ramps
I and side stages used for entertainment or presentation. Along the side of an elevated walking surface when
used for the normal functioning of special lighting or for access and use of other special equipment. At vertical
openings in the performance area of stages.
3. Along vehicle service pits not accessible to the public.
509.2 height. The top of guardrails shall not be less than 42 inches (1067 mm) in height.
' EXCEPTIONS: I. The top of guardrails for Group R, Division 3 and Group M, Division 1 Occupancies
and interior guardrails within individual dwelling units, Group R, Division 3 congregate residences and guest
rooms of Group R, Division 1 Occupancies may be 36 inches (914 min) in height.
2. The top of guardrails on a balcony immediately in front of the first row of fixed seats and which are not
at the end of an aisle may be 26 inches (660 mm) in height.
3. The top of guardrails for stairways, exclusive of their landings, may have a height as specified in Section
1006.9 for handrails.
509.3 Openings. Open guardrails shall have intermediate rails or an ornamental pattern such that --
a sphere 4 inches (102 mm) in diameter cannot pass through.
EXCEPTIONS: I. The open space between the intermediate rails or ornamental pattern of guardrails in
areas of commercial and industrial -type occupancies which are not accessible to the public may be such that
a sphere 12 inches (305 nim) in diameter cannot pass through.
2. The triangular openings formed by the riser, tread and bottom element of a guardrail at the open side of
a stairway may be of such size that a sphere 6 inches (152 min) in diameter cannot pass through.
For guardrail requirements at grandstands, bleachers or other elevated seating facilities, see Sec-
tion 1021.5.7. -
1-90
708.2.2-708.4 1994 UNIFORM BUILDING CODE
Walls having parallel or staggered studs for sound -transmission control shall have fire blocks of
mineral fiber or glass fiber or other approved nonrigid materials.
708.3 Draft Slops. _
708.3.1 Where required. Draftstopping shall be provided in the locations set forth in this section
708.3.1.1 Floor -ceiling assemblies.
708.3.1.1.1 Single-family rlvvellings. When there is usable space above and below the concealed
space of a floor -ceiling assembly in a single-family dwelling, draft slops shall be installed so that
the area of the concealed space does not exceed 1,000 square feet (93 m2). Draftstopping shall di- .
vide the concealed space into approximately equal areas.
708.3.1.1.2 Two or more dwelling units and hotels. Draft stops shall be installed in floor -ceiling
assemblies of buildings having more than one dwelling unit and in hotels. Such draft stops shall be
in line with walls separating individual dwelling units and guest rooms from each other and from
other areas.
708.3.1.1.3 Other uses. Draft stops shall be installed in floor -ceiling assemblies of buildings or
portions of buildings used for other than dwelling or hotel occupancies so that the area of the con-
cealed space does not exceed 1,000 square feet (93 in) and so that the horizontal dimension be-
tween stops does not exceed 60 feet (I8 288 turn).
EXCEPTION: Where approved automatic sprinklers are installed within the concealed space, the area
between draft slops may be 3,000 square feet (279 m2) and the horizontal dimension may be 100 feet (30 480
Mill).
708.3.1.2 Attics.
708.3.1.2.1 Two or more dwelling units and hotels. Draft stops shall be installed in the attics, _
mansards, overhangs, false fronts set out from walls and similar concealed spaces of buildings con-
taining more than one dwelling unit and in hotels. Such draft stops shall be above and in line with the
walls separating individual dwelling units and guest rooms from each other and from other uses.
EXCEPTIONS: I. Draft stops may be omitted along one of the corridor walls, provided draft stops at
walls separating individual dwelling units and guest rooms from each other and from other uses, extend to the
remaining corridor draft stop.
2. Where approved sprinklers are installed, draftstopping may be as specified in the exception to Section
708.3.1.2.2 below.
708.3.1.2.2 Other uses. Draft stops shall be installed in attics, mansards, overhangs, false fronts
set out from walls and similar concealed spaces of buildings having uses other than dwellings or
hotels so that the area between draft stops does not exceed 3,000 square feet (279 1112) and the great-
est horizontal dimension does not exceed 60 feet (18 288 nun).
EXCEPTION: Where approved automatic sprinklers are installed, the area between draft stops may be
9,000 square feet (836 m2) and the greatest horizontal distension may be 100 feet (30 480 mm).
708.3.1.3 Draft sto1 construction. Draftstopping materials shall not be less than 1/2 -inch (12.7
' iron) gypsum board,/8-inch (9.5 mm) wood structural panel, 3/8 -inch (9.5 nim) Type 2-M particle-
board or other approved materials adequately supported.
Openings in the partitions shall be protected by self-closing doors with automatic latches con-
structed as required for the partitions.
Ventilation of concealed roof spaces shall be maintained in accordance with Section 1505.
708.4 Draft Stops or Fire Blocks in Other Locations. Fireblocking of veneer on noncombus-
tible walls shall be in accordance with Section 708.2.1, Item 1, above.
For fireblocking ceilings applied against noncombustible construction, see Section 803, Iteni 1.
1-114
1002.1.2-1003.1 1994 UNIFORM BUILDING CODE k
The occupant load for buildings or areas containing two or more occupancies shall be determined
by adding the occupant loads of the various use areas as computed in accordance with file applicable
provisions of [his section.
1002.1.3 Fixed seating. For areas having fixed seats and aisles, the occupant load shall be deter -
aimed by the number of fixed seats installed therein. The required width of aisles serving fixed seats
shall not be use(] for any other purpose.
For areas having fixed benches or pews, the occupant load) shall not be less than the number of
seats based on one person for each 18 inches (457 111m)'of length of pew or bench.
Where booths are used in dining areas, the occupant load shall be based on one person for each 24
inches (610 nun) of booth length or major portion thereof.
1002.1.4 Reviewing stands, grandstands and bleachers. The occupant load for reviewing
stands, grandstands and bleachers steal I be calculated in accordance with this section and the specif-
ic requirements contained in Section 1021.
1002.2 Maximum Occupant load.
1002.2.1 Assembly occupancies. The maximmn occupant load for assembly occupancies shall
not exceed the occupant load determined in accordance with Section 1002.1.
EXCEPTION: When approved by the building official, the occupant load for an assembly occupancy may
be increased provided the maximum occupant load served does not exceed the capacity of the exit system for
such increased number of persons. The building official may require an aisle, seating or fixed equipment (no -
grain to substantiate such an increase, and may require that such diagram be posted.
1002.2.2 Other occupancies. For other than assembly occupancies, an occupant load greater
than that determined in accordance with Section 1002.1 is permitted; however, the exit system shall
comply with the provisions of this chapter for such increased number of persons.
1002.3 Postingof Room Capacity. Any room having an occupant load of 50 or more where fixed
seals are not instal led, and which is used for assembly purpose, shall have (he capacity of the room
posted in a conspicuous place on an approved sign near the main exit from the room. Such signs
shall be maintained legible by the owner or the owner's authorized agent and shall indicate [he num-
. her of occupants permitted for each room use.
1002.4 Revised Occupant Load. After a building is occupied, any change in use or increase in
occupant load shall comply with this chapter. See Section 3405, - -
SECTION 1003 — EXITS REQUIRED
1003.1 Number of Exits. Every building or usable portion thereof shall have at least one exit, not
less than two exits where required by Table 10-A and additional exits as required by this section.
For purposes of [his section, basements and occupied roofs shall be provided with exits as re-
quired for stories.
EXCEPTION: Occupied roofs on Group R, Division 3 Occupancies may have one exit if such occupied
areas are less than 500 square feel (46.45 in ) and are located no higher than immediately above the second
story.
Floors complying with the provisions for mezzanines as specified in Section 506, Exception 3,
shall be provided with exits as specified therein.
Occupants on stories above the first and in basements shall have access to not less fl nn two sepa-
rate exits from the story or basement.
EXCEPTIONS: 1. Second stories having an occupant load less than 10 may be provided will) only one
exit.
2. Two or more dwelling units on the second story or in a basement may have access to only one common
exit when the total occupant load served by that exit does not exceed 10.
1-174
,I
1994 UNIFORM BUILDING CODE 1004.9-1005.2
access is not required, such dimension shall not exceed 1 inch (25 min). Landings shall be level
except for exterior landings, which may have a slope not to exceed 1/4 unit vertical in 12 units hori-
zontal (2% slope).
EXCEPTIONS: I. In Group R, Division 3, and Group U Occupancies and within individual units of '
Group R, Division I Occupancies:
1.1 A door may open at the lop step of in interior flight of stairs, provided the door does not swing over
the top step.
1.2 A door may open at a landing that is not more than 8 inches (203 mm) lower than the floor level,
provided the door does not swing over the handing.
1.3 Screen doors and storm doors may swing over stairs, steps or landings.
2. Doors serving building equipment roonis,which are not normally occupied.
1004.10 Landings at Doors. Landings shall have a width not less than the width of the stairway or
the width of the door, whichever is the greater. Doors in the fully open position shall not reduce a
required dimension by more than 7 inches (178 min). When a landing serves an occupant load of 50
or more, doors in any position shall not reduce the landing dimension to less than one half its re-
quired width. Landings shall have a length measured in the direction of travel of not less than 44
inches (1 l l8 min).
EXCEPTION: In Group R, Division 3, and Group U Occupancies and within individual units of Group '
R, Division I Occupancies, such length need not exceed 36 inches (914 min).
A landing which has no adjoining door shall comply with Section 1006.7.
1004.11 Door Identification. Glass doors shall conform to the requirements specified in Section
2406.
Exit doors shall be marked so that they are readily distinguishable from the adjacent construction.
1004.12 Additional Doors. When additional doors are provided for egress purposes, they shall
conform to all provisions of this chapter.
EXCEPTION: Approved revolving doors having leaves which will collapse under opposing pressures
may be used in exit situations, provided:
1. Such doors have a minimum width of 6 feet 6 inches (1981 nun).
2. At least one conforming exit door is located adjacent to each revolving door.
3. The revolving door shall not be considered to provide any exit width.
SECTION 1005 — CORRIDORS AND EXTERIOR EXIT BALCONIES
1005.1 General. This section shall apply to every corridor serving as a required exit for an occu-
pant load of 10 or more except that Section 1005.2 shall apply to all corridors. For the purpose of this
section, the term "corridor" shall include exterior exit balconies and covered or enclosed walk- I
ways, tunnels and malls. Partitions, rails, counters and similar space dividers not over 5 feet 9 inches
(1753 mm) in height above the floor shall not be construed to form corridors.
Exit corridors shall not be interrupted by intervening rooms.
EXCEPTION: Foyers, lobbies or reception rooms constructed as required for corridors shall not be con-
strued as intervening rooms.
Corridors which are located within an accessible route of travel shall also comply with Chapter
11.
For Group I Occupancies see Section 1019.3.
1005.2 Width. The minimum corridor width shall be determined as specified in Section 1003.2,
but shall not be less than 44 inches (1118 mm), except as specified herein. Corridors serving an oc-
cupant load of 49 or less shall not be less than 36 inches (914 min) in width. Forspecial requirements
for Groups E and I Occupancies, see Sections 1017 and 1019.
1-179
1005.3-1005.8.1 1994 UNIFORM BUILDING CODE
1005.3 Height. Corridors and exterior exit balconies shall have a clear height of not less than
7 feet (2134 min) measured to the lowest projection from the ceiling.
1005.4 Projections. The required width of corridors shall be unobstructed.
EXCEPTION: Handrails and doors, when fully opened, shall not reduce the required width by more than
7 incites (178 min). Doors in any position shall not reduce the required width by more than one half. Other
nonstructural projections such as trim and similar decorative features may project into the required width 11/2
inches (38 min) on each side.
1005.5 Access to Exits. When more than one exit is required, they shall be so arranged that it is
possible to go in either direction from any point in a corridor to a separate exit, except for dead ends
not exceeding 20 feet (6096 mm) in length.
1005.6 Changes in Elevation. When a corridor or exterior exit balcony is accessible to the handi-
capped, changes in elevation of the floor shall be made by means of a ramp, except as provided for
doors by Section 1004.9.
1005.7 Construction. Walls of corridors serving a Group R, Division 1 or Group I Occupancy
having an occupant load of 10 or more and walls of corridors serving other occupancies having an
occupant load of 30 or more shall be of not less than one-hour fire -resistive construction and the
ceilings shall not be less than that required for a one-hour fire -resistive floor or roof system.
EXCEPTIONS: 1. One-story buildings housing Group S, Division 2 Occupancies.
2. Corridors more than 30 feet (9144 min) in width where occupancies served by such corridors have at
least one exit independent from the corridor. (See Chapter 4 for covered malls.)
3. Exterior sides of exterior exit balconies.
4. In Group 1, Division 3 Occupancies such as jails, prisons, reformatories and similar buildings with
open -barred cells forming corridor walls, the corridors and cell doors need not be fire resistive.
5. Corridor walls and ceilings need not be of fire -resistive construction within office spaces having an
occupant load of 100 or less when the entire story in which the space is located is equipped with an automatic
sprinkler system throughout and an automatic smoke -detection system installed within the corridor. The aclua-
lion of any detector shall activate alarms audible in all areas served by the corridor.
6. In other than Type I or Il construction, exterior exit balcony roof assemblies may be of heavy -limber
construction without concealed spaces.
7. Within office spaces occupied by a single tenant, partial height partitions which form corridors and
which do not exceed 6 feet (1829 mm) in height need not be fire resistive, provided they are constructed in
accordance with Section 601.5 and are not more than three fourths of the floor -to -ceiling height.
8. Corridor wal Is and ceilings need not be of fire -resistive construction within office spaces having an occu-
pant load of 100 or less when the building in which the space is located is equipped with an automatic sprinkler
system throughout.
When the ceiling of the entire story is an element of a one-hour fire -resistive floor or roof system,
the corridor walls may terminate at the ceiling. When the room -side fire -resistive membrane of the
corridor wall is carried through to the underside of a fire -resistive floor or roof above, the corridor
side of the ceiling may be protected by the use of ceiling materials as required for one-hour floor or
roof system construction or the corridor ceiling may be of the same construction as the corridor
walls.
Ceilings of noncombustible construction may be suspended below the fire -resistive ceiling.
For wall and ceiling finish requirements, see Table 8-B.
For restrictions on the use of corridors to convey air, see Chapter 10 of the Mechanical Code.
1005.8 Openings.
1005.8.1 Doors. When corridor walls are required to be of one-hour fire -resistive construction by
Section 1005.7, every interior door opening shall be protected by a tight -fitting smoke- and
draft -control assembly having a fire -protection rating of not less than 20 minutes when tested in
accordance with U.B.C. Standard 7-2. Said doors shall not have louvers. The door and frame shall
1-180
1991 UNIFORM BUILDING CODE 1201-1204
Chapter 12
REQUIREMENTS FOR GROUP R OCCUPANCIES
Group R Occupancies Defined
Sec. 1201. Group R Occupancies shall be:
Division 1. Hotels and apartment houses.
Congregate residences (each accommodating more than 10 persons).
Division 2. Not used.
Division 3. Dwellings and lodging houses.
Congregate residences (each accommodating 10 persons or less).
For occupancy separations, see Table No. 5-B.
z;.
A complete code for construction of detached one- and two-family dwellings is
in Appendix Chapter 12 of this code. When adopted, as set forth in Section 103, it
will take precedence over the requirements set forth in Parts I through X and Chap-
ter 60 of this code.
Construction, Height and Allowable Area
Sec. 1202. (a) General. Buildings or parts of buildings classed in Group R be-
cause of the use or character of the occupancy shall be limited to the types of con-
struction set forth in Tables Nos. 5-C and 5-D and shall not exceed, in area or
height, the limits specified in Sections 505, 506 and 507.
(b) Special Provisions. Walls and Moors separating dwelling units in the same
building shall not be of less than one-hour fire -resistive construction.
GroupR,Division I Occupancies more than two stories in heightorhaving more
than 3,000 square feet of floor area above the first story shall not be of less than
one-hour Tire -resistive construction throughout except as provided in Section 1705
(b) 2.
Storage or laundry rooms that are within Group R, Division I Occupancies that
are used in common by tenants shall be separated from the rest of the building by
not less than one-hour fire -resistive occupancy separation.
For Group R, Division I Occupancies with a Group B,Division I parkinggarage
in the basement or first floor, see Section 702 (b) 1.
For attic space partitions and draft stops, see Section 2516 (f).
Location on Property
Sec. 1203. For fire -resistive protection of exterior wails and openings, as deter-
mined by location on property, see Section 504 and Part 1V.
Access and Exit Facilities and Emergency Escapes
See. 1204. Exits shall be provided as specified in Chapter 33. (See also Section
3317 for special requirements and Section 3314 for exit markings.)
Access to, and egress from, buildings required to be accessible shall be provided
as specified in Chapter 3l.
103
N
W
¢
0U
0
0M
mm
0U
0
1985 EDITION 1201-1204
Chapter 12
REQUIREMENTS FOR GROUP R OCCUPANCIES
Group R Occupancies Defined
Sec. 1201. Group R Occupancies shall be:
Division l�i�o� els and apartment houses:
Convents and monasteries (each accommodating more than 10 persons).
Division 2. Not used.
Division 3. Dwellings and lodging houses.
For occupancy separations, see Table No. 5-B.
A complete code for construction of detached one- and two-family dwellings is
in Appendix Chapter 12 of this code. When adopted, as set forth in Section 103, it
will take precedence over the requirements set forth in Parts I through X and
Chapter 60 of this code.
Construction, Height and Allowable Area
Sec. 1202. (a) General. Buildings or parts of buildings classed in Group R
because of the use or character of the occupancy shall be limited to the types of
construction set forth in Tables No. 5-C and No. 5-D and shall not exceed, in area
or height, the limits specified in Sections 505, 506 and 507.
(b) Special Provisions. Group R, Division l Occupancies more than two
stories in height or having more than 3000 square feet of floor area above the first
story shall be not less than one-hour fire -resistive construction throughout except
as provided in Section 1705 (b) 2.
Storage or laundry rooms that are within Group R, Division I Occupancies that
are used in common by tenants shall be separated from the rest of the building by
not less than one-hour fire -resistive occupancy separation.
Every apartment house three stories or more in height or containing more than
15 dwelling units and every hotel three stories or more in height or containing 20
or more guest rooms shall have an approved fire alarm system as specified in the F
Fire Code. '
EXCEPTION: An alarm system need not be installed in buildings not over two F
stories in height when all individual dwelling units and contiguous attic and crawl
spaces are separated from each other and from public or common areas by at least F
one-hour fire -resistive occupancy separations and each individual dwelling unit has
an exit direct to a yard or public way. F
For Group R, Division 1 Occupancies with a Group B, Division I parking
garage in the basement or first floor, see Section 702 (a).
For attic space partitions and draft stops, see Section 2516 (f).
Location on Property
• Sec. 1203. For fire -resistive protection of exterior walls and openings, as
determined by location on property, see Section 504 and Part IV.
Exits and Emergency Escapes
Sec. 1204. Stairs, exits and smokeproof enclosures shall be as specified in
Chapter 33.
71
1204-1205 UNIFORM BUILDING CODE
Every sleeping room below the fourth story shall have at least one operable
window or exterior door approved for emergency escape or rescue. The units shall
be operable from the inside to provide a full clear opening without the use of
separate tools.
All escape or rescue windows from sleeping rooms shall have,p minimum net
clear opening of 5.7 square feet. The minimum net clear opening height dimen-
sion shall be 24 inches. The minimum net clear opening width dimension shall be
20 inches. Where windows are provided as a means of escape or rescue they shall
have a finished sill height not more than 44 inches above the floor.
Bars, grilles, grates or similar devices may be installed on an emergency escape
or rescue windows or doors, provided:
1. Such devices are equipped with approved release mechanisms which are
openable from the inside without the use of a key or special knowledge or
effort; and
2. The building is equipped with smoke detectors installed in accordance with
Section 1210.
Light, Ventilation and Sanitation —
Sec. 1205. (a) Light and Ventilation. All guest rooms, dormitories and
habitable rooms within a dwelling unit shall be provided with natural light by
means of exterior glazed openings with an area not less than one tenth of the floor
area of such rooms with a minimum of 10 square feet. All bathrooms, water closet
compartments, laundry rooms and similar rooms shall be provided with natural
ventilation by means of openable exterior openings with an area not less than one
twentieth of the floor area of such rooms with a minimum of 11/2 square feet.
All guest rooms, dormitories and habitable rooms within a dwelling unit shall
be provided with natural ventilation by means of openable exterior openings with
an area of not less than one twentieth of the floor area of such rooms with a
minimum of 5 square feet.
In lieu of required exterior openings for natural ventilation, a mechanical
ventilating system may be provided. Such system shall be capable of providing
two air changes per hour in all guest rooms, dormitories, habitable rooms and in
public corridors. One fifth of the air supply shall be taken from the outside. In
bathrooms, water closet compartments, laundry rooms and similar rooms a
mechanical ventilation system connected directly to the outside, capable of
providing five air changes per hour, shall be provided.
For the purpose of determining light and ventilation requirements, any room
may be considered as a portion of an adjoining room when one half of the area of
the common wall is open and unobstructed and provides an opening of not less
than one tenth of the floor area of the interior room or 25 square feet, whichever is
greater.
Required exterior openings for natural light and ventilation shall open directly ` '.-
onto a street or public alley or a yard or court located on the same lot as the
building.
72
4 �I
1991 UNIFORM BUILDING CODE 1209.1210
In nonsprinklered Group R, Division 1 Occupancies, corridors serving an occu-
pant load of 10 or more shall be separated from corridors and other areas on adja-
cent floors by not less than approved fixed wired glass set in steel frames or by
20-minute smoke- and draft-control assemblies which are automatic closing by
smoke detection.
Smoke Detectors and Sprinkler Systems
Sec. 1210. (a) Smoke Detectors. 1. General. Dwelling units, congregate resi-
dences and hotel or lodging house guest rooms that are used for sleeping purposes
shall be provided with smoke detectors. Detectors shall be installed in accordance
with the approved manufacturer's instructions.
2. Additions, alterations or repairs to Group R Occupancies. When the valu-
ation of an addition, alteration or repair to a Group R Occupancy exceeds $1,000 I
and a permit is required, or when one or more sleeping rooms are added or created
in existing Group R Occupancies, smoke detectors shall be installed in accordance
with Subsections 3, 4 and 5 of this section.
3. Power source. In new construction, required smoke detectors shall receive
their primary power from the building wiring when such wiring is served from a
commercial source and shall be equipped with a battery backup. The detectorshall
emit a signal when the batteries are low. Wiring shall be permanent and without a
disconnecting switch other than those required for overcurrent protection. Smoke
detectors may be solely battery operated when installed in existing buildings; or in £
buildings without commercial power; or in buildings which undergo alterations,
repairs or additions regulated by Subsection 2 of this section.
4. Location within dwelling units. In dwelling units, a detector shall be in-
stalled in each sleeping room and at a point centrally located in the corridor or area>
giving access to each separate sleeping area. When the dwelling unit has more than
one story and in dwellings with basements, a detector shall be installed on each
story and in the basement. In dwelling units where a story or basement is split into
two or more levels, the smoke detector shall be installed on the upper level, except
that when the lower level contains a sleeping area, a detector shall be installed on
each level. When sleeping rooms are on an upperlevel, the detector shall be placed
at the ceiling of the upper level in close proximity to the stairway. In dwelling units
where the ceiling height of a room open to the hallway serving the bedrooms ex-
ceeds that of the hallway by 24 inches or more, smoke detectors shall be installed in
the hallway and in the adjacent room. Detectors shall sound an alarm audible in all
sleeping areas of the dwelling unit in which they are located.
5. Location in efficiency dwelling units, congregate residences and hotels. In
efficiency dwelling units, hotel suites and in hotel and congregate residence sleep-
ing rooms, detectors shall be located on the ceiling or wall of the main room or each
sleeping room. When sleeping rooms within an efficiency dwelling unit or hotel
suite are on an upper level, the detector shall be placed at the ceiling of the upper
level in close proximity to the stairway. When actuated, the detectorshall sound an
alarm audible within the sleeping area of the dwelling unit, hotel suite or sleeping
room in which it is located.
107
1985 EDITION 1210.1212
sleeping rooms are on an upper level, the detector shall be placed at the center of
the ceiling directly above the stairway. All detectors shall be located in accordance
with approved manufacturer's instructions. When actuated, the detector shall
provide an alarm in the dwelling unit or guest room.
When the valuation of an addition orrepair to a Group R, Division 3 Occupancy
exceeds $1,000.00, or when one or more sleeping rooms are added or created in
existing Group R, Division 3 Occupancies, the entire building shall be provided
with smoke detectors located as required for new Group R, Division 3 Occupan-
cies.
In new construction, required smoke detectors shall receive their primary
power from the building wiring when such wiring is served from a commercial
source. Wiring shall be permanent and without a disconnecting switch other than
those required for overcurrent protection. Smoke detectors may be battery oper-
ated when installed in existing buildings, or in buildings without commercial
power, or in buildings which undergo alterations, repairs oradditions regulated by
the second paragraph of this section.
A smoke detector shall be installed in the basement of dwelling units having a
stairway which opens from the basement into the dwelling. Such detector shall be
connected to a sounding device or other detector to provide an alarm which will be
audible in the sleeping area.
(b) Sprinkler and Standpipe Systems. When required by other provisions of
this code, automatic sprinkler systems and standpipes shall be installed as speci-
fied in Chapter 38.
Heating
Sec. 1211. Every dwelling unit and guest room shall be provided with heating
facilities capable of maintaining a room temperature of 70°F at a point 3 feet
above the floor in all habitable rooms.
Special Hazards
See. 1212. Chimneys and heating apparatus shall conform to the requirements
of Chapter 37 and the Mechanical Code.
The storage and handling of gasoline, fuel oil or other flammable liquids in
Division 1 Occupancies shall be in accordance with the Fire Code.
In Division 1 Occupancies, doors leading into rooms in which Class I flamma-
ble liquids are stored or used shall be protected by a fire assembly having a one -
(tour fire -protection rating. Such fire assembly shall be self-closing and shall be
posted with a sign on each side of the door in 1 -inch block letters stating: FIRE
DOOR—KEEP CLOSED.
Every room containing a boiler, central heating plant or hot-water supply boiler
in Division I Occupancies shall be separated from the rest of the building by not
less than a one-hour fire -resistive occupancy separation.
EXCEPTION: A separation shall not be required for such rooms with equipment
serving only one dwelling unit.
75
..,.� y ........
1991 UNIFORM BUILDING CODE
(b) Sprinkler and Standpipe Systems. When required by other provisions of
this code, automatic sprinkler systems and standpipes shall be installed as speci-
fied in Chapter 38. -
Fire Alarm Systems
Sec. 1211. Group R, Division 1 Occupancies shall be provided with an approved
manual and automatic fire alarm system in apartment houses three or more stories
in height or containing 16 or more dwelling units, in hotels three or more stories in
height or containing 20 or more guest rooms and in congregate residences three or
more stories in height or having an occupant load of 20 or more. A fire alarm and
communication system shall be provided in Group R, Division I Occupancies lo-
cated in a high-rise building.
EXCEPTIONS: 1. A manual fire alarm system need not be provided in build-
ings not over two stories in height when all individual dwelling units and contiguous
attic and crawl spaces are separated from each other and public or common areas by
at least one-hour fire -resistive occupancy separations and each individual dwelling
unit or guest room has an exit directly to a public way, exit court or yard.
2. A separate fire alarm system need not be provided in buildings which are pro-
tected throughout by an approved supervised fire sprinkler system having a local
alarm to notify all occupants.
Heating
Sec. 1212. Dwelling units, guest rooms and congregate residences shall be pro-
vided with heating facilities capable of maintaining a room temperature of 70oF.
at a point 3 feet above the floor in all habitable rooms.
Special Hazards
Sec. 1213. Chimneys and heating apparatus shall conform to the requirements
of Chapter 37 and the Mechanical Code.
The storage, use and handling of flammable and combustible liquids in Division
1 Occupancies shall be in accordance with the Fire Code.
In Division 1 Occupancies, doors leading into rooms in which Class I flammable
liquids are stored or used shall be protected by a fire assembly having a one-hour
fire -protection rating. Such fire assembly shall be self-closing and shall be posted
with a sign on each side of the door in 1 -inch block letters stating: FIRE DOOR—
KEEP CLOSED.
Every room containing a boiler, central heating plant or hot-water supply boiler
in Division I Occupancies shall be separated from the rest of the building by not
less than a one-hour fire -resistive occupancy separation.
EXCEPTION: A separation shall not be required for such rooms with equip-
ment serving only one dwelling unit.
N
108
Chapters 13-16
NO REQUIREMENTS
1710-1712 UNIFORM BUILDING CODE
Projections from walls of Type III, IV or V construction may be of noncombus-
tible or combustible materials.
Combustible projections located where openings are not permitted or where
protection of openings is required shall be of one-hour fire -resistive or heavy
timber construction conforming to Section 2106.
Projections shall not extend more than 12 inches into the areas where openings
are prohibited.
For projections extending over public property, see Chapter 45.
For combustible ornamentation, see Section 1705 (d).
Guardrails
Sec. 1711. All unenclosed floor and roof openings, open and glazed sides of
landings and ramps, balconies or porches vyjj "WL ;e,p�gC 4 7I an, 30 jtiche.s,ahctiue,
de or floor below W. than -service -of the buildir_)g Sha(I
,rotgcted_by. a_guarslrail. Guardrails shall be not less than 42 inches in height.
Open guardrail and staff railings shall have intermediate rails or an ornamental
pattern such that a sphere 6 inches in diameter cannot pass through. The height of
stair railings on open sides may be as specified in Section 3306 0) in lieu of
providing a guardrail. Ramps shall, in addition, have handrails when required by
Section 3307.
EXCEPTIONS: 1. Guardrails need not be provided on the loading side of
loading docks.
2. Guardrails for Group R, Division 3 and Group M, Division I Occupancies may
be 36 inches in height.
3. Interior guardrails within individual dwelling units or guest rooms of Group R,
Division 1 Occupancies may be 36 inphes in height.
4. The open space between the intermediate rails or ornamental pattern of guard-
rails in areas of commercial and industrial -type occupancies which are not accessible
to the public may be increased such that a 12 -inch -diameter sphere cannot pass
through.
5. Guardrails on a balcony immediately in front of the first row of fixed seats and
which are not at the end of an aisle may be 26 inches in height.
6. Guardrails need not be provided on the auditorium side of a stage or enclosed
platform.
Ep, LPIastic Insulation
See. 1712. (a) General. The provisions of this section shall govern the require-
ments and uses of foam plastic in buildings and structures. For trim, see Section
1705 (e).
Except where otherwise noted in this section, all foam plastics used in building
construction shall have a flame -spread rating of not more than 75 and shall have a
smoke -developed rating of not more than 450 when tested in the maximum
thickness intended for use in accordance with U.B.C. Standard No. 42-1. All
packages and containers of foam plastic and foam plastic ingredients shall bear the
label of an approved agency showing either the flame -spread rating and smoke -
developed rating of the product at the thickness tested or the use for which the
product has been listed. The interior of the building shall be separated from the
foam plastic by an approved thermal barrier having an index of 15 when tested in
82
1710.1712 1991 UNIFORM BUILDING CODE
r
(iv) The entire building shall be provided with not less than a Class B roof cov-
cring.
(b) Construction. Parapets shall have the same degree of fire resistance re-
quired for the wall upon which they are erected, and on any side adjacent to a roof
surface, shall have noncombustible faces for the uppermost 18 inches, including
counterflashing and coping materials. The height of the parapet shall not be less
than 30 inches above the point where the roof surface and the wall intersect. Where
the roof slopes toward a parapet at slopes greater than 2:12, the parapet shall extend
to the same height as any portion of the roof that is within the distance where protec-
tion of wall openings would be required, but in no case shall the height be less than
30 inches.
Projections
Sec. 1711. Cornices, eave overhangs, exterior balconies and similar architectur-
al appendages extending beyond the floor area as defined in Section 407 shall con-
form to the requirements of this section. (See Sections 3305 and 3306 for additional
requirements applicable to exterior exit balconies and stairways.)
Projections from walls of Type I or II construction shall be of noncombustible
materials.
Projections from walls of Type III, IV or V construction may be of noncombus-
tible or combustible materials.
Combustible projections located where openings are not permitted or where
protection of openings is required shall be of one-hour fire -resistive or heavy -tim-
ber construction conforming to Section 2106.
N For projections extending over public property, see Chapter 45.
For combustible ornamentation, see Section 1705 (d).
For fire -resistive requirements, see Section 504 (b).
Guardrails and Vehicle Barriers
g Sec. 1712. (a) Guardrails. Unenclosed floor and roof openings, open and
glazed sides of stairways, landings and ramps, balconies or porches, which are
more than 30 inches above grade or floor below, and roofs used for other than ser-
vice of the building shall be protected by a guardrail.
EXCEPTION: Guardrails need not be provided at the following locations:
A. On the loading side of loading docks.
of
B. On the auditorium side of a stage or enclosed platform.
C. Along vehicle service pits not accessible to the public.
The top of guardrails shall not be less than 42 inches in height.
EXCEPTIONS: I. The top of guardrails for Group R, Division 3 and Group M,
Division I Occupancies and interior guardrails within individual dwelling units,
Group R, Division 3 congregate residences and guest rooms of Group R, Division
Occupancies may be 36 inches in height.
2. The top of guardrails on a balcony immediately in front of the first row of fixed
seats and which are not at the end of an aisle may be 26 inches in height.
116
2516 UNIFORM BUILDING CODE
(iii) Other uses. Draft stops shall be installed in floor -ceiling assemblies of
buildings or portions of buildings used for other than dwelling or hotel occupan-
cies so that the area of the concealed space does not exceed 1,000 square feet and
so that the horizontal dimension between stops does not exceed 60 feet.
EXCEPTION: Where approved automatic sprinklers are installed within the
concealed space, the area between draft stops may be 3,000 square feet and the
horizontal dimension may be 100 feet.
B. Attics. (i) Single-family dwellings. None required.
(ii) 3:w.go more,dwelling.unitsand-hoteig, Draft stops shall be installed in the
attics, mansards, overhangs, false fronts set out from walls and similar concealed
spaces of buildings containing more than one dwelling unit and in hotels. Such
draft stops shall be above and in line with the walls separating tenant spaces from
each other and from other uses.
EXCEPTIONS: 1. Draft stops may be omitted along one of the corridor walls,
provided draft stops at tenant separation walls extend to the remaining corridor draft
stop. 1
2. Where approved sprinklers are installed, draftstopping may be as specified in
the exception to Item (iii) below.
(iii) QJhcF,,„uses, Draft stops shall be installed in attics, mansards, overhangs,
false fronts set out from walls and similar concealed spaces of buildings having
uses other than dwellings or hotels so that the area between draft stops does not
exceed 3,000 square feet and the greatest horizontal dimension does not exceed 60
feet.
EXCEPTION: Where approved automatic sprinklers are installed the area be-
tween draft stops may be 9,000 square feet and the greatest horizontal dimension
may be 100 feet.
5. Draft stop construction. Draftstopping materials shall be not less than Ch-
inch gypsum board, 3/8 -inch plywood or other approved materials adequately
supported.
Openings in the partitions shall be protected by self-closing doors with auto-
matic latches constructed as required for the partitions.
Ventilation of concealed roof spaces shall be maintained in accordance with
Section 3205.
6. Draft or fire stops in other locations. Firestopping of veneer on noncom-
bustible walls shall be in accordance with Item No. 2 A above.
For firestopping of wood floors on masonry or concrete floors, see Sections
1804 and 1904. `
For firestopping ceilings applied against noncombustible construction, see
Section 4203, Item No. 1.
For firestopping penetrations in walls required to have protected openings, see
Section 4304 (e).
For firestopping penetrations through floors, see Section 4305 (a).
(g) Exterior Wall Coverings. 1. General. Exterior wood stud walls shall be
covered on the outside with the materials and in the manner specified in this
section or elsewhere in this code. Studs or sheathing shall be covered on the
204
1985 EDITION 3204-3206
Roof Insulation
See. 3204. The use of combustible roof insulation shall be permitted, provided
it is covered with approved roof covering applied directly thereto. For foam
plastic, see Section 1712.
Insulation shall be of a rigid type suitable for application of a roof covering.
Where fire -retardant roof coverings are required, insulations shall be a type
approved for the type of deck and the built-up roofing applied.
Where built-up roofing is to be applied, vapor barriers shall be installed
between the deck and the insulation where the average January temperature is
below 45°F. or where excessive moisture conditions are anticipated within the
building.
Attics: Ac e, a(irS#o spa �c a t��JIAQ
'"ST M,2 (a) Access. An attic access opening Aall be provided in the ceiling
of the top floor of buildings with combustible ceiling or roof construction. The
opening shall be located in a corridor or hallway of buildings of three or more
stories in height and readily accessible in buildings of any height.
The opening shall be not less than 22 inches by 30 inches.
Thirty -inch minimum clear head room shall be provided above the access
opening.
Attics with a maximum vertical clear height of less than 30 inches need not be
provided with access openings.
(b) Draft Stops. Attics, mansards, overhangs and other concealed roof spaces
formed of combustible construction shall be draft stopped as specified in Section
2516 (f).
(c) Ventilation. Where determined necessary by the building official due to
atmospheric or climatic conditions, enclosed attics and enclosed rafter spaces
formed where ceilings are applied direct to the underside of roof rafters shall have
cross ventilation foreach separate space by ventilating openings protected against
the entrance of rain and snow. The net free ventilating area shall be not less than
t/t5o of the area of the space ventilated, except that the area may be 1/300, provided
at least 50 percent of the required ventilating area is provided by ventilators
located in the upper portion of the space to be ventilated at least 3 feet above cave
or cornice vents with the balance of the required ventilation provided by eaveKor
cornice vents. The openings shall be covered with corrosion -resistant metal mesh
with mesh openings of 1/4 inch in dimension.
Smoke and Heat Venting
See. 3206. (a) When Required. Smoke and heat vents shall be installed in
accordance with the provisions of this section as follows:
1. In single -story Group B, Divisions 2 and 4 Occupancies having over 50,000
square feet in undivided area.
EXCEPTIONS: 1. Office buildings and retail sales areas.
2. Group B, Division 4 Occupancies used for bulk frozen food storage when the
building is protected by a complete automatic sprinkler system.
547
3302-3303 UNIFORM BUILDING CODE
The maximum occupant load for an assembly use shall not exceed the occupant
load as determined in accordance with Section 3302 (a).
EXCEPTION: The occupant load for an assembly building or portion thereof
may be increased, when approved by the building official, if all the requirements of
this code are met for such increased number of persons. The building official may `
require an approved aisle, seati ng or f fixed equipment diagram to substantiate such an
increase, and may require that such diagram be posted.
(c) 's}tlg nl^)pQnt,,GQ��{y. Any room having an occupant load of 50 or
C l,) O f�t Lore where fixed seats are not installed, and which is used for classroom,
t assembly or similar purpose, shall have the capacity of the room posted in a
conspicuous place on an approved sign near the main exit from the room. Such
signs shall be maintained legible by the owner or his authorized agent and shall
indicate the number of occupants permitted for each room use.
(d) Revised Occupant Load. After a building is occupied, any change in use or
increase in occupant load shall comply with this chapter. See Section 502.
is 1jequirrect
Sec. 3303. (a) Number of Exits. Every building or usable portion thereof shall
have at least one exit, not less than two exits where required by Table No. 33-A
and additional exits as required by this subsection.
For purposes of this section, basements and occupied roofs shall be provided
with exits as required for stories.
Floors complying with the provisions for mezzanines as specified in Section
1716 shall be provided with exits as specified therein.
The second story shall be provided with not less than two exits when the
occupant load is 10 or more.
EXCEPTIONS: 1. Except as provided in Table No. 33-A, only one exit need be
provided from the second story within an individual dwelling unit. Refer to Section
1204 for emergency escape or rescue requirements from sleeping rooms.
2. Two or more dwelling units on the second story may have access to only one
common exit when the total occupant load does not exceed 10.
Occupants on floors above the second story and in basements shall havgaccess
to not less than two separate exits from the floor or basement.
EXCEPTIONS: I. Floors and basements used exclusively for service of the
building may have one exit. For the purposes of this exception, storage rooms,
laundry rooms, maintenance offices and similar uses shall not be considered as
providing service to the building.
2. Basements within an individual dwelling unit having an occupant load of less
than 10 may have one exit.
3. Storage rooms, laundry rooms and maintenance offices not exceeding 300
square feet in floor area may be provided with only one exit.
'`
4. Occupied roofs on Group R, Division 3 Occupancies may have one exit if such
occupied areas are less than 500 square feet located no higher than immediately
'''A above the second story.
For special requirements see the following sections: Group A, Sections 3317
and 3318; Group E, Section 3319; Group H, Section 3320; Group 1, Section 3321;
Rooms Containing Fuel -fired Equipment and Cellulose Nitrate Handling Rooms,
556
3304 UNIFORM BUILDING CODE
3. Doors swinging g toward flow of traffic shall no( be
b 6 permitted for use by �
untrained pedestrian traffic unless actuating devices start to function at least 8 feet l l
inches beyond door in open position and guide rails extend 6 feet 5 inches beyond
door in open position.
Clearances for guide rails shall be as follows:
1. Six inches maximum between rails and leading edge of door at the closest
point in its arc of travel.
2. Six inches maximum between rails and the door in open position.
3. Two inches minimum between rail at hinge side and door in open position.
4. Two inches maximum between freestanding rails andjamb or other adjacent
surface.
(h) door Level at Doors. Regardless of the occupant load, there shall be a
floor oranan in�dfii Me of a door. When access for the physically handi-
capped is required by Section 3301 (e), the floor or landing shall be not more than
1/2 inch lower than the threshold of the doorway. When such access is not required,
such dimension shall not exceed 1 inch.
EXCEPTIONS: 1. In Groups R, Division 3 and M Occupancies and within
individual units of Group R, Division 1 Occupancies:
A. A door may open at the top step of a flight of stairs, provided the door does not
swing over the top step.
B. A door may open at a landing that is not more than 71/2 inches lower than the floor
level, provided the door does not swing over the landing.
C. Screen doors and storm doors may swing over stairs, steps or landings.
2. Doors serving building equipment rooms which are not normally occupied.
(i) Landings at -Doors, Landings shall have a width not less than the width of
the stairway or the width of the door, whichever is the greater. Doors in the fully
open position shall not reduce a required dimension by more than 7 inches. When
a landing serves an occupant load of 50 or more, doors in any position shall not
reduce the landing dimension to less than one half its required width. Landings
shall have a length measured in the direction of travel of not less than 44 inches.
EXCEPTION: In Group R, Division 3 and M Occupancies and within individual
units of Group R, Division 1 Occupancies, such length need not exceed 36 inches.
A landing which has no adjoining door shall comply with Section 3306 (g).
0) Door Identification. Glass doors shall conform to the requirements speci-
fied in Section 5406.
Exit doors shall be so marked that they are readily distinguishable from the
adjacent construction.
(k) Additional Doors. When additional doors are provided for egress pur-
poses, they shall conform to all provisions of this chapter.
560
EXCEPTION: Approved revolving doors having leaves which will collapse
under opposing pressures may be used in exit situations, provided:
L Such doors have a minimum width of 6 feet 6 inches.
2. At least one conforming exit door is located adjacent to each revolving door.
3. The revolving door shall not be considered to provide any exit width.
1985 EDITION
Corridors and Exterior Exit Balconies
3305
Sec. 3305. (a) General. This section shall apply to every corridor serving as a
required exit for an occupant load of 10 or more except as provided in Subsection
(b) for Group R, Divisions 1 and 3 Occupancies. For the purposes of the section,
the term "corridor" shall include "exterior exit balconies" and any covered or
enclosed exit passageway, including walkways, tunnels and malls. Partitions,
rails, counters and similar space dividers not over 5 feet 9 inches in height above
the floor shall not be construed to form corridors.
Exit corridors shall not be interrupted by intervening rooms.
EXCEPTION: Foyers, lobbies or reception rooms constructed as required for
corridors shall not be construed as intervening rooms.
(b tdth, Every corridor serving an occuuantt load of 10 or o pliall be not
I�,s than 44 orches in width. Regardless less occupant a , c rridors-in Group
R, Divis o 3 Occupancies and within dwelling units in Group R, Division l
Occupancies shall have ahuf3Wg. For special requirements
for Groups E and I Occupancies, see Sections 3319 and 3321.
(c) Height. Corridors and exterior exit balconies shall have a clear height of not
less than 7 feet measured to the lowest projection from the ceiling.
(d) Projections. The required width of corridors shall be unobstructed.
EXCEPTION: Handrails and doors, when fully opened, shall not reduce the
required width by more than 7 inches. Doors in any position shall not reduce the
required width by more than one half. Other nonstructural projections such as trim
and similar decorative features may project into the required width I1/2 inches on
each side.
(e) Access to Exits,When more than one exit is required, they shall be so
arrangectia�It is possible to go in either direction from any point in a corridor to a
separate exit, except for dead ends not exceeding 20 feet in length.
(f) Changes in Elevation. When a corridor or exterior exit balcony is accessi-
ble to the handicapped, changes in elevation of the floor shall be made by means
of a ramp, except as provided for doors by Section 3304 (h).
(g) Construction. Walls of corridors serving a Group R, Division 1 or Group I
Occupancy having an occupant load of 10 or more and walls of corridors serving
other occupancies having an occupant load of 30 or more shall be of not less than
one-hour fire -resistive construction and the ceilings shall be not less thati that
required for a one-hour fire -resistive floor or roof system.
EXCEPTIONS: 1. One-story buildings housing Group B, Division 4 Occupan-
cies.
2. Corridors more than 30 feet in width where occupancies served by such 1
corridors have at least one exit independent from the corridor. (See Appendix
Chapter 7, Division I, for covered malls.) ev
3. Exterior sides of exterior exit balconies.
4. In Group I, Division 3 Occupancies such as jails, prisons, reformatories and
similar buildings with open -barred cells forming corridor walls, the corridors and
cell doors need not be fire resistive.
561
1905 EDITION 3306
Stairways
Sec. 3306. (a) General. Every stairway having two or more risers serving any
building or portion thereof shall conform to the requirements of this section.
EXCEPTION: Stairs or ladders used only to attend equipment are exempt from
the requirements of this section.
(b) Width. Stairways serving an occupant load of 50 or more shall be not less
than 44 inches in width. Stairways serving an occupant load of 49 or less shall be
not less than 36 inches in width.
Handrails may project into the required width a distance of 342 inches from 49
each side of a stairway. Stringers and other projections such as trim and similar a
decorative features may project into the required width 11/2 inches on each side.
jhe rise of every step in a stairway shall be not less than 4
inches nor greater than 7 inches. Except as permited in Subsections (d) and (f), the p
run shall be not less than I I inches as measured horizontally between the vertical #`
planes of the furthermost projection of adjacent treads. Except as permitted in
Subsections (d), (e) and (f), the largest tread run within any flight of stairs shall
not exceed the smallest by more than 3/8 inch. The greatest riser height within any
flight of stairs shall not exceed the smallest by more than 3/8 inch.
EXCEPTIONS: 1. Private stairways serving an occupant load of less than 10 and
stairways to unoccupied roofs may be constructed with an 8 -inch maximum rise and
9 -inch minimum run.
2. Where the bottom or top riser adjoins a sloping public way, walk or driveway {
having an established grade and serving as a landing, a variation in height of the #<
bottom or top riser of not more than 3 inches in every 3 feet of stairway width is
permitted.
(d) Winding Stairways. In Group R, Division 3 Occupancies and in private
stairways in Group R, Division 1 Occupancies, winders may be used if the
required width of run is provided at a point not more than 12 inches from the side
of the stairway where the treads are the narrower, but in no case shall any width of
run be less than 6 inches at any point.
(e) Circular Stairways. Circular stairways may be used as an exit, provided
the minimum width of run is not less than 10 inches and the smaller radius is not
less than twice the width of the stairway. The largest tread width or riser height
within any flight of stairs shall not exceed the smallest by more than 3/8 inch.
(f) Spiral Stairways. In Group R, Division 3 Occupancies and in private
stairways within individual units of Group R, Division I Occupancies, spiral
stairways may be installed. Such stairways may be used for required exits when
the area served is limited to 400 square feet.
The tread must provide a clear walking area measuring at least 26 inches from
the outer edge of the supporting column to the inner edge of the handrail. A run of
at least 71/2 inches is to be provided at a point 12 inches from where the tread is the
narrowest. The rise must be sufficient to provide 6 -foot 6 -inch headroom. The
rise shall not exceed 91/2 inches.
r
(g) Landings. Every landing shall have a dimension measured in the direction
of travel equal to the width of the stairway. Such dimension need not exceed 44
563
1985 EDITION 3306-3307
Except when enclosed usable space under stairs is prohibited by Section 3309
(f), the walls and soffits of the enclosed space shall be protected on the enclosed
side as required for one-hour fire -resistive construction.
All required interior stairways which extend to the top floor in any building four
or more stories in height shall have, at the highest point of the stair shaft, an
approved hatch openable to the exterior not less than 16 square feet in area with a
minimum dimension of 2 feet.
EXCEPTION: The hatch need not be provided on smokeproof enclosures or on
stairways that extend to the roof with an opening onto that roof.
(n) Exterior Stairway Construction. Exterior stairways shall be of noncom-
bustible material except that on Types III and IV buildings not exceeding two
stories in height, and on Type V buildings, they may be of wood not less thati 2
inches in nominal thickness.
Exterior stairways shall not project into yards where protection of openings is
required.
Enclosed usable space under stairs shall have the walls and soffits protected on
the enclosed side as required for one-hour fire -resistive construction.
(o) Stairway to Roof. In every building four or more stories in height, one
stairway shall extend to the roof surface, unless the roof has a slope greater than 4
in 12. See Subsection 3306 (m) for roof hatch requirements.
(pLijeadroom. Every stairway shall have a headroom clearance of not less
than 6'fee Vin ji s. Such clearances shall be measured vertically from a plane
parallel and tangent to the stairway tread nosings to the soffit above at all points.
(q) Stairway Numbering System. An approved sign shall be located at each p
floor level landing in all enclosed stairways of buildings four or more stories in
height. The sign shall indicate the floor level, the terminus of the top and bottom F
of the stairway and the identification of the stairway The sign shall be located
approximately 5 feet above the floor landing in a position which is readily visible
when the door is in the open or closed position. Signs shall comply with require-
ments of U.B.C. Standard No. 33-2. F
Ramps
Sec. 3307. (a) General. Ramps used as exits shall conform to the provisions of
this section.
(b) Width. The width of ramps shall be as required for stairways.
(c) Slope. The slope of ramps required by Table No. 33-A shall be not steeper
than I vertical to 12 horizontal. The slope of other ramps shall not be steeper than
I vertical to 8 horizontal.
When provided with fixed seating, the main floor of the assembly room of a
Group A, Division 1, 2, 2.1 or 3 Occupancy may have a slope not steeper than I
vertical to 5 horizontal.
(d) Landings. Ramps having slopes steeper than 1 vertical to 15 horizontal
shall have landings at the top and bottom, and at least one intermediate landing
shall be provided for each 5 feet of rise. Top landings and intermediate landings
shall have a dimension measured in the direction of ramp run of not less than 5
565
i
4304-4305 UNIFORM BUILDING CODE
assigned fire -resistive rating will be the shortest duration obtained from the two
tests conducted in conformance with U.B.C. Standard No. 43-1. When evidence
is furnished to show that the wall was tested with the least fire -resistive side
exposed to the furnace, the building official may not require that the wall be
subjected to tests from the opposite side.
(e) Penetrations. Penetrations in walls requiring protected openings shall be
fire -stopped. Firestopping shall be an approved material securely installed and
capable of maintaining its integrity when subjected to test temperatures pre-
scribed in U.B.C. Standard No. 43-1 for the specific wall or partition.
Openings in walls and partitions shall be protected as specified in Section
4306. Where fire -rated walls and partitions require protected openings, the „
following penetrations into or through such construction are permitted:
1. Copper or ferrous pipes or conduits may penetrate the walls or partitions,
provided firestopping is provided in accordance with the first paragraph of this
section.
2. Openings for steel electrical outlet boxes not exceeding 16 square inches in
area, provided the area of such openings does not aggregate more than 100 square
incites for any 100 square feet of wall or partition area. Outlet boxes on opposite
sides of walls or partitions shall be separated by a horizontal distance of 24 inches. ti -
3. Where walls are penetrated by other materials or where larger openings are
required than permitted in Item No. 2 above, they shall be qualified by tests
conducted in accordance with the provisions of Section 4302 (b).
Floor -Ceilings or Roof -Ceilings
See. 4305. (a) General. Fire -resistive floor -ceiling or roof -ceiling construc-
tion systems shall be assumed to have the fire -resistance ratings set forth in Table
No. 43-C. Penetrations in floors and ceilings requiring protected openings shall
be fire -stopped. Firestopping shall be of an approved material, securely installed
and capable of maintaining its integrity when subjected to the time -temperature
curve of U.B.C. Standard No. 43-1 for the specific floor -ceiling or roof -ceiling
construction.
EXCEPTION: Where penetrations are protected as shaft enclosures as required
in Section 1706.
When materials are incorporated into an otherwise fire -resistive assembly
which may change the capacity for heat dissipation, fire test results or other
substantiating data shall be made available to the building official to show that the
required fire -resistive time period is not reduced.
(b) Floors. Fire -resistive floors shall be continuous and all openings for me-
chanical and electrical equipment shall be enclosed as specified in Section 1706.
614
EXCEPTIONS: 1. Occasional pipes, conduits, sleeves and electrical outlets of
copper, sheet steel or ferrous construction may be installed within or through fire -
resistive floorsystems, provided such installations do not unduly impair the required
fire resistance of the assembly.
2. The provisions of this section shall not apply when such openings are in =
accordance with the results of tests conducted pursuant to the provisions of Section
4302 (b).
CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS
February 20, 1996
Joe Laird, PE
City of Rexburg Building Official
PO Box 280
Rexburg, ID 83440
RE: Stephen Clark, et al. - Response to Appeal of Building Inspection
Dear Joe:
The Uniform Building Code Board of Appeals, duly established by action
Council, has met to consider an appeal made by Stephen Clark over the
Report of the Applewood Apartment located at 151 S 1st E in Rexburg.
wrresVeb-Ma1fd2.20
of the Rexburg City
Building Inspection
We have considered the Building Inspector's reports of February 9, 1996 for buildings 1A, 1B,
1C, 2, 3, and 4 in accordance with our authority as we understand it from the Code and have
made the following determinations:
1) The Building Official's reports appear to be in compliance with applicable provisions of the
Uniform Building Code and the inspections were not completed in an arbitrary nor
capricious manner.
2) Previous actions by the Building Inspector(s), the inspection process, the issuance of
permits, and the issuance of a certificate of occupancy do not absolve the building
owner(s) of the responsibilities to meet all applicable provisions of the Code. Specifically,
Section 307(f) gives specific authority to suspend or revoke a certificate of occupancy
issued under the provision of the Code whenever "...it is determined that the building or
structure, or portion thereof, is in violation of any ordinance or regulation or any provisions
of this (UBC) code".
If further action or information is required, please advise.
Sincerely,
CITY OF REXBURG UNIFORM BUILDING CODE BOARD OF APPEALS
Charles Cartmill
Winston Dyer
Ted Hill
Bart Stevens
John Watson
��EX9URG' o%�
U
9gCI5HE0
NILE L. BOYLE
IMYOR
ROSE BAGLEY
CLEPK
RICHARD HORNER
TAMURER 6 FINANCIAL OFFICER
Applewood Apts
c/o Steve Clark
625 South 5000 West
Rexburg, Idaho 83440
STATE OF IDAHO
March 8, 1996
Re: Building Inspection Results
Dear Mr. Clark:
P.O. BOX 280
12 NORTH CENTER STREET
REXBURG, IDAHO 83440
PHONE (208) 359-3020
FAX (208) 359-3022
As a result of the recent visit by the U.B.C. Appeals Board to your property known as
Applewood Apartments, the City of Rexburg has been made aware of possible problems in your
structures that go beyond the items identified in the February 9, 1996 letter from the City
Engineer.
The cumulative effect of the items brought to the City's attention by the U.B.C. Board,
and the items in the February 9th letter, leaves the City with no choice but to formally request,
that you obtain an evaluation, and advice from an independent source as to the structural and
mechanical integrity of the various buildings located on your property.
As has been discussed in the past, the City of Rexburg has an obligation to issue
occupancy permits to only those structures which are safe for habitation, and if it cannot be
determined that your structures fall within this category, it is possible that your occupancy permit
could be rescinded.
On behalf of the City of Rexburg, I would welcome the opportunity to meet with you and
your representatives, and discuss the findings of an independent architect or structural engineer
with respect to your property. If you have questions concerning what is being asked of you,
please don't hesitate to contact me during regular business hours at 359-3020 ext. 316.
Sincerely,
Stephen P. Zollinger,
Rexburg City Attorney
cc: Joe Laird, City Engineer
Nile L. Boyle, Mayor