I have attached a copy of the Fire Department review of the Apex site plan to the
back of this document. If you have any questions, please give me a call at 359-3020 ext.
324.
Sincerely,
Val Christensen
Building Official
REXBURG MADISON COUNTY FIRE
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code
Plan Review
Building Name: Apex Development Site Plan
Plan Date: 8-01
Review Date: 9-11-01
Building Address: Approximately 4th West and 6th South
Stories: U/R Type of Construction: U/R
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: Approximately 16,560 SQ. FT/Building
1).Required Fire Flow (Appendix III -A): 3,500 GPM for 3 Hours
Comments: This flow may be.reduced by 50% with the installation of
an approved sprinkler system in each building.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location
Fire Hydrant Flows: N/A
Fire Flow Test Location:
Fire Flow Supplied By:
One Existing, Five proposed
Other Approved Water Source: NONE
Water Supply Acceptable: NONE
Fire Hydrant Location Acceptable: NO
Water Supply Comments: Additional hydrants need to be installed
throughout complex OR fire sprinkler systems installed in each
building.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable Width: YES Length: YES Surface: OKAY
Turning Radius: OK Grade: OK Vehicle Vertical: U/K
Clearance: U/K Turn Arounds: YES
Complete Road Acceptable: YES
Comments:
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: Both must be installed and made serviceable prior to
construction or a stop work order will be issued.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: NOT SHOWN
Type Provided Acceptable: Minimum size is 2A-10BC extinguisher
Comments:
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: Unknown at this time Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Standpipes (Article 10 Section 1004) Required:
Type Required: Unknown at this time Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: Unknown
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
Comments:
9).Fire Alarm Systems (Article 10 Section 1007)Required: Unknown
Type Of System Required: Manual: Automatic: Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System Shown: Smoke Detectors: Heat Detectors:
Manual Pull Station: Sounding Devices: Visual Devices:
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable:
10).Other Corrections That Are Required By Special Occupancy Or
Conditions:
Plans As Submitted Are Acceptable: NO
Plans Checked By: Chris Huskinson Date: 9-11-01
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES
9/7/2001
Curt Rowland
Forsgren Engineering
350 North 2"d East
Rexburg, Idaho 83440
Dear Curt,
I have reviewed the site plan for Apex Development and have identified the
following discrepancies:
1.
— Clearly identify 5' sidewalks along 4'h West.
2.
Provide cross section details for 6`h South and 4`h West. 6`h South is to be
a 44' wide residential cross section. 4th West is to match the existing
street and is a 38' wide cross section with curb and gutter on the East side
only.
3.
Please identify the areas of street construction and the amount provided by
the developer.
4.
Show all dimensions. Include the dimensions from the buildings to the
property lines. Include dimensions to right-of-way, sidewalks, streets, etc.
5.
Identify 71h South on sheet no. P-2.
6.
The trash bin configuration will not work using City of Rexburg service.
Our trucks are side pick-up type and require that dumpsters be parallel to
aisle with room for approach.
7.
The painted walkway from the south portion of the project to the
clubhouse will not be allowed. Please remove it from the plans. The
crosswalk at 0 West will have to do for pedestrian traffic.
(j 8.
Please identify handicap ramps. On handicap ramp detail, please show the
tooling required for the blind as per the Americans with Disabilities Act
`J�
0
(ADA).
Jr 9.
Provide details for inlet at 36" concrete sewer pipe from city ditch.
CR 10.
Provide pump and vault details for the transfer of storm water to canal.
-• Please identify if approval has been given from the canal company for use.
11.
Identify easements across 6`h South and 4th West for all utility lines.
Include dimensions to easements and dimensions of easements.
12.
— Identify location and size of service lines to the buildings.
13. Include the size of water lines. Show the location and size of the existing
16" water main in 6'h South. Also show a 16" water line connecting at 6`h
South and running south to connect with the existing water line in 7`h
South. The City of Rexburg will reimburse the developer for the
additional cost of providing this 16" line.
14. Identify existing electrical, telephone, etc. lines. Also show all new utility
locations, including the size and location of their easements.
15. Identify additional catch basins. The current drawings identify only one
catch basin on 40' West. Include the size and locations of all storm drain
pipes to the catch basins.
16. - I have attached a copy of the City of Rexburg Commercial Driveway
Approach Construction Details to the back of this document. Please show
rebar as per the specs in the curb/gutter, driveway approach and the
sidewalk crossing the approach. Also please identify 6" of crushed gravel
under all sidewalks within the City of Rexburg right-of-way. Show the
approach aprons on the site plan. The current plans show the approach
ending at the right-of-way.
17. - Please identify handicap parking and the access from parking to the
buildings. Include any ramp locations.
18. --Provide parking aisle dimensions and the size of spaces.
19. Provide calculations for storm water retention system. - ?
-%.20. -Include lighting plan for parking lot and streets.
21. At this time I do not have any building plans, so I can't identify if the
amount of parking is adequate.
22. The Fire Department has not finished their review of the plan and may
have additional requirements.
Please provide me with 2 new copies of the corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
9/26/2001
Curtis Miner
357 East 1200 South
Orem, Utah 84058
Dear Curtis,
STATE OF IDAHO
www.ci.rexburg.jd.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburg.id.us
I have reviewed the plans for the Apex Development and have identified the
following discrepancies:
1. Provide details that identify balcony wall and ceiling construction as per
Section 1006.3.2.3 of the 1997 Uniform Building Code (UBC)
2. The room labeled as "Niche" is not large enough to be considered a habitable
room. Section 310.6.2 of the 1997 UBC requires that habitable rooms be at
least 70 square feet. Section 310.6.3 of the 1997 UBC requires that habitable
rooms shall not be less than 7 feet wide. Please resize this room or remove it
and re -label the units as 1 -bedroom.
3. The ADA Type B bathroom details on sheet A1.3 do not seem to meet the
requirements for forward approach to the bathtubs as per Section 1106.6. of
the 1997 UBC.
4. Please have the structural engineer provide calculations for the masonry
columns that hold up the entry roof.
5. Please provide plans for clubhouse.
6. The Fire Department has reviewed the drawings and has identified some
discrepancies. I have attached a copy of their list to the back of this
document.
I have also attached a copy of Forsgren Engineering's site plan review to the back
of this document. Please provide me with 2 new copies of the corrected plans. If you
have any questions, please give me a call at 359-3020 ext. 324.
Sincerely,
r �-
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
1997 Uniform Fire Code Plan Date: 9/01
Plan Review Review Date: 9/20/01
Building Name: Newport Condos
Building Address: 300 Block of West 7th South
Stories: Three Type of Construction: V -N
Occupancy Classification: R-1 Existing Floor Area: N/A
New Construction Floor Area: Approximately 190,000 total square
feet, 14,661 square feet each unit in addition to clubhouse.
1).Required Fire Flow (Appendix III -A): Approximately 3,250 GPM/
3 hours
Comments: Fire flow needs to be verified in writing PRIOR to
construction. Plans for Clubhouse not included, not able to make an
accurate determination of required fire flow. Water supply may be
reduced by 75% if the buildings have an approved automatic
sprinkler system.
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: One existing
Fire Hydrant Flows: U/K
Fire Flow Test Location: N/A
Fire Flow Supplied By: N/A
Other Approved Water Source: NONE
Water Supply Acceptable: NO
Fire Hydrant Location Acceptable: NO
Water Supply Comments: Previous site plan has shown some proposed
hydrants. This plan has no hydrants shown. Based on estimated
square footage this project requires a total of at least five new
hydrants distributed throughout complex with spacing of 350 feet or
less.
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES
Turning Radius: U/K
Clearance: U/K
Length: YES Surface: U/K
Grade: U/K Vehicle Vertical: U/K
Turn Arounds: OK
Complete Road Acceptable: YES
Comments: NONE
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES
Comments: Both hydrants and vehicle accessible roads must be
installed and made serviceable PRIOR to construction or a stop work
order will be issued.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: Not Shown
Type Provided Acceptable: Not Shown
Comments: Please provide minimum size of 2A-10BC fire extinguisher
in each unit as per 1997 UFC and City of Rexburg Life Safety
Ordinance. Fire extinguisher placement in Clubhouse unknown at this
time. Notes on A1.4 for mounting of fire extinguisher in ADA
apartments too high.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments: Not required based on one hour separation between
dwelling units and two hour area separation between units.
7).Standpipes (Article 10 Section 1004) Required: NO
Type Required:
Comments:
8).Ventilating Hood And Duct Fire Extinguishing System (Article 10
Section 1006.2) Required: NO
Type Being Provided:
Automatic Fuel Shutoff Shown (Article 10 Section 1006.2.4):
Portable Fire Extinguisher Shown (Article 10 section 1006.2.7):
9).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type Of System Required: Manual: YES Automatic: Both:
Type Of System Being Provided: Manual: Automatic: Both:
Components Of System Shown: Smoke Detectors: YES Heat Detectors:
Not Shown
Manual Pull Station: Not Shown
Visual Devices: Not Shown
Sounding Devices: Not Shown
Door Holders: Duct Detectors: Flow Alarm:
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: A manual fire alarm system shall be installed. System
shall meet ADA requirements in handicapped apartments which include
horn/strobe units and activation by smoke detectors and building
alarm system. System shall also include heat and smoke detectors in
common areas (laundry, computer rooms, etc.), horn/strobe units
throughout complex with minimum audibility requirements in each
dwelling unit. Plans for fire alarm system shall be submitted for
review and approval PRIOR to system installation. Plans and
specifications shall include, but not be limited to, a floor plan;
location of all alarm initiating and alarm -signaling devices; alarm
control and trouble signaling equipment; power connection; battery
calculations; conductor type and sizes; voltage drop calculations;
manufacturer; model numbers and listing information for all
equipment, devices and materials. I will also need the number of
devices per circuit, manufacture cut sheets on all fire alarm
equipment, shop drawings, wire run length, and voltage drops. There
may be additional ADA requirements.
10).Other Corrections That Are Required By Special Occupancy Or
Conditions: Provide plans for Clubhouse.
Plans As Submitted Are Acceptable: NO
Plans Checked By: Chris Huskinson Date: 9/21/01
Please furnish comments back to the plan reviewer in the following
manner: written Comments: YES New Plans: YES
9/7/2001
,curt Rowland
Forsgren Engineering
350 North 2nd East
Rexburg, Idaho 83440
Dearkurt,
STATE OF IDAHO
www.ci.rexburgJd.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg*ci.rexburg.id.us
I have reviewed the site plan for Apex Development and have identified the
following discrepancies:
1. Clearly identify 5' sidewalks along 4's West.
2. Provide cross section details for 60' South and 4`I' West. 6a' South is to be
a 44' wide residential cross section. 4t° West is to match the existing
street and is a 38' wide cross section with curb and gutter on the East side
only.
3. Please identify the areas of street construction and the amount provided by
the developer.
4. Show all dimensions. Include the dimensions from the buildings to the
property lines. Include dimensions to right-of-way, sidewalks, streets, etc.
5. Identify 7s South on sheet no. P-2.
6. The trash bin configuration will not work using City of Rexburg service.
Our trucks are side pick-up type and require that dumpsters be parallel to
aisle with room for approach.
7. The painted walkway from the south portion of the project to the
clubhouse will not be allowed. Please remove it from the plans. The
crosswalk at 4"' West will have to do for pedestrian traffic.
8. Please identify handicap ramps. On handicap ramp detail, please show the
toolingrequired for the blind as per the Americans with Disabilities Act
(ADA).
9. Provide details for inlet at 36" concrete sewer pipe from city ditch.
10.. Provide pump and vault details for the transfer of storm water to canal.
Please identify if approval has been given from the canal company for use.
11. Identify easements across 6h South and 4`s West for all utility lines.
Include dimensions to easements and dimensions of easements.
12. Identify location and size of service lines to the buildings.
13. Include the size of water lines. Show the location and size of the existing
16" water main in 6h South. Also show a 16" water line connecting at 6a'
South and running south to connect with the existing water line in 7`'
South. The City of Rexburg will reimburse the developer for the
additional cost of providing this 16" line.
14. Identify existing electrical, telephone, etc. lines. Also show all new utility
locations, including the size and location of their easements.
15. Identify additional catch basins. The current drawings identify only one
catch basin on 4s' West. Include the size and locations of all storm drain
pipes to the catch basins.
16. I have attached a copy of the City of Rexburg Commercial Driveway
Approach Construction Details to the back of this document. Please show
rebar as per the specs in the curb/gutter, driveway approach and the
sidewalk crossing the approach. Also please identify 6" of crushed gravel
under all sidewalks within the City of Rexburg right-of-way. Show the
approach aprons on the site plan. The current plans show the approach
ending at the right-of-way.
17. Please identify handicap parking and the access from parking to the
buildings. Include any ramp locations.
18. Provide parking aisle dimensions and the size of spaces.
19. Provide calculations for storm water retention system.
20. Include lighting plan for parking lot and streets.
21. At this time I do not have any building plans, so I can't identify if the
amount of parking is adequate.
22. The Fire Department has not finished their review of the plan and may
have additional requirements.
Please provide me with 2 new copies of the corrected plans. If you have any
questions, please give me a call at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
C.C. John Millar
Chris Huskinson
11/14/2001
Ross Farmer
456 East 2"d South
Rexburg, ID 83440
Dear Ross:
cily 012exiary
STATE OF IDAHO
www.ci.rexburaJd.us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburg.id.us
I have reviewed the plans for the 2"d phase of the Avonlea Apartments and have
identified the following discrepancies:
I. The parking lot should not be drained using French drains. There is a
storm sewer line adjacent to the property. Catch basins should be
installed and connected to the existing storm sewer.
2. Please identify handicap parking spaces. Include space sizes, details of
access from parking lot and any markings or signs.
3. Page A8 identifies wind speed at 70 mp.h.. Our design wind speed is
80 m.p.h.. Please redo calculations based on higher wind speed and
make any necessary changes to the plans.
4. Identify smoke detectors and fire extinguishers as per the review from
the Fire Department that is attached to the back of this document.
5. Please identify at least one "Type A" handicap accessible unit. Identify
special features such as clearance for water closet, sink heights,
accessible cabinets, horn strobes (as per Fire Department review), etc.
6. Please identify sill height on 3' high egress windows. The maximum
sill height for an egress window is 44" from floor.
7. Provide truss details prior to frame inspection.
8. Electrical review must be performed by the State of Idaho.
The structural notes are cut off on page A8. I can't identify shear wall nailing.
Make the necessary changes to the plans and return two copies. If you have any
questions, I can be reached at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
cc: John Millar
Chris Huskinson
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(2 08) 359-3010
1997 Uniform Fire Code Plan Date: 6-01
Plan Review Review Date: 11/02/01
Building Name: Avonlea Apartments 2
Building Address: Second West and Third South
Stories: 2.5 Type of Construction: V -N
Occupancy Classification: R Existing Floor Area: N/A
New Construction Floor Area: Approximately 14,500 square feet/
4,800 sq. feet per floor
1).Required Fire Flow (Appendix III -A): 1750 GPM/2 Hours
Comments: Flow may be reduced by up to 50% if an approved automatic
sprinkler system is installed
2).Water Supply (Article 9, Section 903) Required: YES
Fire Hydrant Location: Second West, Third South
Fire Hydrant Flows: OK
Fire Flow Test Location: Same
Fire Flow Supplied By: FD
Other Approved Water Source: None
Water Supply Acceptable: YES
Fire Hydrant Location Acceptable: YES
Water Supply Comments: N/A
3.)Fire Apparatus Access Roads (Article 9 Section 902)
Required: YES
Acceptable: Width: YES
Turning Radius: OK
Clearance: OK
Length: OK Surface: OK
Grade: OK Vehicle Vertical: OK
Turn Arounds: OK
Complete Road Acceptable: YES
4).Access Roads and Water Supply, Including Fire Hydrants Are
Required To Be Installed And Made Serviceable Prior To And During
Time Of Construction (Article 9 Section 901.3): YES, if not
installed PRIOR to construction a STOP WORK order will be issued.
5),Installation Of Portable Fire Extinguisher (Article 10 Section
1002) Required: YES Location Acceptable: Not Shown
Type Provided Acceptable: Not Shown
Comments: Each unit shall have a minimum of one 2A-10BC fire
extinguisher mounted on the wall in an accessible location.
6).Automatic Fire Extinguishing Systems: (Article 10 Section 1003
Required: NO Type Of System Being Installed:
Sprinkler System Monitoring Required (Article 10 Section 1003.3)
Required:
Comments:
7).Fire Alarm Systems (Article 10 Section 1007)Required: YES
Type
Of
System
Required: Manual: Automatic: YES
Both:
Type
Of
System
Being Provided: Manual: Automatic:
Both:
Components Of System Shown: Smoke Detectors: Not Shown, required
Manual Pull Station: Sounding Devices: YES Visual Devices:
YES
Sprinkler Valve Monitoring: Fire Alarm System Acceptable: NO
Comments: Plans did not shown handicap units. If units are being
provided need horn/strobe alarms in those units in addition to
smoke detectors. Plans state smoke detectors to be provided in each
bedroom and one in each living room/kitchen area. Detectors are not
required in living room/kitchen area but are in hallways outside of
bedrooms. Minimum of two detectors in each hallway outside of
sleeping rooms.
Plans As Submitted Are Acceptable: NO
Plans Checked By: Chris Huskinson
Date: 11/05/01
Please furnish comments back to the plan reviewer in the following
manner: Written Comments: YES New Plans: YES