Friday, March 24, 2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla,
For the past few months I have been inspecting the ongoing construction taking
place at the American Manor Apartments. Your contractor, Scott Caffaro seems to
be doing a good job and has been pleasant to work with. He has addressed the
issues I have needed taken care of promptly. Your request for Conditional
Occupancy can be met by meeting the schedule which I have attached to this letter.
I have tried to set the schedule to meet your needs in performing some of the
interior work during the break between college semesters.
Thank you for your consideration in these matters. If you have any questions, I
can be reached at 359-3020 ext. 314.
Sincerely,
Val Christensen
Assistant Engineer
A1MERICAN MANOR APARTMENTS - SCHEDULE FOR CONDITIONAL
OCCUPANCY
The following is a list of items that have not been finished at the American Manor
Apartments. Each unfinished item is listed along with required date of completion.
1. Building #4 laundry headroom Sign shall be posted at entry of laundry.
Sign shall read "Low Head Clearance" and shall state the actual height of
the ceiling. The letters shall be 1" high. Also fluorescent striped warning
tape shall be applied to the ends of all of the light fixtures which extend
below ceiling. Completion Date — 3/27/00
2. Railing missing at concrete stairs behind Buildings #3 and #4. Add railing
as per code. Completion Date — 3/27/00
3. Building #1-B, Building #3 and Building #4 mechanical rooms must be
separated from dwelling units with one layer of 5/8" type X drywall.
Completion Date — 3/27/00
4. Enclosed area between Building #3 and Building #4. The enclosed area
must be constructed to meet corridor requirements. The floor will be
covered with %" duro-rock and then covered with ceramic tile. All
windows must be changed out to meet'/4 hour fire resistance. All doors
must be changed out to meet 20 minute fire resistance. Completion Date —
4/29/00
5. Building #1-B, Building #3 and Building #4 fire walls and ceiling
separation must be completed. All walls that separate dwelling units must
have one layer of 5/8" type X drywall added on walls and ceilings. The
walls must continue in the attic withtwo layers of 5/8" type X drywall
continuous to roof sheathing. Completion Date — 8/27/00
6. The egress windows in Building #I -B have not been completely changed
out. Completion Date — 8/27/00
7. Metal drain cover in sidewalk at Northwest corner of Building #IA creates
tripping hazard. Discuss plans for eliminating hazard with City Engineer
prior to repair. Completion Date — 6/30/00
8. Drainage System is required for entire complex. The current system is
inadequate and will only become worse as more grass and landscaped
areas are removed and more asphalt parking is added. The owner must
provide city with a drainage plan. Completion Date — 6/30/00. Drainage
System construction should be started as soon as possible and continued
until parking lot is reconstructed. Completion Date — 8/31/04
9. Retaining wall at North property line. Drainage system should be installed
North of Building #1 prior to the retaining wall construction. Completion
Date — 5/31/02
10. Parking lot is not currently configured to allow for Fire Department
access. The lot has a long term plan for complete renovation. Until the
changes are made, the lot must be reconfigured to meet Fire Department
standards. Completion Date — 6/30/00
11. All repairs must be made to Buildings #1-C and #2 prior to occupancy.
The repairs include but are not limited to stair reconstruction, firewall
construction, smoke alarms, window replacement, mechanical room
drywall repair, 2 -hour separation walls at #1 -A/#1 -B/#1 -C common walls,
exterior siding, etc.. In whole, the units must have all the punchlist items
complete from the Joe Laird List. Completion Date — 8/31/05
As per the above list, a Conditional Occupancy has been given to
Buildings #1B, #1C, #2, #3 and #4 only. Building #lA is not included in this
Conditional Occupancy. All repairs must be completed by schedule or have the
Rexburg City Engineer sign a change in schedule. All punchlist items including
parking lot reconstruction, drainage and retaining wall must be completed prior to
the City of Rexburg issuing a Final Occupancy for the entire complex.
September 14, 2000
Sharon Tuckett
Housing Director
196 Kimball Building
Ricks College
Rexburg, Idaho
83460-1045
Re: American Manor Apartments
Dear Sharon:
P.O. Box 280
0 12 North Center Street
Rexburg, Idaho 83440
STATE OF IDAHO Phone (208) 359-3020
Fax (208) 359.3022
e-mail rexburg@srv.net
This letter is to inform the college that
schedule American Manor Apartments is in compliance and on
with the repairs to the aparttnentcomplex that were listed in eartiercorr'flee astheesponde
11 item list for Conditional Occupancy.
.Apartments IE, 2E, 1F, 2F, and 3F have been approved for conditional occupancy by the City of
Rexburg.
The reconstructed portion of the prior existing parking lot and parking plan for the old portion of
the tot has been approved by the City of Rexburg.
Sincerely,
ohn W. Millar
ubfic Facilities Coordinator
OF��URG�O
0
p�
O Q 4
v p
4eCISHEO
September 14, 2000
Sharon Tuckett
Housing Director
196 Kimball Building
Ricks College
Rexburg, Idaho
83460-1045
Re: American Manor Apartments
Dear Sharon:
m/ V U.texQ!/MP
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone(208)359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
This letter is to inform the college that American Manor Apartments is in compliance and on
schedule with the repairs to the apartment -complex that were listed in earliercorrespondence as the
11 item list for Conditional Occupancy.
Apartments IE, 2E, 1F, 2F, and 3F have been approved for conditional occupancy by the City of
Rexburg.
The reconstructed portion of the prior existing parking lot and parking plan for the old portion of
the lot has been approved by the City of Rexburg.
S' rely, /r
Vo W i11arP.E./i:S.
Public Facilities Coordinator
DATE: (082300)
PLANNING & ZONING
August 23, 2000
7:00 p.m.
Present: Chairman:
Davawn Beattie
Members:
LaDawn Bratsman
Ted Whyte
Raymond Hill
Doug Smith
Mike Thueson
Roger Muir
Bobbette Carlson
Riley Bowman
City Clerk:
Marilyn Hansen
P.F.C.:
John Millar
Council Member:
Donna Benfield
City Attorney:
Stephen Zollinger
Excuse John Watson
Ted made a motion to approve the minutes of August 9, 2000, Bobbette seconded motion. All
voted aye, none opposed.
Public Hearing for Glen Reed for zone change at 41" West
Stephen read the Notice of Public Hearing. John reviewed and described the location of the
property, between 4`" and 5h South along the canal on the east side of the road and the proposed
tentative plans of Mr. Reed.
Davawn opened the public hearing.
Janice Allison - 405 W. 4' South
She lives across the street from the mentioned property and questioned what the plans are for this
location. This area is highly residential and she does not feel the street can handle the additional
traffic, the road is dangerous, there is a hazardous corner and there are a lot of accidents at that
location.
No fiirther comment and the public hearing was closed.
Discussion was on this property being left HBD, depending on the business that might go in it
could create more traffic than apartments would and the need to address the road and bridge as a
safety hazard.
Mike made a motion to approve the zone change from HBD to HDR and send on to public
hearing with the City Council. Doug seconded motion, all voted aye, none opposed.
Todd Hill - Zone Change at 10 Barney Dairy Road
John showed an aerial map showing the location of this property south of Barney Dairy Road and
east of 3rd East across the road from District 7 Health. This parcel is currently zoned industrial
and they are requesting a change to HBD.
Ray Walker owns the property and felt good about the change. He feels it can't be used for an
industrial use anyway and this proposal would be a good use of the property.
Nannette Hill, wife of Todd, presented a new drawing showing the proposed use of the land.
Roger made a motion to send this request to public hearing, Ted seconded the motion. All voted
aye, none opposed.
Bonnie Rice - 502 E. I' North - CUP for apartment
John related the history of the property in question located on the corner of Millhollow and 1,`
North. It has a 3 car garage, circular driveway, basement is a half basement with egress windows
and in the past was used as a separate living residence. The property is located in LDRI and does
require a conditional use permit.
Bonnie states that 2 cars will be in the garage and the driveway is large enough to allow 2 cars,
giving this parcel ample parking. The plan is to use the apartment for 4 students. A person can
crawl out of all the bedrooms windows, the Fire Department has been there to check all the
smoke alarms.
Doug made a motion for this request for a conditional use permit to go to public hearing with a
condition that it meet the building standards. Motion was seconded by Bobbette. All voted aye,
none opposed.
Gene Palmer preliminary plat approval for Hidden Valley Estates subdivision.
Boyd Cardon presented the plat and explained where the second phase would be located in
comparison to Phase I. There is a ditch along the property which is owned by Woodmansee-
Johnson Canal Company which is used basically for drainage but will be kept opened.
The plat needs information which is defined in the Subdivision Ordinance as well as showing
drainage, water and sewer. The property also needs to go through the annexation process. There
was discussion concerning the roads, sewer, water and other missing items.
2
Mike made a motion to table this for further details and paper work. Ted seconded the motion.
All voted aye, none opposed.
Tamla Rencher - American Manor Parking Lot
This project was before Planning & Zoning approximately a month ago. Due to timing problems
in getting this ready for rental this fall it has moved ahead out of necessity. There are items still
outstanding, including the buffer area on the south, and the retaining wall on the north side. The
parking for the dentist office, which will remain a dentist office for 4 years had no off-street
parking before and cannot now be required to be added in. There was discussion on the amount
of parking, the landscape, how much better the parking lot is now than it ever has been and the
efforts in trying to work with them to get this long standing problem cleared up. There are issues
still remaining to be cleared up with the neighbors.
Chris and Barbara Mann, neighbors, expressed concern that it be completed and completed nicely.
Stephen assured the neighbors this will not be approved and still rentable without all the issues
resolved. He explained the efforts that have been made in meeting with her regularly to work
with her in an effort to clear this matter up.
No action could be taken, Planning & Zoning just needs to be kept informed.
Davawn discussed the upcoming proposed changes to the Parking Ordinance. Bryce Owen from
Ricks College was invited to join in the discussion. After a lengthy discussion, it was determined
to keep the suggested parking requirements in place until the public hearing which will take place
on September 13.
Meeting was adjourned.
AUG -01-00 03:34 PH
885 N. Capkal
Idaho Fells, ID
93402
Phone: 208-524-0212
Fax: 20"2"220
Fax
HORPER—LERVITT
T•' Val Christensen
F•jq 359.3022
524 0229
P. 01
Harper -Leavitt
Engineering
From, Jeff Freiberg
Date: August 1, 2000
Phone; 359-3020
P•gset 13 indudIng cover
R•r Tamla Rancher Relaining Walls CCr
0 Urgent 0 For Review 0 Pleaee Comment 0 Pleas• Reply 0 Please Reeyele
•Cwnmentsl Val, Call me with any comments. Thank you. Jeff Frelberg
AUG -01-00 03:35 PM HARPER-LEAVITT 524 0229 P.02
Hager Leavitt Engineering
985 N. Capital
Idaho Falls, 10 63402
0208)-524-0212
ax: (208)•5240229
Retained Height
4,05 a
Well height above soll
0.35 R
Slope Behind Weil
0.00:1
Height of $011 over Toe r
7.00 in
Soil Denney .
11000 pct
Wind on Stem a
0.0 psf
Surcharge Loads
RoWnpro Basic S.OJ, a,1ur-o9, (o)11
Surcharge Over Heel -
0,0pu f
Used To Reslst Sliding a Overturning
Surcharge Over Toe
0.0 paf
Used for Ending a Overtuming
'ted
Axial Load Applied to Stem
Axial Dead Load
20.0 The
Axial Live Load a
20.0 Ibe
Avlal Load Frrantdctty .
0.0 In
Design Summary -�
Fooling Thiclvraes a 12.00 In
Total Bearing Load •
3,064 lbs
...resultant *cc.
7.91 In
Sell Pressure Q Toe
1,392 per OK
Soil Pressure a Heel
50 psf OK
Allowable
1,600 Pot
Soil Pressure Less Than Allowable
Moment.... Actual
ACI Factored Q Toe
1,945 pef
ACI Factored flif Heel =
70 per
Footing Shear Q Toe .
14.5 psi OK
Footing Shear Q Heel -
9.8 psi OK
Allowable •
93.1 gel
Wall Stability Ratios
BLEI Bar Develop ABOVE Ht.
Overturning
2.07 OK
Sliding
0.82 UNSTA
Sliding Calve Slab Reslsts All Sliding I
Lateral Sliding Force . 1,403.8 be
Allow Solt Dealing
EquWlent Fluid Press
Heel Active Pressure
TOO Active Pressure
Passive Pressure
Water height over hoer
FsotingllSOlf Friction
Soil height to Ignore
for passive pressure
Title Rancher 5 Foot Ret. Wall
Jab N 2000580--traonc Jeff Fmlb Oats- AUG 1,2000
Descdptfon....
an wesrgn
RoWnpro Basic S.OJ, a,1ur-o9, (o)11
Load
Footing Strengths 3 Dimefif
.war_
a
- 1,600.0 per
1`0 - 3,000 per FY - 80,000 p
'ted
Min. As % 0.0018
35.0 Pettit
Toe Width . 1, R
• 35.0 psftrt
• 250.0 peftfl
Heel Width • 2.50
--4$`
• 0.0 a
Total Footing Width •
= 0.300
Fooling Thiclvraes a 12.00 In
0.00 In
Lateral Load Applied to Siem
Lateral Load 0.00/it
...Height to Top 0.00 it
...Height to Bottom • 0.00 R
Key Width • 12.00 In
Key Depth 0.00 In
Key Distance from Toe a 1.75 it
Cover Q Top • 2.00in Q Btm.• 3.00 In
(Ad cent Footing
Load
•
scent not ng Loan
a
3.000.0 lba
Footing Width
TAlokneoe
2.00 R
Eccentricity
Reber Size
0.00 In
Wall to Fig CL Dist
Reber Spacing
0.00 rt
Footing Type
Rebar Placed at
Line Load
Base Above/Below Sell
Design Data
Medlwo Walght
at Back of Well
fblFS • fa/Fa
o.b rt
Stem Construction
Top Stem_
Design heightR
•
Stem
00
Wall Material Above "Ht"
•
Concrete
TAlokneoe
Actual t -Way Shear
8,00
Reber Size
93.11 93.11 psi
0 6
Reber Spacing
a
18.00
Rebar Placed at
•
Edge
Design Data
Medlwo Walght
CfccreteData -
fblFS • fa/Fa
a
0.682
Total Force Q Section
Ills •
2,104.7
Moment.... Actual
R41=
4,805.0
Moment..... Allowable
7,044.3
Shear..... Actual
pal •
31.2
Shear..... Allowable
pal-
03.1
BLEI Bar Develop ABOVE Ht.
In •
25.83
Footing Design Results
Factored rreaoun)
Too KH1
1.908 70 psf
MV: Upward
2,655 570 R-#
Mu,: Downward
459 2,042 R4
Mu: Design
2,128 1,471 rt -s
Actual t -Way Shear
• 14.46 9.59 psi
Allow 1 -way shear
93.11 93.11 psi
Toe Reinforcing
Sp0'Odln
: N
Heel Reinforcing
one
Q
Key Reinforcing
• None Spae'd
Bar Lap/Fink BELOW Ht. In. 7.71
Wall Weight
= 100.0
Rebar Depth 'd'
in • 5.83
Masonry Data --
--------
fm
pal=
Fs
pal
Solid Grouting
=
special inspection
Mudular Retlo'n'
Short Term Factor
Equiv. Solid Thick.
Masonry Block Type a
Medlwo Walght
CfccreteData -
pal= 3.000.0
Fy pal • 00,000.0
Mer Acceptable Sizes b Spaelnae
Toe: Not rev'd, Mu 6 • Fr
Heel: Not req'd, Mu < SFr
Key: Slab Resists Sliding - No Force on Key
nUG-01-00 03:35 PM HARPER—LEAVITT
524 0229 P. 03
Harper Leavitt Engineering
985 M Capltxl
Idaho Fella, ID 83402
(208)-524-0212
Fax: (208)-524-0229
ounllnery 01 overturning R Resisting Forms -LN
Vedicel Loads used for Soil Pressure a 3,084.9 Ibe
Vertical component of active pressure used for loll pressure
Title ; Rancher 6 Foot Ret. Wall
Job .2OU0660 Dsgnr; Jeff Frelb Date: AUG 1,M
Description....
Wall In
Retalri Basic 5.0.7, 8 -Jul -98, (c)1
.......- _.
Forco
.,,..OVERTURNING.....
Mertrent
Item
— .. Ibe
Fore o
Distance
Moment
_...
3.33
The
R
nw
Host Active Preaeum
-
50.6
186
1.062.1
Toe Active Pressure
s
-43.9
0.53
.23,2
Surcharge Over Toa
a
2.118
41 7
Soil Over Toe
Adjacent Footing Load
a
889.0
3.50
3,115.8
Added t■taml Lead
r
Stem Welght(s)
Load (0 Stem Above Sell
.
500,0
.
2.08
1,041.7
SsiamlcLoad
■
2.13
1,354.7
Key Walght
Total
s
1,403.8
O.T.M. a
4,144.7
Reslstingl0verturning
Ratio
2,07
Vedicel Loads used for Soil Pressure a 3,084.9 Ibe
Vertical component of active pressure used for loll pressure
Title ; Rancher 6 Foot Ret. Wall
Job .2OU0660 Dsgnr; Jeff Frelb Date: AUG 1,M
Description....
Wall In
Retalri Basic 5.0.7, 8 -Jul -98, (c)1
.......- _.
Forco
_;. jw.....
Distance
Mertrent
— .. Ibe
it
Rao
Soil Over Hest
- 937.8
3.33
3,125.8
Sloped Soil Over Heel
■
Surcharge Over Heal
e
Adjacent Footing Load
a 881.1
3.33
2,270.4
Axial Dead Lead on Stem
a 20,0
2.118
41 7
Soil Over Toe
112,3
0.88
98.3
Surcharge Over Tae
Stem Welght(s)
Earth IM Stem Transitions
500,0
.
2.08
1,041.7
Footing Weight
. 837,5
2.13
1,354.7
Key Walght
Vert. Component
:
225
155.7
'
425
661.7
Tota'
3.044.3 IIx
R.M.-
S,SO4.2
AUG -01-00 03:36 PM HARPER—LEAVITT 524 0229 P.04
Sk&g Reslrshl
2.h Cm'.Iaga I a I. k
MOea Orin
(2Tae
Oldwa select
N6@I8.h dhoriz. rehl.
(wHeel See APPI.&A
i'4•
rj K'ccT w%1,1,
2'
m
AUG -01-00 03:36 PM HARPER—LEAVITT 524 0229
P.05
Sidng AeflraW
A4 Hp U&d - 30004
Emu O.n 6mn CL
Pp= J 13,37#
PPPPOPSP2�4pf JSS'64#
1392,2pd
RUG -01-00 03:37 PH
Harper L03YM Engineering
965 N. Capital
Idaho Falls, IU 83402
1208)-5240212
ax; (208)524-0229
HARPER-LEAVITT 524 0229 P.06
Title ; Rancher i foot"I
Job M 2000500 Dagnr: Jeff Frelb 0e1e7 AUG 112000
Descdpl(on....
Retained Height
3.05 R
Well height above $011
0.35 R
Slope Behind Wall
0.00:1
Height of Soll over Toa •
7.00 In
Solt Denaity -
110.00 pcf
Wind on Stem • 0.0 par
Surcharge Loads
to Ste
Surohorgo Over Heel .
00 pof
Used To Resist Sliding a Overturning
Surcharge Over Toe
0.0 Psf
Ua•d fur Sliding 6 Ovajtuning
Toe Active Pressure
Axial Load Applied to Stem
A>dal Dead Load =
20.0 Ibis
Axial Live Load
20.0 The
Axial Load Eccentricity .
0.0 In
Design Summary
18.00
Total Bearing Load •
2,431 lbs
...resultant ecc. •
0.68 In
This
13011 Data
to Ste
Allow bell eeednglease
1,500,0 par
EquKralant Fluid Pleasure
Method
Heel Active Pressure
36.0 psf/R
Toe Active Pressure
35.0 perm
Passive Pressure
250.0 pal/ft
Water height over heel
• 0.0 R
FnotingIlSoll Friction
• 0.300
Sell heloht to Ignore
18.00
for passive pressure
O.DOIn
Lateral Load Applied
to Ste
Lateral Load
= 0.0 e/6
...Height to Top
= 0.00 R
...Height to Bottom
0.00 R
RetalnPro Basic
re - 3,000 pal
Fy - 60,0600
Min. As %
0.0018
Toa Width
• 1.50 R
Heel Width
= 2,25
Total Footing Width
176
Footing Thickneas
• 17.00 in
Key Width • 12,001n
Key Depth • 0.00 In
Key Distance from Toe 1.50 R
Cover Q Top • 2.D0In m Btm.= 3.00 In
Ad scent Footing
Load -�
ACI)aeanf Fwtina Load
,TJX
Footing Width
2.00 R
Eccentricity
= 0.00 In
Wall to Fig CL DI51
- 3,00 It
Footing Type
Line Load
Base Above/Below Soil
1,800 at
Pat
at Back of Well
0.0 R
Stem Construction __k Top st«n
Design height R = Steo 0000
Well Material Above "HP • Concrete
Soil Pressure ® Toe
Resulte
1,228 Pat OK
Thickness
,TJX
8.00
Soil Pressure Q Heel
1,708
71 psf OK
Reber Size
•
N S
Allowable
• 1,368
1,800 at
Pat
Reber Spacing
a
18.00
Sell Pressure Less Than
Allowable
Rebar Placed at
•
Edge
ACI Factored ® Toe1,734
Heel Reinforcing
pef
Design Dais --
----.-
• None Spec d
ACI Factored @Heel
=
100 pef
fb/F9 - fa/FA
0.a1a
Footing Shear ® Toe
9.8 I OK
Pa
Total Force ct Section
Ilu •
1,745.9
Footing Shear g1 Heel
=
8.1 0 OK
Moment.....
R -N •
2,987.9
Allowable
93.1 psi
Allow
Momenl.....Allovnble
a
6,585.4
Wail Stability Ratloe
Sheer..... Acluni
pal=
23.e
Overturning
213 OK
Shear..... Allowable
Pal.
03,1
Sliding • 0.81 UNSTABLEI
Sliding Calcs Slab Resists All Sliding I
Lateral Sliding Force a 1,2DO.2 The
Footing Design
Resulte
Reber Depth 'd'
Factored Presaurs=
,TJX
Heel
Mu' : Upward
1,708
414 at
Mu'! Downward
= 337
1,252 R#
Mu: Design
• 1,368
1106 RSM
Actual 1 -Way Shear
a
6,12 psi
Allow 1 -Way Shear
99.18
93.11 psi
Toe Reinforcing
a None Speed
Heel Reinforcing
• M 5 C 18.00 In
Key Reinforcing
• None Spec d
Bar Develop ABOVE Ht. In • 21.38
ear LoplHWk BELOW HI. In. 6.60
Well Weight
= 100.0
Reber Depth 'd'
In= 6.19
Masonry Pala -
----
I'm
psi'
Fa
pal.
Solid Grouting
'
Special Inspection
Modular Ratlo'n'
Short Term Factor
Equiv. Solid Thick.
Masonry Block Type • Medlum Weight
Concrete Datere - pal • 3,0X0
FY pyla 60,000.0
Other Accept+ble Sleea 4 6paelaal
Toe: Not req'c'Mu . eFr
Heel: Not rsq'd, Mu < 8' Fr
Kay Slab Resists Sliding - No Force on Key
AUG -01-00 03:37 PM HARPER—LEAVITT 524 0229 P.07
Harper Leavitt Engineering
M N. Capital
Idaho Falls, ID 83402
208)•524-0212
; (208)-6240229
8
Vertical Loads used for Soil Pressure = 2,430.8 IDs
Vertical component of active pressure used for soil pressure
TRIS ; Rsneher 4 Foot Walt
Job # 200055560 Degnr: Jafl Frelh Data: AUO 1,2000
Description.,,,
This Well In File; E;IRPMENCHER RPS
InD Wall be9lpn RetainPro Basic 5.0.7, 8 -Jul -99, (a) 1989 99
Force
Distance
IHament
hem
Iba
R
114
Heal Active Pressure =
378.4
1.55
588.5
Ta Active Pressure
43.9
0.53
43.2
Surcharge Over Toa
Adjacent Footing Load =
885.8
2.59
2,2,41.7
Addad L.brYl Load
20,0
1,83
98.7
Load @ Stem Above Soil
98.3
0.75
72.2
SolemleLoad
Total
1,200.2
O.T.M. •
2,806.1
RealatinglOvertuming Ratio
.
2.13
Vertical Loads used for Soil Pressure = 2,430.8 IDs
Vertical component of active pressure used for soil pressure
TRIS ; Rsneher 4 Foot Walt
Job # 200055560 Degnr: Jafl Frelh Data: AUO 1,2000
Description.,,,
This Well In File; E;IRPMENCHER RPS
InD Wall be9lpn RetainPro Basic 5.0.7, 8 -Jul -99, (a) 1989 99
Force
Distance
Moment
-.,__----
lbs
h
11_11
Soil Over Heel
835.7
2.96
1,880.6
Sloped Soil Over Heel
Surcharge Over Heel =
Adjacem Footing Load
$90.9
7.06
1,799.11
Axial Dead Load on Mam
20,0
1,83
98.7
Soil Over Toa
98.3
0.75
72.2
Surcharge Over Toe
StemWelght(s)
4000
183
7393
Earth Q Stem Trenselons =
Footing Weight
582.5
1.85
1,084.7
Key Weight ,
200
Vert. component e _
1055
3.75
396.3
Total) •
2,410,8 Iba
R.M.•
5,972.8
AUG -01-00 03:37 PM
Sing RestraN
som.h
@Tee
N5@18.h
@ Heel
HARPER—LEAVITT
a,h fnv r10; IM 1 d.in ek
�¢
524 0229
peslww adM
fa. Z.•3.
A hoH:, rehf. _11
See Ippen& h
3'•7
Q Fri wALL
P.08
RUG -01-00 03:38 PM HARPER—LEAVITT 524 0229 P.O9
S.Yd(ng f4:b.Jn1
kj Hg Loyd - 3000.01
&o- O.F hem CL
Pp= 313.3701
378.39M
PPPP7071psl
12257psl
AUG -01-00 03:38 PM
HARPER-LEAVITT
524 0229
P.10
Harper Leavitt Engineering Title Rencher 3 Foot Wall
Ida N. Capitol Job 9 200056d" --176M. Jeff Freib Date: AUG 1.2000
Idaho Fall-, 163402 Description....
(208)324-0212
Fax' (208).524-0220
Thin Wall In Flls: E:IRPSIRENCHER,RPS
Cantilevered Retaining_Wall Design RetalnPro Basic 5.0.7, JWul99, (c)1080.09
Retained Height
2.66 R
Allow Boll Bearing •
1,600.0 psi re - 3,000 psi
Fir . 60,000 psi
Wall height above soil
a 0,36 R
Equivalent Fluid Pressure Method Min. As %
0.0018
844 Behind Wall
- 6,60;1
Heel Active Pressure
Toe Active Pressure •
35.0 psf/R Toe Width
35.0 perm
= 1.25 R
Height of Boll over Toe
• 7.00 in
Passive Pressure
Heel Width
250.0loaf/R Total Footing Width
2.00
9oll Denary
- 110.00 pof
Waley height over heel •
0.0 B
Foolingl)Soll Frldlon =
Footing Trilckneee
0100
- 12.00 In
Wind on Stem
• 0.0 psf
Sell height to Ignore
Ke Width
Key Depth
12.00 In
• 0.00 In
for passive pressure
0.00 In Key Distance from Toa
■ 1.25 B
Cover 0 Top a 2.00
in 0 Btm = 3.00 in
Surcharge Loads
Lateral Load Applied to Stem
Ad scent Footle
Load T -A
Surcharge Over Heel
• 0.0 per
Lateral Load
0.0 */It boon n9 L0Qd
'3,DUU.0 Ihb
Used To Resist Sliding
d Overturning
.,,Height to Top
0.00 R Fooling Width
2.00 6
Surcharge Over Toe
• 0.0 psf
...Height to Bottom :
0,00 R Eccentricity
0.001n
Used for Sliding & Overturning
Wall to Fig CL Dist
• 3.00 it
Axial Load Applied to Stem
Footing Type
Line Load
cele
Axial Dead Load
s 20.0 lbs
Bars AbovelBelow Boll
at Back of Wall
o.o rt
Axial Live Load
• 0.0 lbs
Axial Load Eccentdcity
- 0.0 In
Summa
Design Summary
Stem construction -
Top Stern .,
Warn OK
Total Bearing Load
a 1,676 IM
Design height
R= 0.00
...resultant ecc.
6.06 In
Wall Material Above "HC
• Concrete
Soil Pressure 0 Toe
997 paf OK
Thickness
Reber Size111
: .04
Soil Pressure 0 Heel
35 psf OK
Rebar spacing
16A0
Allowable
• 1,500 par
Reber Placed at
• Edge
Boll Preaeure Less
Than Allowable
Design Data -
-- - --
ACI For.Inrod C Toe
• 1,401 pal
WFB • fa/F%
• 0.367
ACI Factored 0 Heel
• 40 psi
Total Force 0 Section
lbs - 1,316.1
Footing Shear 0 Toa
• 5.2 psi OK
Moment.... Actual
My • 1,311.7
Footing Shear 0 Heel
• 4.4 pit OK
Moment..... Allowable
= 3,571,3
Allowable
= 93.1 psi
Shear..... Actual
psi • 17.5
Wall Sidblllty Ratios
Sneer.....Allowahld
pal - 03.1
Overturning
Sliding
' 2.13 OK
0.77UNSTABLEI Bar Develop ABOVE Ht.
in - 17.09
Sliding talcs Slab Resists All Sliding I
Bar Lapffl dk BELOW Ht. In • 6.00
• 100.0
Lateral Sliding Force
= 990.8 lbs
Wall Weight
Reber Depth 'd'
In • 6.25
Masonry Data -
--
I'm
psi.
Fe
Pal `
Solid Grouting
=
special Inspection
'
Tooi Ing Design Results
Modular Ratio 'n'
Bhori Term Factor
`
Factored Pressure •
40 r Pof Equly. Solid Thick,
208 M1.0 Masonry Block Type •
Medium Weight _
,-
Mu' :Upward a
•
959
234 89711 concrete Dais ----
- - OOOA
Mu : Downward •
Md; Design
725 469 R
-M
Fy
peel • 00,000.0
Actuall-Way Shear ■
6.25 4.38 Psi
03.11 93.11 pat Orbe, Aeeeptable Sire, & Sp,elae,
Allow 1 -Way Shea( •
None Spec'd
Tae: Not req'd, Mu <
• Fr
Toe Reinforcing •
=
k 4 018.00 In
S
Heel: Not reed, < S'
Sliding
Fr
- No Force on Key
Heel Reinforcing
=None
Speed
Key' Slab Resists
Key Reinforcing
,-ruu-01-00 05:39 PH HARPER—LEAVITT
Harper Leavitt Engineering
985 N. Cepllai
Idaho Falls, ID 83402
v)-5240212
%:(206)-524-022&
524 0229 P.11
Title • Rancher 3 Fool Wall
Job N 200osao Dagnr Jeff Frelb Oale: AUG 1.2000
Description....
Cantilevered 1114t21nina Wall Desion RetainPro Basic 5.0.7. 8-Jul4g. to) 1859.99
of Overturnina & Resistina Forces &
Added Lateral Load =
Load @ Stem Above Soil
CelemlcLoad
Total 990.8 D.T.M. 1,884.8
Reslating)Overturning Ratio 2.13
Vertical Loads used for Soil Pressure a 1,676.1 lbs
Vertical component of active pressure used for sell pressure
Force
Distance
Moment
Item _ _
_ Ibe
R
ft4
Heel Active Pressure
233.1
1.22
283.7
Toe Active Pressure
.43.8
0.53
-23.2
Surcharge Over Toe
Surcharge Over Heel
Adjacent Footing Load
• 801,8
1.75
1,404.4
Added Lateral Load =
Load @ Stem Above Soil
CelemlcLoad
Total 990.8 D.T.M. 1,884.8
Reslating)Overturning Ratio 2.13
Vertical Loads used for Soil Pressure a 1,676.1 lbs
Vertical component of active pressure used for sell pressure
.....MISTING.....
Force
Distance
Moment
lbs
R
R-IY
Soil Over Heel
388.7
2,56
1,004.1
Sloped Soil Over Heel =
Surcharge Over Heel
Adjacent Footing Load •
334.7
2,02
077.7
Axial Deed Load on Stem
20.0
1.88
31.7
Sall Over Toe
80,2
0.83
50.1
Surcharge Over Too
Stem Weight(s) •
300,0
1.58
475.0
Earth @ Stem Transitions
Footing Weight
487.5
1.83
792.2
Key Weight
1.75
Vert. cgmponenl e
65.0
3.23
211.2
_
Total •
1,678.1
Ibe R.M.•
3,542.0
Huh 01-00 03:39 PM
Sldng Restraint
HARPER—LEAVITT
e.ln fnnt d 8e /d' I a In Or
524 0229
—_...�...�
MD@O.In
fine
Y4@18.In
@Heel
Designer select
A hortz. mint. 1` Z'
See Append. A
v.3__.
3 Fv*T WAL.
P_12
AUG -01-00 03:40 PM HARPER—LEAVITT 524 0229 P.13
S4kq Rastriml
14 Fig load = 3000.0
&c,� O.In from CL
Fp' 313.370233,111!
{.79{psl
99d,6.Sp f
f3O8l 356-104 G
haketts@ricks.edu
April 20, 2000
Tamla Rencher
836 North Skyline
Idaho Falls ID 83404
Dear Tamla:
Vice President Robert Wilkes has received your signed copy of the letter dated April 12,
2000, from Mike Orme to Royce Lee, in which you and your managers have agreed to all
conditions for future temporary, conditional and final approvals for American Manor.
Ricks College Housing, therefore, will grant American Manor an April 23, 2000, to April
28, 2001, temporary, conditional permit for occupancy in apartments which have received
occupancy permits by the City of Rexburg (According to Val Christensen's letter to you
dated March 24, 2000, buildings #113, #1C, #2, and #4 currently have occupancy permits.)
and also been inspected and approved by Ricks College for compliance with Ricks
College minimum facility requirements. We are willing to do additional inspections as
needed and as we are invited to do so. Please call our office to set up an appointment for
inspections.
This temporary, conditional permit, is based on complete compliance with all conditions
contained in the April 12, 2000, letter. Failure to comply with all conditions may result in
having the permit revoked.
We appreciate your interest in complying with all conditions for approval and look for-
ward to working with you.
Sincerely,
—'el"a tU /�
Sharon Tuckett
Housing Director
cc: Robert Wilkes, vice president of Student Life
Ric Page, assistant vice president of Student Life
Mike Orme, legal counsel
Royce Lee, legal counsel
vJohn Millar, City engineer
SHARON Tu CKE'rT
�-s cott
`fm
Housing Director
I 1.
Hanning office
�Pe ,aea �0
�ei/RG
196 Kimball Building
IOP
Rerbnrg, ID 8346o -r635
f3O8l 356-104 G
haketts@ricks.edu
April 20, 2000
Tamla Rencher
836 North Skyline
Idaho Falls ID 83404
Dear Tamla:
Vice President Robert Wilkes has received your signed copy of the letter dated April 12,
2000, from Mike Orme to Royce Lee, in which you and your managers have agreed to all
conditions for future temporary, conditional and final approvals for American Manor.
Ricks College Housing, therefore, will grant American Manor an April 23, 2000, to April
28, 2001, temporary, conditional permit for occupancy in apartments which have received
occupancy permits by the City of Rexburg (According to Val Christensen's letter to you
dated March 24, 2000, buildings #113, #1C, #2, and #4 currently have occupancy permits.)
and also been inspected and approved by Ricks College for compliance with Ricks
College minimum facility requirements. We are willing to do additional inspections as
needed and as we are invited to do so. Please call our office to set up an appointment for
inspections.
This temporary, conditional permit, is based on complete compliance with all conditions
contained in the April 12, 2000, letter. Failure to comply with all conditions may result in
having the permit revoked.
We appreciate your interest in complying with all conditions for approval and look for-
ward to working with you.
Sincerely,
—'el"a tU /�
Sharon Tuckett
Housing Director
cc: Robert Wilkes, vice president of Student Life
Ric Page, assistant vice president of Student Life
Mike Orme, legal counsel
Royce Lee, legal counsel
vJohn Millar, City engineer
Nov. 17, 2000
John Millar
Public Facilities Coordinator
City of Rexburg
P O Box 280
Rexburg, Id 83440
RE: occupation on American Manor C building apartments
Dear John Millar,
This is to certify that students will not be occupying the C building , i.e., C1, C2, C3, C4
apartment, until you have personally given your verbal and/or written reapproval after
a final inspection.
Thank you for your assistance and cooperation. It is greatly appreciated.
Sincerely,
Tamla Rencher
1748 Jeppson Ave
Idaho Falls, Id 83404
(208) 529-3836
October 12, 2000
John Millar
Public Works Facilitator
City of Rexburg
Dear John.
I have read Tamla Rencher's letter and do not agree with her statement that she is ,not
remodeling, changing or building anything". She goes on to say that all of the work is being
performed because of the "list" which we have provided her and that she is "making no
modifications". Many of the work items being performed at the American Manor Apartments are
not those created by the "list". The list below identifies some of these items:
1. The removal of the "eyebrow" eaves is one example. Each of the apartment
buildings thus far have had this work performed. This work was not part of our
correction list. It is not only cosmetic in nature but involves structural changes
that include extension of the trusses to create a roof over the entrances.
2. The metal stairs to the units complete with the entire metal entrance structures are
being altered.
3. The lowering of the parking lot created the need for new concrete stairs. These
stairs must be built to meet the building code and therefore inspected. These stairs
also require handrails that must meet code requirements. When the lot was
lowered, walking surfaces were created that had adjacent drop-offs of over 30".
These areas require guardrails. I happened to drop in on American Manor about a
month ago when the railing installers were constructing the new iron railings. If I
had not, they would have installed all of the guardrails at a 36" height instead of
the 42" height required for R-1 use.
4. In one apartment a 2" high landing was installed when the exterior entrance
balcony remodeled. I don't know what they could have done instead, but by
performing the work without a permit and not letting us in the loop, we surely
could not help out with a solution.
5. The parking lot changes were not on the list. The excavation for the retaining
walls was so close to the foundations of the buildings that catastrophic failure
could easily have occurred with the slightest seismic activity. The contractor and
owner were proceeding without any professional guidelines and when confronted
by their own engineer ended up removing substantially undersized footings. The
critical design of the retaining wall was left to a contractor who admitted to me
that he had no real commercial experience and was just now breaking into the
field. If I had not been checking the work at the complex, the work would have
been completed in a seriously negligent manner.
6. By not providing us with a parking plan that adequately described the work that
was going to be performed, the sewer line therefore was not addressed. Once
again if we had not stopped by to monitor the work in progress, Im sure that the
plastic line would have been covered over with about twelve inches of dirt. This
winter the line would have frozen and we would have had a big mess on our hands.
Even if it didn't freeze it would have eventually busted from being buried too
shallow. Then the parking lot would have to be tore up and either a ductile iron
line like we finally received would have been placed with the proper amount of
blue board. All at Tamla's expense. She doesn't realize that we are not only
protecting others from her but we are protecting her from herself.
There are many other construction item that are on the "list" that we still need to inspect.
All of the drywall that Scott is placing for separation needs to be inspected. We inspect drywall
fastening on all applications and especially on firewall application. I have caught Scott on a few
occasions applying the drywall in the incorrect areas and on walls which have penetrations caused
by electrical service boxes. The drywall was only required on one side of the wall and could have
been installed on the other side that did not have the electrical panel.
Scotts tendencies have been to call us after an installation, instead of before. This is a
correct procedure if you don't have any questions about the work. The life -safety problem caused
by enclosing the area between the two buildings was a direct result of Scott's nonchalant attitude
toward the Building Department, After discussions with Scott and having read Tamla's letter, I
feel that his attitude is a reflection of hers. Her attitude can be clearly seen in her statement that
she had "not been aware that we needed the inspectors to be informed of the changes before being
started since they were the ones who made up the violation list".
Tamla has now provided us with a drainage plan that sends all of the water out into the
street. When I asked for a drainage plan I also asked how the water would be put into the system
or if french drains or surface retention would be used. I asked Scott Cafaro and Jeff Freiberg
these very questions. Scott informed me that Tamla just ignored him when he proposed the
question to her. Jeff called me back and stated that surface retention and french drains were out
of the question. The understanding that Tamla agreed to in order for us to provide her with
"conditional occupancy" is contingent on her finishing items by certain dates. Item #8 states
"Drainage system is regired for the entire complex. The current system is inadequate and will
only become worse as more grass and landscaped areas are removed and more asphalt is added.
The owner must provide city with a drainage plan. Completion Date - 6/30/00. Drainage System
construction shaould be started as soon as possible and continued until parking lot is
reconstructed. Completion Date - 8/31/04". The drainage plan was critical to parking lot
construction.
It is evident that Tamla regards our direction as insignificant. It is my opinion that she will
say and do almost anything to keep the construction progress going. We keep bowing to her wish
for a letter here and one there that will help her get her financing. She will even spend $5000 on a
plan that does nothing for her (i.e. the parking lot is already built) and nothing for us. She will
install footings and then tear them out rather that get our opinion. I guess I am at a loss as to
how we should treat this situation. I think that the improvements to the complex are very good
for our community and I am willing to continue trying to work with Tamla to reach the end goal.
Thank you,
Val Christensen
OSP URC �O
V 0
a
4e[ISHEO
12/27/2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla,
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359.3020
Fax (208) 359-3022
e-mail rexburg@srv.net
Recently I was asked by Scott Caffaro if there was a way that one of the units in American
Manor Building A could be used for a family who you were evicting. I talked with my superiors
and they felt that if it would be a charitable offering (rent free) and that one of the units on the
lower floors was safe enough, then the possibility existed. I met with Scott Caffaro to try and
locate a suitable unit on Tuesday December 26, 2000. What I found is that you have illegally
moved a tenant into Building A without notifying us.
Our recent decision to grant you an occupancy permit for Building C was done as a favor
to you so that you could stay financially solvent. The granting of that permit was based solely on
an understanding of trust. John Millar went out on a limb to help you. If it bad been up to me
you would have had to abide by the original agreements that you made with us.
As a result of your decision to illegally move another tenant into Building A, you have put
the occupancy of Building B and Building C in jeopardy. Building B is connected to Building A.
The original list of construction items that you agreed to perform includes a two-hour wall
between Building A and Building B. As long as Building A was not occupied we did not feel that
an unsafe situation existed. Please immediately remove the tenants from Building A or I will
revoke your Occupancy for Buildings B and C. If you have any questions, I can be reached at
359-3020 ext. 314.
Sincerely,
Val Christensen
Assistant Engineer
C.C.
John Millar
Steve Zollinger
Dee Owens
March 7, 2001
Val Christensen
Assistant Engineer
City of Rexburg
P.O. Box 280
Rexburg, ID 83440
Dear Val Christensen,
The C building is ready for re -inspection. The list of items that you attached to the
certificate of occupancy is complete. Those items had to be removed and then reattached
due to the double drywall construction --but no one has been occupying C1, C2, C3, or C4
during this process.
No one is occupying the A building either. It is being used for storage, and hence, no one
is allowed in two apartments A6 and A14 so missing items will not be my responsibility.
They contain wedding gifts and personal boxes of storage.
I was confused by your earlier angry letter. I was not "evicting" anyone. No one was
living in the A building. I had not asked or authorized Scott to visit with you about
anything or anyone except to get construction codes, inspections, and advise.
I agree that John Millar is an asset to the city of Rexburg, deserves great respect, and
works well with people. I am very aware that you would not have "gone out on a limb" to
help me get a loan, while John Millar did. I am most grateful for his wisdom, compassion,
insight to other's concerns, and his ability to solve problems, I agree that he is a
remarkable leader.
I promised John that no one would be living in building C or building A without his or
your personal permission. No one is! I have not violated that promise or trust.
Aaron Gamble had asked me if he could move back into the apartment he had been in
before being a manager for me. I told him, "No, I promised John Millar than no one
would be living in the A building without Val Christensen's personal permission." When
he persisted, I told him that if he personally visited with you (that is, not asking anyone
else-- me or Jim or Scott or anyone) and get your written permission addressed to me for
this exception, then I would consider it.
I specifically asked Jim and Scott not to get involved, because this had nothing to do with
certification, regulations, American Manor construction, etc. This was a personal matter
for Aaron and his family, and had nothing to do with the construction crew or me as the
owner. I made that very clear to Aaron. Scott was out of line to talk to you about a favor
for Aaron. He had no authority from me, in fact he was told not to. That was Aaron's
responsibility.
If I had instead secretly "illegally moved" Aaron or someone into the A building, I would
not have received such an accusing letter from you because you would have been unaware
of it. On the contrary, I denied him access without your written permission to be sure I
was acting completely in accord with my promise. No one is or was living there.
There is double (and in some places triple) drywall between building A, building B, and
building C. The occupancy certificate of Building B was never in danger of being revoked
by students living in building B. We had already spent much time and money to add layers
of drywall between apartments as well as between empty buildings. Even if someone had
been living in A6 or Al or Al l (which they weren't and aren't), there is more than a two
hour burn between the first column of A and the last column of C. The students would
never have been in danger. I was confused by your outrage of this misunderstanding.
I am honestly not trying to be difficult in this situation --but with John Millar's foresight, I
am trying to turn American Manor into a beautiful, useable, and higher taxable real estate
for the city of Rexburg, neighbors, students, and everyone. Having the buildings just sit
and become an "eye sore" without use and upkeep, is the easy answer, but not the smart
one. Yes, sometimes people have to go "out on a limb" to help projects and people who
are trying to do good and make improvements. And yes, I am grateful that John Millar is
one of them.
I am sorry for any frustration this misunderstanding has caused.
The C building is ready for your re -inspection. No one is living there.
Thank you.
Sincerely,
Tamta Rencher "
1748 Jeppson Ave
Idaho Falls, Id 83404
(208)529-3836
cc: John Millar
Steve Zollinger
Dee Owens
March 7, 2001
Val Christensen
Assistant Engineer
City of Rexburg
P.O. Box 280
Rexburg, ID 83440
Dear Val Christensen,
The C building is ready for re -inspection. The list of items that you attached to the
certificate of occupancy is complete. Those items had to be removed and then reattached
due to the double drywall construction --but no one has been occupying CI, C2, C3, or C4
during this process.
No one is occupying the A building either. It is being used for storage, and hence, no one
is allowed in two apartments A6 and A14 so missing items will not be my responsibility.
They contain wedding gifts and personal boxes of storage.
I was confused by your earlier angry letter. I was not "evicting" anyone. No one was
living in the A building. I had not asked or authorized Scott to visit with you about
anything or anyone except to get construction codes, inspections, and advise.
I agree that John Millar is an asset to the city of Rexburg, deserves great respect, and
works well with people. I am very aware that you would not have "gone out on a limb" to
help me get a loan, while John Millar did. I am most grateful for his wisdom, compassion,
insight to other's concerns, and his ability to solve problems. I agree that he is a
remarkable leader.
I promised John that no one would be living in building C or building A without his or
your personal permission. No one is! I have not violated that promise or trust.
Aaron Gamble had asked me if he could move back into the apartment he had been in
before being a manager for me. I told him, "No, I promised John Millar than no one
would be living in the A building without Val Christensen's personal permission." When
he persisted, I told him that if he personally visited with you (that is, not asking anyone
else-- me or Jim or Scott or anyone) and get your written permission addressed to me for
this exception, then I would consider it.
I specifically asked Jim and Scott not to get involved, because this had nothing to do with
certification, regulations, American Manor construction, etc. This was a personal matter
for Aaron and his family, and had nothing to do with the construction crew or me as the
owner. I made that very clear to Aaron. Scott was out of line to talk to you about a favor
for Aaron. He had no authority from me, in fact he was told not to. That was Aaron's
responsibility.
If I had instead secretly "illegally moved" Aaron or someone into the A building, I would
not have received such an accusing letter from you because you would have been unaware
of it. On the contrary, I denied him access without your written permission to be sure I
was acting completely in accord with my promise. No one is or was living there.
There is double (and in some places triple) drywall between building A, building B, and
building C. The occupancy certificate of Building B was never in danger of being revoked
by students living in building B. We had already spent much time and money to add layers
of drywall between apartments as well as between empty buildings. Even if someone had
been living in A6 or Al or AI I (which they weren't and aren't), there is more than a two
hour burn between the first column of A and the last column of C. The students would
never have been in danger. I was confused by your outrage of this misunderstanding.
I am honestly not trying to be difficult in this situation --but with John Millar's foresight, I
am trying to turn American Manor into a beautiful, useable, and higher taxable real estate
for the city of Rexburg, neighbors, students, and everyone. Having the buildings just sit
and become an "eye sore" without use and upkeep, is the easy answer, but not the smart
one. Yes, sometimes people have to go "out on a limb" to help projects and people who
are trying to do good and make improvements. And yes, I am grateful that John Millar is
one of them.
I am sorry for any frustration this misunderstanding has caused.
The C building is ready for your re -inspection. No one is living there.
Thank you.
Sincerely,
Tamia Rencher
1748 Jeppson Ave
Idaho Falls, Id 83404
(208)529-3836
cc: John Millar
Steve Zollinger
Dee Owens
11/16/2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla,
hIN.1'�lll'r�
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
I am issuing you an occupancy permit for Building "C" with the following
conditions:
1. A 2 -hour firewall will be constructed between buildings "C" and "B".
2. All drywall will be completed.
3. All electrical now in repair will be completed and the State of Idaho
Electrical Inspector will be notified for final inspection.
4. All toilets, sinks and bathtubs will be properly installed.
5. Floor coverings will be finished.
6. Fire extinguishers will be properly mounted.
7. Smoke detectors will be installed in each bedroom.
8. Stairs shall be completed.
All of the above work must be complete and inspected by the City of Rexburg
prior to the units in Building "C" being rented or used for human habitation.
Thank you for your consideration in these matters. If you have any questions, I
can be reached at 359-3020 ext. 314.
Sinncerely,
Val Christensen
Assistant Engineer
11/16/2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla,
I am issuing you an occupancy permit for Building "C" with the following
conditions:
1. A 2 -hour firewall will be constructed between buildings "C" and `B"
2. All drywall will be completed.
3. All electrical now in repair will be completed and the State of Idaho
Electrical Inspector will be notified for final inspection.
4. All toilets, sinks and bathtubs will be properly installed.
5. Floor coverings will be finished.
6. Fire extinguishers will be properly mounted.
7. Smoke detectors will be installed in each bedroom.
8. Stairs shall be completed.
All of the above work must be complete and inspected by the City of Rexburg
prior to the units in Building "C" being rented or used for human habitation.
Thank you for your consideration in these matters. If you have any questions, I
can be reached at 3 59-3 020 ext. 314.
Sincerely,
Val Christensen
Assistant Engineer
pOF�uaC�O Cly
p "'iii/// Q !L
�s 114,E
9QCIS14
12/27/2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla,
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359.3020
Fax (208).359-3022
e-mail rexburg@srv.net
Recently I was asked by Scott Caffaro if there was a way that one of the units in American
Manor Building A could be used for a family who you were evicting. I talked with my superiors
and they felt that if it would be a charitable offering (rent free) and that one of the units on the
lower floors was safe enough, then the possibility existed. I met with Scott Caffaro to try and
locate a suitable unit on Tuesday December 26, 2000. What I found is that you have illegally
moved a tenant into Building A without notifying us.
Our recent decision to grant you an occupancy permit for Building C was done as a favor
to you so that you could stay financially solvent. The granting of that permit was based solely on
an understanding of trust. John Millar went out on a limb to help you. If it had been up to me
you would have had to abide by the original agreements that you made with us.
As a result of your decision to illegally move another tenant into Building A, you have put
the occupancy of Building B and Building C in jeopardy. Building B is connected to Building A.
The original list of construction items that you agreed to perform includes a two-hour wall
between Building A and Building B. As long as Building A was not occupied we did not feel that
an unsafe situation existed. Please immediately remove the tenants from Building A or I will
revoke your Occupancy for Buildings B and C. If you have any questions, I can be reached at
359-3020 ext. 314.
Sincerely,
Val Christensen
Assistant Engineer
C.C.
John Millar
Steve Zollinger
Dee Owens
nt ❑'y:
COOPER WETZEL AVERY & LEE,P.A.; 2085242051; May -30-03 4:19PM; Page 1/2
TO:
FROM:
M
ROYCE B. LEE
Attorney at Law
770 S. Woodruff Avenue
Idaho Falls, Idaho 83401
Telephone (208) 524-2001
Fax (208) 524-2051
FAX TRANSMISSION COVER SHEET
WA I
ORIGINALS TO FOLLOW BY MAIL
FAX ONLY
NUMBER OF PAGES (including cover)
CONF[AENTIAUTY NOTICE: The documents acoompanying this teleoopy transmission may contain
confidential infomrmation belonging to the sender mAkh is legally privileged. The information is Intended only
for the use of the individual or entity named above. If you are not the intended recipient, you are hereby
notified that any dlsdostae, copying, distribution or the hAdng of any action In u lianee on the contents of this
telecopled hrfonnation is shkHy prohlUted. If you have r"ved this oekupy In error, please immediately
notify us by telephone to arrange for return of the original documents to us.
sent By: COOPER WETZEL AVERY & LEE,P.A.; 2085242051;
City Report of Review
of Design of Building A
of American Manor
May -30-03 4:2OPM; Page 2/2
Val Christensen met with Patrick Bragassa, a structural engineer, to inspect Building
A at American Manor Apartment, Various areas of concern were identified including a
cantilever roof eve problem, an overspan of joists problem and other miscellaneous items.
Mr. Bragassa recommended a plan for corrections which Val Christensen approved. A
building permit has been granted to proceed with this plan for building A.
DATED May .ah , 2003,
Val Christensen
Transmission Result Revort(MemorYTX) ( May.31, 2003 6;14AM) ' " g P, 1
2)
2)
Date/Time: May,31, 2003 6:13AM
File Page
No. Mode Destination Pg (S) Result Not Sent
----------------------------------------------------------------------------------------------------
3835 Memory TX 95242051 P. I OK
----------------------------------------------------------------------------------------------------
Reason for error
E.1) Hants u or line fail E 2) Busy
E.3) No answer E.4) No facsimile connection
Aant ayf CMPFP W TZEL AoaY 6 LEE,P.a.i 40B524Ta51i W+Y'ae.M a.4 opal PqF 414
City Report of Review
.11 slgn afDrrildkeA
ofAmerican Manor
Vel C6Aslensen ioel with Petrick B�astmclural engincer,to inspect Building
A al Amcricen Mor Aprnww. Various meas If. was idMlified including a
caotilever mofevepmblem, m ovenpmt ofpism problem and other miscellenwus items.
W. Bregassa reeon dd a plan fm co,,,fi ns which Vsl Chrislmsm ap mvr . A
buildingpermit bat been gre w proceed with this plw<< barlwgA.
DATED htay� o , 2003
Val CloistenMn
• P. 1
Transmission Result Report(MemoryTX) ( May -31, 2003 6:13AM)
I)
2)
Date/Time: May,31, 2003 6:12AM
File Page
No. Mode Destination Pg(s) Result Not Sent
----------------------------------------------------------------------------------------------------
3834 Memory TX 94962158 P, I OK
----------------------------------------------------------------------------------------------------
Reason for error
E. )) Hang up or I ine f a i I E.2) Busv
E.3) No answer E.4) No facsimile connection
Sent By: G Fo nim n ' 3 LEE,P.,k, 2Ba5242051p Mey-30-0.i a:N@M, Pepe 22
City Report of Review
ufDeelgn of Building A
of Acn A .Macer
Val Chrialens..d Mth patdckHregass%ashuclural engiaeer,to inspect Building
A at Asn i. Macer Apmbnent Von.. ores¢ of. were id®nfled including a
ceitBlever roof eycproblept, on oyerspan ofjoislapmblmn Me other miscellaneous Items.
Mr. Dcagssso ren—ewld a pion for wmeduue -M h Vel Christensen epp,--I. A
building permit has been g lacd m proceed with this plan fm 6u ,Hag A.
DAT May -RP 2003.
�_— ,
Val Christensen
eily 0/ 2exlurl
STATE OF IDAHO
BRUCE SUTHERLAND
P.O. BOX 280
ROSE BAGLEY August 28, 2001
12 NORTH CENTER STREET
W"
REXBURG, IDAHO 83440
RICHARD HORNER
PHONE (208) 359-3020
MUSURER&FN "CULOAMR
FAX (208) 359-3022
Royce B. Lee
Cooper, Wetzel, Avery & Lee
770 South Woodruff
Idaho Falls, Idaho 83401
Re: State v. Tamla Rencher
Dear Mr. Lee:
Over the course of the past 18 to 24 months, Ms. Rencher has obtained numerous permits
and conditional occupancy provisions, as I am sure you are aware. In doing so, she made several
representations, upon which the permits were conditioned. The public hearings which have taken
place have served to formalize many of the stipulations that Ms. Rencher has entered into, as
well as letter agreements between the City of Rexburg and Ms. Rencher, to which I believe you
are privy. To enumerate all of the items to which she has agreed would be redundant, and
somewhat burdensome, although if you are making a formal request for discovery, I can provide
you with the information in the course of preparing to convict your client.
As I discussed with your client last week, it would go a long way toward resolving the
criminal matter, if she would complete as much of the agreed upon work prior to the pre-trial as
possible. In particular, I referenced a fence between her property and.the neighbors to the South.
While I do not believe nor did I intend to represent that the fence alone would fulfill all of her
agreements with the City, it would remove the issue of directed complaints from the neighbor.
At this point in time Ms. Rencher is in possession of all of the documents setting forth the
items she needs to complete, and should work with all haste to complete the same in accordance
with the terms of our previous agreements. Should you or your client wish to discuss the
specifics of these agreements, I would be happy to set up a meeting between our building
department and whomever you desire to bring. Let me know of your wishes.
Sincerely,
Stephef[ P. Zollinger U
Rexburg City Attorney
cc: `American Manor File
11/7/2001
Sharon Tuckett
BYU Idaho
Housing Department
196 Kimball
Rexburg, ID 83440
Dear Sharon,
cily 4912exlur7
STATE OF IDAHO
www.ci. rexbu rn.id _ us
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@ci.rexburg.id.us
This letter is written in response to your call concerning the American Manor Apartments.
At this time Ms. Rencher is in compliance with the time schedule that was required for a
conditional occupancy permit for the American Manor Apartments. The one item that causes the
City of Rexburg Building Department concern is the parking lot. Ms. Rencher has left a portion
of the parking tot unfinished. The unfinished portion is being parked on and vehicles are tracking
mud onto the city street. Even though Ms. Rencher was not required to add this section of
parking lot at this time, she now needs to finish it off with asphalt.
Please let me know if I have answered all your questions on this matter. I can be reached
at 359-3020 ext. 324.
Sincerely,
Val Christensen
Building Official
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No.
Zoning/Land Use Class:
Building Street Address: 139 S lest E -• %,11161inf 111d
Land - Legal Description:
Building Owner: TA,It%A RPNCHFR --
Address: 1748 JEPPSON AVE, IDAHO FALLS, 11) $3404
Contractor: SCOTT CAFFARO
Description of building or portion of building for which this
certificate is issued:
BU IL)I ENG - ' D'
AMERICAN MANOR APARTMENTS
Occupancy / Use Classifications(s):
This Certificate, issued pursuant to the requirements of Section 109 of
the Uniform Building Code, certifies that, at the time of issuance, this
building or that portion of the building that was -inspected on''the4AG—
listed was found to be in compliance with the requirements of the code
for the group and division of occupancy and the use for which the
proposed occupancy was classified.
DATE: C.O. Issued' by:
Approved:
This Certificate of Occupancy shall be posted in a conspicuous place on
the premises and shall not be removed except by the Building Official.
There shall be no future change in the existing occupancy classification of the building nor shall any
structural changes, modifications or additions be made to the building or any portion thereof until the
Building Official has reviewed and approved said future changes.
FIRE DEPARTMENT (. r -n
PLMIBING
ELECTRICAL
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No.
Zoning/Land Use Class:
Building street Address: 1$* 139 9 Ist E. Buildinp 1W
Land - Legal Description:
Building Owner: Talmla
Address: 1748 Jeppson Ave., Idaho Palls, ID 83404
Contractor: Scott Caffaro
Description of building or portion of building for which this
certificate is issued:
Building, 'i3'
AMW3,11CAN MANOR APARTMENTS
Occupancy / Use Classifications(s):
This Certificate, issued pursuant to the requirements of Section 109 of
the Uniform Building Code, certifies that, at the time of issuance, this
building or that portion of the building that was inspected on the date
listed was found to be in compliance with the requirements of the code
for the group and division of occupancy and the use for which the
proposed occupancy was classified. x
DATE: ,)C.Q. Issued by:
f�
Approved:
This Certificate of Occupancy shall be posted in a conspicuous place on
the premises and shall not be removed except by the Building Official.
There shall be no future change In the existing occupancy classification of the building nor shall any
structural changes, modifications or additions be made to the building or any portion thereof until the
Building Official has reviewed and approved said ful;Le changes.
FIRE DEPARTMENT
� p
PLUMBING DEPARTMENT
ELECTRICAL DEPARTMaNT.�^��
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No.
Zoning/Land Use Class:
Building street Address: 179 S lot. F - Building 'F:'
Land — Legal Description:
Building owner: TAMLA RENCHER
Address: 1748 aPPSON avE, IDAHO FALLS ID 83404
Contractor: UCOTT CAFFARO
Description of building or portion of building for which this
certificate is issued:
BUILDING 'E"
A14R UCAN MANOR APARTMENTS
occupancy / Use Claseifications(s):
This Certificate, issued pursuant to the requirements of Section 109 of
the Uniform Building Code, certifies that, at the time of issuance, this
building or that portion of the building that was inspected on the date
listed was found to be in compliance with the requirements of the code
for the group and division of occupancy and the use for which the
proposed occupancy was classified. �.
7 �
DATE: % / P.(7 Cc O. Issued by:
r,.,
f�
Approved:
ire �
This Certificate of Occupancy shall be posted in a conspicuous place on
the premises and shall not be removed except by the Building Official.
There shall be no future change in the existing occupancy classification of the building nor shall any
structural changes, modifications or additions be made to the building or any portion thereof until the
Building Official has reviewed and approved said future changes.
FIRE DFTARTMF.WT (
PLUMBING DEPAIITMBNT
ELECTRICAL DEPARTMENT
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No. Zoning/Land Use Class:
Building Street Address: 1#( 139 S. 1st E. Building k$,'d 'B' i,,'
Land — Legal Description:
Building Owner: TAMLA BENCHER
Address: 17108 JEPPSON AVE, IDAHO PALLS, Ill 193404
Contractor: SCUTT CAFFARO
Description of building or portion of building for which this
certificate is issued:
BUILDING W '1T" - ;_S;r
AMERICAN MANOR APARTMENTS
Occupancy / Use Classifications(s):
This Certificate, issued pursuant to the requirements of Section 109 of
the Uniform Building Code, certifies that, at the time of issuance, this
building or that portion of the building that was inspected on the date
listed was found to be in compliance with the requirements of the code
for the group and division of occupancy and the use for which the
proposed occupancy was classified.
DATE: /11
Approved:
This Certificate of Occupancy shall be posted in a conspicuous place on
the premises and shall not be removed except by the Building Official.
There shall be no future change in the existing occupancy classification of the building nor shall any
structural changes, modifications or additions he made to the building or any portion thereof until the
Building Official has reviewed and approved said future changes.
FIRE DEPARTMENT t....:... ._,.. :.
PLUMBING DEPARTMENT
-Li �,F ' / >
�/- :..
ELECTRICAL DEYARYM$HT
Li, -4-,C 1.f dt_,:.
STATE OF IDAHO
FAX TRANSMITTAL SHEET
Date: (.),. 17 o2�DD
Fax: �V4 - 6X97
From: City of Rexburg
P. O. Box 280
Rexburg, ID 83440
208-359-3020 - Phone
208-359-3022- Fax
RE:
V
Pages -�?
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359.3020
Fax (208) 359-3022
e-mail rexburg@srv.net
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No.
Zoning/Land Use Class:
Building Street Address: 139 So. 1st East - Building "C"
Land - Legal Description:
Building Owner: TAMLA RENCHER
Address: 1748 Jeppson Ave. Idaho Falls ID 8 404
Contractor: Scott Caffa o
Description of building or portion of building for which this
certificate is issued:
Building "C"
American Manor Apartment
Occupancy / Use Classifications(s):
This Certificate, issued pursuant to the requirements of Section 109 of
the Uniform Building Code, certifies that, at the time of issuance, this
building or that portion of the building that was inspected on the date
listed was found to be in compliance with the requirements of the code
for the group and division of occupancy and the use for which the
proposed occupancy was classified.
DATE: //
z-6Da C O. Is d by: '��41�
Approved:
This Certificate of Occupancy shall be posted in a conspicuous place on
the premises and shall not be removed except by the Building Official.
There shall be no future change in the existing occupancy classification of the building nor shall any
structural changes, modifications or additions be made to the building or any portion thereof until the
Building Official has rev 1wed and approved t
id future changes.
Fire Department
Water Department
Fire Department
ore URc o
o
a n
i0srq �$d>'
e(ISHE�
11/16/2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla,
cif y (0/ -W eXIMF7
STATE OF IDAHO
P.O. Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359.3020
Fax (208) 359-3022
e-mail rexburg@srv.net
I am issuing you an occupancy permit for Building "C" with the following
conditions:
1. A 2 -hour firewall will be constructed between buildings "C" and "B".
2. All drywall will be completed.
3. All electrical now in repair will be completed and the State of Idaho
Electrical Inspector will be notified for final inspection.
4. All toilets, sinks and bathtubs will be properly installed.
5. Floor coverings will be finished.
6. Fire extinguishers will be properly mounted.
7. Smoke detectors will be installed in each bedroom.
8. Stairs shall be completed.
All of the above work must be complete and inspected by the City of Rexburg
prior to the units in Building "C" being rented or used for human habitation.
Thank you for your consideration in these matters. If you have any questions, I
can be reached at 359-3020 ext. 314.
Sincerer
Val Christensen
Assistant Engineer
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No.
Building Street Address:
Land - Legal Description:
Building Owner:
Address:
Contractor:
Zoning/Land Use Class:
139 So. lest &1st — Building "C"
TAMLA RYNCHER
1740 Jeppson Ave., Idaho Falls, 11) 83404
Scott Caffarb
Description of building or portion of building for which this
certificate is issued:
11COT
American Manor Apartmento
Occupancy / Use Classifications(s):
This Certificate, issued pursuant to the requirements of Section 109 of
the Uniform Building Code, certifies that, at the time of issuance, this
building or that portion of the building that was inspected on the date
listed was found to be in compliance with the requirements of the code
for the group and division of occupancy and the use for which the
proposed occupancy was classified.
DATE: 1 /fn 0() C.O. Issued by: Z�:r
/ r r
Approved:
Building Official
This Certificate of Occupancy shall be posted in a conspicuous place on
the premises and shall not be removed except by the Building Official.
There shall be no future change in the existing occupancy classification of the building nor shall any
structural changes, modifications or additions be made to the building or any portion thereof until the
Building official has reviewed and approved eaid future changes.
Watv,C
Firs Department
CERTIFICATE OF OCCUPANCY
City of Rexburg
Department of Building Inspection
Building Permit No.
Building Street Address:
Land - Legal Description:
Zoning/Land Use Class:
139 So. 1st East - Buildine "C"
Building owner: TAM A RENCHER
Address: 1748 Jeppson Ave., Idaho Falls ID 83404
Contractor: Scott Caffaro
Description of building or portion of building for which this
certificate is issued:
American Manor Apartments
Occupancy / Use Classifications(s):
This Certificate, issued pursuant to the requirements of Section 109 of
the Uniform Building Code, certifies that, at the time of issuance, this
building or that portion of the building that was inspected on the date
listed was found to be in compliance with the requirements of the code
for the group and division of occupancy and the use for which the
proposed occupancy was classified.
DATE: /ln DaO C„O. Issuld by: A
ayllzs�-
Approved:
This Certificate of Occupancy shall be posted in a conspicuous place on
the premises and shall not be removed except by the Building Official.
There shall be no future change in the existing occupancy classification of the building nor shall any
structural changes, modifications or additions be made to the building or any portion thereof until the
Building Official hasrevs wed and approvedaid future changes.
Fire Department
Water Department
Ill,
Fire Department
P. 1
Transmission Result Revort(MemoryTX) ( Nov -17. 2000 9:57AM ) * ' '
CITY OF REXBURG
File Page
No, Mode Destination pg (S) Result Not Sent
----------------------------------------------------------------------
5051 Memory TX 95426591 P; 3 OK------
--------------------------------------------------------------------------------------
Reason for error
E.1) Hans u or line fail E.2) 8usv
E.3) No answer E.4) No facsimile connection
°"Q. n
o CQ ly
geQso v
Friday, March 24, 2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla,
/[J
P.O. 8ox 280
12 North Center Street
Rexburg, Idaho 83440
STATE OF IDAHO
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexhurg@srv.net
For the past few months I have been inspecting the ongoing construction taking
place at the American Manor Apartments. Your contractor, Scott Caffaro seems to
be doing a good job and has been pleasant to work with. He has addressed the
issues I have needed taken care of promptly. Your request for Conditional
Occupancy can be met by meeting the schedule which I have attached to this letter.
I have tried to set the schedule to meet your needs in performing some of the
interior work during the break between college semesters.
Thank you for your consideration in these matters. If you have any questions, I
can be reached at 359-3020 east. 314.
Sincerely,
Val Christensen
Assistant Engineer
AMERICAN MANOR APARTMENTS - SCHEDULE FOR CONDITIONAL
OCCUPANCY
The following is a list of items that have not been finished at the American Manor
Apartments. Each unfinished item is listed along with required date of completion.
1. Building #4 laundry headroom. Sign shall be posted at entry of laundry.
Sign shall read "Low Head Clearance" and shall state the actual height of
the ceiling. The letters shall be 1" high. Also fluorescent striped warning
tape shall be applied to the ends of all of the light fixtures which extend
below ceiling. Completion Date — 3/27/00
2. Railing missing at concrete stairs behind Buildings #3 and #4. Add railing
as per code. Completion Date — 3/27/00
3. Building #1-B, Building #3 and Building #4 mechanical rooms must be
separated from dwelling units with one layer of 5/8" type X drywall.
Completion Date — 3/27/00
4. Enclosed area between Building #3 and Building #4. The enclosed area
must be constructed to meet corridor requirements. The floor will be
covered with %" dura -rock and then covered with ceramic tile. All
windows must be changed out to meet % hour fire resistance. All doors
must be changed out to meet 20 minute fire resistance. Completion Date —
4/29/00
5. Building #I -B, Building #3 and Building #4 fire walls and ceiling
separation must be completed. All walls that separate dwelling units must
have one layer of 5/8" type X drywall added on walls and ceilings. The
walls must continue in the attic with.two layers of 5/8" type X drywall
continuous to roof sheathing. Completion Date — 8/27/00
6. The egress windows in Building #1-B have not been completely changed
out. Completion Date — 8/27/00
7. Metal drain cover in sidewalk at Northwest corner of Building #IA creates
tripping hazard. Discuss plans for eliminating hazard with City Engineer
prior to repair. Completion Date — 6/30/00
8. Drainage System is required for entire complex. The current system is
inadequate and will only become worse as more grass and landscaped
areas are removed and more asphalt parking is added. The owner must
provide city with a drainage plan. Completion Date — 6/30/00. Drainage
System construction should be started as soon as possible and continued
until parking lot is reconstructed. Completion Date — 8/31/04
9. Retaining wall at North property line. Drainage system should be installed
North of Building #1 prior to the retaining wall construction. Completion
Date — 5/31/02
10. Parkinglot is not currently configured to allow for Fire Department
access. The lot has a long term plan for complete renovation. Until the
changes are made, the lot must be reconfigured to meet Fire Department
standards. Completion Date — 6/30/00
11. All repairs must be made to Buildings #1-C and #2 prior to occupancy.
The repairs include but are not limited to stair reconstruction, firewall
construction, smoke alarms, window replacement, mechanical room
drywall repair, 2 -hour separation walls at #1 -A/#1 -B/#1 -C common walls,
exterior siding, etc.. In whole, the units must have all the punchlist items
complete from the Joe Laird List. Completion Date — 8/31/05
As per the above list, a Conditional Occupancy has been given to
Buildings #1B, #1C, #2, #3 and #4 only. Building #IA is not included in this
Conditional Occupancy. All repairs must be completed by schedule or have the
Rexburg City Engineer sign a change in schedule. All punchlist items including
parking lot reconstruction, drainage and retaining wall must be completed prior to
the City of Rexburg issuing a Final Occupancy for the entire complex
O��yE7CRupo 9 0
�f �� ��D,� P.O. Bax 280
c ¢ l � 12 North Center
Street
Rexburg, Idaho 83440
STATE OF IDAHO Phone (208) 359-3020
4eCISHEO Fax (208) 359.3022
e-mail rexburgpsrv.net
7/14/2000
Tamla Rencher
836 North Skyline
Idaho Falls, ID 83404
Dear Tamla:
I have reviewed the plans for the parking lot at American Manor and have found the
following discrepancies:
1. The lot has been designed with parking in the front yard set -back. This is not
allowed as per Section 5.6 in the Parking Regulations.
2. The lot has not been designed for adequate landscaping requirements as per
Section 5.5 I in the Parking Regulations.
3. Shrubbery located on the neighbors lot can not qualify as necessary screening as
per Section 4.7 A2 of the Supplementary Regulations. The same house lot is not
shown to be screened on its East property line.
4. Plan shows power pole marked as retain and protect that is clearly in the traffic
aisles.
5. Plan shows house with 19 parking places in rear. This property is not owned by
the developer and is confusing at best.
6. The Fire Department has found that the aisle widths do not meet their needs.
7. The Fire Department has identified the need of another fire hydrant.
8. Drainage plans are not shown for the rear of the long building on the north side.
The current drainage gutter cuts across the sidewalk and empties into the street
gutter. It is covered with a loose metal top and creates a tripping hazard.
Another problem that has evolved is the lowering of the parking lot. On July 10, 2000, I
was called to American Manor for an inspection. Kauer Construction was proceeding to remove
the asphalt and concrete surfaces of the existing parking lot. Scott Cafaro informed me that they
were going to lower the height of the parking lot by about 4' at the highest locations. He
informed me that there would be retaining walls around the entire complex to separate the
walkways around the apartments from the driveway. He further stated that he was planning to
install handrails along these sidewalks because they would now have a drop-off to the parking lot.
I informed Mr. Cafaro that he would be taking at least 6 units that had entrances that were
accessible and would now make them non -accessible. Furthermore, I instructed him that the laws
were aimed at making units more accessible instead of the contrary. I instructed him at that time
that the parking plan that we were planning on presenting at the July 12th Planning and Zoning
meeting did not show these changes. He was also instructed that if he was going to continue with
the idea of lowering the parking lot, he would have to have handicap access to the walkways and
Parking that would work with them. I informed him that we needed plans showing how he was
going to construct the retaining walls behind the long building on the north side and the retaining
wall around the units. Finally I informed him that it would be nice if we were given plans that
accurately depicted that which was really going to be constructed so that we were approving the
right thing in our P&Z meeting.
At the P&Z meeting the group unanimously agreed that we need a plan that accurately
depicts the actual construction taking place. Please provide us with accurate drawings. Please let
me know if you have any questions. I can be reached at 359-3020 ext. 314.
Sincerely,
u-c-- l f
Val Christensen
Assistant Engineer
cc: Dee Owens
John Millar
Joe Laird
September 14, 2000
Tamla Rencher
1748 Jeppson Ave.
Idaho Falls, Idaho 83404
Re: American Manor Apartments Letter
Tamla:
PO.BOX280
12 North Center Street
Rexburg, Idaho 83440
STATE OF IDAHO Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
Accompanying this letter is a letter I have prepared for Sharon Tuckett at Ricks College. I hope this
letter, will meet their needs. If not I will modify it as I can.
There are several items that are still outstanding from the list of 11. On of the major issues from
the letter of l I is the preparation and submission of a overall site drainage plan. This was to have
been submitted in June. This must be prepared and submitted as soon as possible. Please review
the list and complete all agreed to items.
We still have a problem with notification of repairs or changes prior to them being started. These
modifications have been done without a building permit for the current work or, repairs. The City
of Rexburg will be billing you for the inspection time that has been sent of bringing the buildings
into compliance.
Other outstanding items include the fence between you and the Manns' and final approval of the site
Plan by the Planning and Zoning. The fire department also requested that the fire hydrant by the
dentist office be replaced with a larger hydrant to allow for adequate fire suppression supply.
Please keep in mind that we want to work with you on this development and are pleased with the
improvements to date. Please keep us informed on what and when things are being done.
7Si erely,, ,
ohn W. Millar P.A.S.
Public Facilities Coordinator
October 12, 2000
John Millar
Public Works Facilitator
City of Rexburg
Dear John:
I have read Tamla Rencher's letter and do not agree with her statement that she is "not
remodeling, changing or building anything". She goes on to say that all of the work is being
performed because of the "list" which we have provided her and that she is "making no
modifications". Many of the work items being performed at the American Manor Apartments are
not those created by the "list". The list below identifies some of these items:
1. The removal of the "eyebrow" eaves is one example. Each of the apartment
buildings thus far have had this work performed. This work was not part of our
correction list. It is not only cosmetic in nature but involves structural changes
that include extension of the trusses to create a roof over the entrances.
2. The metal stairs to the units complete with the entire metal entrance structures are
being altered.
3. The lowering of the parking lot created the need for new concrete stairs. These
stairs must be built to meet the building code and therefore inspected. These stairs
also require handrails that must meet code requirements. When the lot was
lowered, walking surfaces were created that had adjacent drop-offs of over 30".
These areas require guardrails. I happened to drop in on American Manor about a
month ago when the railing installers were constructing the new iron railings. If I
had not, they would have installed all of the guardrails at a 36" height instead of
the 42" height required for R-1 use.
4. In one apartment a 2" high landing was installed when the exterior entrance
balcony remodeled. I don't know what they could have done instead, but by
performing the work without a permit and not letting us in the loop, we surely
could not help out with a solution.
5. The parking lot changes were not on the list. The excavation for the retaining
walls was so close to the foundations of the buildings that catastrophic failure
could easily have occurred with the slightest seismic activity. The contractor and
owner were proceeding without any professional guidelines and when confronted
by their own engineer ended up removing substantially undersized footings. The
critical design of the retaining wall was left to a contractor who admitted to me
that he had no real commercial experience and was just now breaking into the
field. If I had not been checking the work at the complex, the work would have
been completed in a seriously negligent manner.
6. By not providing us with a parking plan that adequately described the work that
was going to be performed, the sewer line therefore was not addressed. Once
again if we had not stopped by to monitor the work in progress, Im sure that the
plastic line would have been covered over with about twelve inches of dirt. This
winter the line would have frozen and we would have had a big mess on our hands.
Even if it didn't freeze it would have eventually busted from being buried too
shallow. Then the parking lot would have to be tore up and either a ductile iron
line like we finally received would have been placed with the proper amount of
blue board. All at Tamla's expense. She doesn't realize that we are not only
protecting others from her but we are protecting her from herself.
There are many other construction item that are on the "list" that we still need to inspect.
All of the drywall that Scott is placing for separation needs to be inspected. We inspect drywall
fastening on all applications and especially on firewall application. I have caught Scott on a few
occasions applying the drywall in the incorrect areas and on walls which have penetrations caused
by electrical service boxes. The drywall was only required on one side of the wall and could have
been installed on the other side that did not have the electrical panel.
Scotts tendencies have been to call us after an installation, instead of before. This is a
correct procedure if you don't have any questions about the work. The life -safety problem caused
by enclosing the area between the two buildings was a direct result of Scott's nonchalant attitude
toward the Building Department. After discussions with Scott and having read Tamla's letter, I
feel that his attitude is a reflection of hers. Her attitude can be clearly seen in her statement that
she had "not been aware that we needed the inspectors to be informed of the changes before being
started since they were the ones who made up the violation list".
Tamla has now provided us with a drainage plan that sends all of the water out into the
street. When I asked for a drainage plan I also asked how the water would be put into the system
or if french drains or surface retention would be used. I asked Scott Cafaro and Jeff Freiberg
these very questions. Scott informed me that Tamla just ignored him when he proposed the
question to her. Jeff called me back and stated that surface retention and french drains were out
of the question. The understanding that Tamla agreed to in order for us to provide her with
"conditional occupancy" is contingent on her finishing items by certain dates. Item #8 states
"Drainage system is reqired for the entire complex. The current system is inadequate and will
only become worse as more grass and landscaped areas are removed and more asphalt is added.
The owner must provide city with a drainage plan. Completion Date - 6/30/00. Drainage System
construction shaould be started as soon as possible and continued until parking lot is
reconstructed. Completion Date - 8/31/04". The drainage plan was critical to parking lot
construction.
It is evident that Tamla regards our direction as insignificant. It is my opinion that she will
say and do almost anything to keep the construction progress going. We keep bowing to her wish
for a letter here and one there that will help her get her financing. She will even spend $5000 on a
plan that does nothing for her (i.e. the parking lot is already built) and nothing for us. She will
install footings and then tear them out rather that get our opinion. I guess I am at a loss as to
how we should treat this situation. I think that the improvements to the complex are very good
for our community and I am willing to continue trying to work with Tamla to reach the end goal.
Thank you,
� Val Christensen
HOUSING OFFICE
RE%BURG, IDAHO 83460-4119
(208) 356-1045
March 29, 1999
Tamla Rencher
836 North Skyline Drive
Idaho Falls ID 83404
Dear Tamla:
This letter is a follow-up to our telephone conversation on Monday, March 15, 1999, in regards
to your request for a temporary approval to rent American Manor for summer and fall 1999 to
Ricks College single students. As I indicated on the telephone, Ricks will grant a one-time addi-
tional year of temporary approval for American Manor. This approval allows American Manor
to rent to 67 students for occupancy until April 22, 2000, at which time the temporary approval
will be concluded. No additional contracting may be done for summer or fall 2000 or any future
time periods until a final and complete approval is granted.
We are hopeful that granting a final approval for the entire American Manor complex will be
forthcoming. This would be based on the following criteria:
1. Ownership of the entire complex needs to be secured. This would include the
stacks now owned by Beneficial Mortgage, Investor's Financial, and any other
areas for which you do not have title.
2. Parking spaces must be obtained to meet the Ricks standard of .7 spaces per resi-
dent, with the space sizes, striping, and fire -safety issues also resolved and
approved in writing by the city of Rexburg.
3. Occupancy documents from the City must be obtained for all apartments within
the complex.
4. Our office will be ready to inspect each of those apartments as they are complet-
ed and as we are invited to do them. This inspection is to determine whether or
not minimum requirements have been met.
Representatives from the city of Rexburg and I have spoken several times through the last
month as Ricks has considered your request for temporary approval. It appears that the City is
also interested in an immediate dialogue with you regarding a plan for upgrading and a plan for
parking at American Manor. The plan that you sent with your last letter has been on file in our
office and at the City from the previous owner. However, my understanding is that no formal
approval for the plan has been granted.
The Housing Office will require documentation for each of the points listed prior to granting a
final approval for American Manor. As we discussed on Monday, Ricks will not extend tempo-
rary approval beyond April 22, 2000. Our office, however, is available at any reasonable time
to answer questions or to address concerns you may have regarding either the temporary or the
final approval process.
Sincerely,
Sharon Tuckett
Housing Director
Enclosure
cc: Bob Wilkes
Ric Page
Mike Orme
Blair Manwaring
American Manor History
Sept 1996 Disapproved Applewood Apartments.
12-9-97 Vivian Hunt (manager) has been hired by Tamla Rencher who is buying former
Applewood Apt --now called American Manor. She indicated that they had met
with City and received permission to start advertising to rent burned bldg and the
first 15 units. Sharon indicated that Ricks would need to give the OK if they
were planning to rent to single students because an approval needs to be granted.
Sharon asked for documentation of ownership for each tract of the complex.
Ric and Sharon had each talked to Tamla about the need to have the entire com-
plex under one ownership for approval.)
12-18-97 Ric, Sherstin, Sharon met with Tamla in IF to go over matters with American
Manor and Arcadia. (We took minutes of that meeting.)
12-19-97 Letter reiterating name/management, city documentation, ownership, plan of
action, advertising, parking.
12-20-97 Letter from Housing giving enrollment trends and indicating that ownership of
the entire complex need to be documented, the City of Rexburg needs to certify
the unit for occupancy, and apartments need to meet minimum approval guide-
lines.
1-5-98 Began receiving documentation of ownership for property (tracts 10 & 12).
1-5-98 Ric & Sharon inspected 209, 210, 211.
1-6-98 Asked Nedra for ernest money agreements which are signed; HUD agreement,
which had not been signed; City approval documents; & timeline for upgrading.
We received City documentation to satisfy occupancy for partial occupancy
(209, 210, 211, 115, 116, 214, 215), agreed to approve one apartment at a time.
1-6-98 Letter to Tamla regarding inspection and items that need additional work.
1-13-98 Fax received documentation for tracts 3,4,7,9,11,13.
1-21-98 Short-term plan received from Gary Hunter (man).
1-22/23-98 Received letter and fax from Nedra indicating the earnest money agreement has
been signed (we did not see a copy). Also additional information on tract 12.
1-27-98 Ric spoke with Nedra indicating a need for more definitive verification of own-
ership, such as a warranty deed, etc.
1-28-98 Ric & Sharon inspected 115, 116, 214, 215.
undated Letter (undated) received from Tamla with long term plan -of -action. (6 points
with no detail). Also a note that City has "approved all apartment in American
Manor."
2-3-98 Fax and letter received similar to undated letter, plus letter of petition to grant
approval of one building at American Manor.
Ric sent letter regarding inspection of 115, 116, 214, 215 and that we had
received short and long-term plans. Indicated that we still need ownership.
2-5-98 Memo from Mack Shirley, who had received correspondence from Tamla about
this.
2-13-98 Fax received regarding tracts 5 & 6.
2-20-98 Fax regarding a revision to agreement with Scott Taylor.
2-98 (envelope) Received a notice from UT that American Manor is advertising for block
as approved housing.
2-23 Letter granting temporary approval for 115, 116, 214, 215 through April 1998.
Asked to not advertise or contract for any period beyond that.
4-13-98 Received mail from a prospective student indicating that American Manor is
advertising.
4-23-98 Ric spoke with Tamla. She indicated that she would not have ownership until
May and that she had let one bldg go to foreclosure before she could pick it up.
Ric discussed this need for .7 parking and that she was not grandfathered. She
could not understand why she is not grandfathered. Ric explained that the unit
has not been approved with September 1996, which means that approval has
lapsed for over 17 months. She asked whom to appeal this decision to, she was
told to appeal to Jerry Price.
4-29-98 Got word that there are 90 openings at American Manor. (We have only
approved 67 because of parking.)
6-2-98 Fax indicated Tamla as sole owner of American Manor, because name is on deed
for all properties that City will grant occupancy for.
6-15-98 Ric asked Tamla to send documentation and a letter from City indicating that
Beneficial & Investors Financial tracts cannot be occupied.
6-15-98 City fax indicating property owned by Beneficial Mortgage and Investors
Financial has no parking so cannot be occupied.
6-16-98 Fax of deeds for tracts 5,6 (HUD), 3,4,7,9,11,13, (Blackbear) 10 (Clarke and
Hawkes).
6-17-98 Ric & Sharon inspected apts 108, 109, 111,112,208,209,210,211,212,213.
6-18-98 Fax from Tamla of City indicating parking space sizes and statement of
Beneficial Mortgage and Investors Financial as not able to receive certificates of
occupancy because no parking.
6-24-98 Received a faxed copy of long-term plan for safety repairs - still no dates for
completion, etc.
6-25-98 Received fax from Alliance Title of warranty deed for tract 12 and IA.
6-25-98 Received original copy of new long-term plan for safety repairs.
6-26-98 Received fax of longer-term plan with dates for completion.
6-29-98 Letter to Tamla regarding application for approval:
ownership - have documentation for all but tracts 1,2,3 (no parking for these)
City approval - for 115, 116, 214, 215
College inspection - 108, 109, 111, 112, 208, 209, 210, 211, 212, 213
Parking - 47 spaces (at .7 will occupy 67 students).
Disposition - temporary and limited approval until April 24, 1999, with no
advertising for any future term.
6-29-98 Fax from Tamla with statements of long-term plan, ownership for tract 12,
scheduled City inspection, indication that they are meeting City on July 8th, they
are fulfilling punch list okayed by City.
6-30-98 Sharon talked to Blair Manwaring at the City. He has no time line for repairs.
He does not have an appointment on July 8th as indicated by Tamla. He has
asked that they have plumbing, electrical, & fire inspections before he does a
final. Parking lines are not painted correctly. City will not let them occupy
more than they have parking for.
6-30-98 Spoke to Liz (manager) to let her know to fill not more than 67 students and no
advertising or contraction beyond April 1999.
7-9-98 Fax that City has inspected 108, 109, 208, 209, 111, 112, 210, 211, 212, 213.
7-10-98 Ric talked to Jerry Price and Liz (man) as asked to rent for 3rd summer term
only, wait a week on renting for fall. The issue is still no clear title to the entire
complex.
7-13-98 Letter to Tamla to rent to students as indicated in 6-29-98 letter. Reiterated that
we need .7 parking.
8-12-98 Housing secretary called to check on vacancies and was told that they have 114
openings. (We have approved them for 67 total.)
8-24-98 Ric & Sharon did inspection in 106, 107, 206, 207.
8-26-98 Letter to Tamla about inspections and reiterated that only 67 beds could be used
because there are only 47 parking places. Asked for a parking plan with City
approval.
8-26-98 Received memo from Fire Department that owner needs to submit parking plan
because fire truck cannot get through the complex.
9-3-98 Received City approval for 106, 107, 206, 207.
9-8-98 Letter to Tamla indicating City approval for 106, 107, 206, 207. Sent copies of
City letter and mem from the Fire Department.
9-21-98 Received call from Beneficial Financial wanting to get their portion approved.
Ric discussed parking, getting the property to an acceptable facility level. She
was not aware that another group had opened a portion already. Ric left a mes-
sage with Tamla to call Beneficial Finance if interested.
10-21-98 Letter to Tamla suggesting we review for occupancy beyond April 24, 1999.
1-11-99 Fax received from Tamla petitioning for an extension of approval form April 25,
1999 - April 25, 2000, understanding that the terms would be the same.
1-20-99 Letter to Tamla asking for updates of improvements, current status, plan for full
compliance. Also ownership status was asked for, along with City approval of
long-term plan, and the parking issue.
1-25-99 Received letter from Tamla indicating that l of 13 tracts have been purchased, E
bldg repair continue, Desire to purchase Investor's Financial and Beneficial
Mortgage, City inspections have been completed, a parking plan has been
approved by City.
2-99 Sharon spoke with Blair Manwaring. He checked and did not find a parking
plan on file, nor did he find any approval for a long-term plan. He indicated that
although he has spoken with Scott Caffaro, the builder, he has not spoken with
the owner and approved a plan.
2-5-99 Letter sent to Tamla asking for City documentation of approval for long-term
plan. Also questioned the statement on the long-term plan that the parking was
"grandfathered," and asked for more information about ownership for tracts 2
and 3.
2-12-99 Received letter from Tamla along with 29 pages of "Steve Clark Apartments"
that seems to be a former inspection by the City of Rexburg. Tamla explains that
she is grandfathered under the 1968 parking ordinance because there were stu-
dents in the complex ending in April 1997 and then beginning Feb 1998. She
indicated that parking plan is "still' approved fro the past eleven years. She fur-
ther states that the City has approved the long-term plan and that tract 2 and 3
cannot be rented because there is no parking.
2-24-98 Mike Orme called and had received a copy of the letter from Tamla.
2-26-98 Sharon spoke again with Blair Manwaring. He has received a letter from Tamla
in which parking was being discussed. He has sent that on to the City attorney,
who indicated they would ask for .7 parking.
3-1-98 Sharon will meet with Blair Manwaring.
JUN -18-90 THU 00:46 AN Lr . 11 i ch as I Suiues 20852CIO022
0j.
--CO i vayes (G)
c Ille�
`'d-7-3,03(,
C on+4'1
P�P
3s�_ �iPs
P. k]1
JUN -10--31 THU 08:46 AN Dr. N ichaal James 2005200022 p,02
JUNE 18,1998
TO WHOM IT MAY CONCERN:
IN REXBURG, ACCORDING TO ZONING ORDINANCE 725, AN APARTMENT
COMPLEX MUST PROVIDE OFF-STREET PARKING IN ORDER TO SECURE A
CERTIFICATE OF OCCUPANCY.
Till'. RE• QUIRED NUMBER OF SPACES FOR RES1DLNTIAL SINGLE OR MIiL'IT-
FAMILY DWELLINGS IS 2 SPACES PER UNIT. TETE REQUIRED NUMBER OF
SPACES OF STUDENT HOUSING IS 0-1 SPACES PER STUDENT'.
EACH REQUIRED OFF-STREET PARKING SPACE SHALL BEAT LEAST NINE
FEET (9') IN WIDTH AND AT LEAST EIGHTEEN FTE;f (18') IN LENCi'TIE,
EXCLUSIVE OF ACCESS DRIVE AND AISLES. UP TO 25°x6 (OR 409„ FOP.
STUDENT HOUSING) OF THE SPACES MAY BE ALLOCATED FOR COMPACT
CARS WITH A MINIMUM STALL WIDTH OF 8' AND LENGTH OF 15'.
TRACT 3 O NED BY BENEFICIAL MORTGAGE AND TRACT 1 &1E&2
OWNED BY INVESTORS FINANCIAL AS RECORDED IN THE LEGIT.
DESCRIPTIONS DO NOT MEET THIS PARKD;G REQUIREMENT. THUS, TIfEY
''IRF- UNABLE TO RECEIVE FROM THE CI'T Y OF REXBURG A CERTIFICATE OF
OCCUPANCY AND ARE AT THE PRESENT CONDITION UNOCCUPIABLE.
THANK YOU,
RLAIR AIANWARING
BUILDING INSPECTOR.
REXBURG, IDAHO
IHU OU :47 HH Dr. f9 i ch ua I Jn...as
G10GJJb7�L:� HLL 11 -ERIC I 1 I LL N< X.
�.� r•r IL:h
2OBb2U'8022 F' {pS
d-;4 r,1j fNL)U 1_3 ^1i lb:yl
-rkA-i2l- io
WALE FOA OwRTFN OLWgo ulf .V.
SECTION. PID tc _r In<A 5 an.Na ID •adC y7D MY: .na o+syo.n a .e,q,
FW .IC. .nW nd AUYy . l.b sN.ln.. S loch 373 I..1: .n. el .ev... .1(b2S el t .en,
.110NT0 I ND YEUVSS K� N F SNEE1
w•�u+n � •un uc. ai .,.�
HU O'd:411 fN 1),.1-1l ch -I Ju... 20852a:10v% 1'_,�4
COMMI'TMEN'T' FOR TITLE INSURANCE
CONTINUATION PAGE
SCHEDULE A
Order Number. 5-12245-V
TRACT 1: BEGINNING AT A POINT THAT IS NORTH 16.5 FEET AND EAST 68 FEET FROM
THE NORTHWEST CORNER OF IAT 3 BLOCK 50 OF THE ORIGINAL TOWNSITE OF
REXBURG, MADISON COUNTY, IDAHO, AS PER THE RECORDED PLAT THEREOF; THENCE
EAST 26 FEET; THENCE SOUTH 44.0 FEET; THENCE WEST 26 FEET; THENCE NORTH 44.0
FEET TO THE POINT OF BEGINNING.
TRACT IE: TOGETHER WITH PARKING DESCRIPTION F'OR INGRESS AND EGRESS FOR
IIS COMMON USE OF OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT
THAT IS SOUTH 27.5 FEET FROM THE NORTHWEST CORNER OF LOT 3 BLOCK 50 OF TILE
ORIGINAL TOWNSITE OF REXBURG, MADISON COUNTY, IDAHO AS PER TIM RECORDED
PLAT THEREOF; AND RUNNING THENCE EAST 1".0 FFFT; THENCE SOUTH 10.0 FEET;
THENCE WEST 146.0 FEET; THENCE NORTH 10.0 FEET TO THE POINT OF BEGINNING:
ALSO TOGETHE, R WITH A CENTERLINE EASEMENT DESCRIPTION OF 20.0 FOOT STRIP
THAT ADJOINS THE ABOVE INGRESS AND EGRESS TO BE USED IN COMMON WITH
OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT THAT IS 53.5 FEET SOUTH
FROM THE NORTHWEST CORNER OF LOT 3 BLOCK 50 OF THE ORIGINAL TOWNSITE OF
REXBURG, MADISON COUNTY, IDAHO, AS PER TIM RECORDED PIAT THEREOF; ,AND
RUNNING THENCE EAST 165.0 FEET.
ALSO TOGETHER WITH A CENI'ERLINE EASEMENT DESCRIPTION FOR 20.0 FOOT STRIP
THAT ADJOINS THE ABOVE FOR INGRESS AND EGRESS TO BE USED IN COMMON WITH
OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT THAT IS 47.5 FEET SOI.ITH
FROM THE NORTHWEST CORNER OF LOT 3 BLOCK 50 OF THE ORIGINAL TOWNSI'TE OF
REXBURG, MADISON COUNTY, IDAHO, AS PER THE RECORDED PLAT 'THEREOF; AND
RUNNING THENCE EAST 165.0 FEET.
TRACT 2: BEGINNING AT A POINT THAT IS NORTH 16.5 FEET AND EAST 42 FEET FROM
THE NORTHWEST CORNER OF LOT 3 BLOCK 50 OF TIIF ORIGINAL, TOWNSITE OF
REXBURG, MADISON COUNTY, IDAHO, AS PER THE RECORDED PLAT THEREOF; THENCE
EAST 26 FEET; THENCE SOUTH 44.0 FEET; THENCE WEST 26 FEET; THENCE NORTH 44.0
FEET TO THE POINT OF BEGINNING.
TRACT' 2E: TOGETHER WITH PARKING DESCRIPTION FOR INGRESS AND EGRESS FOR
THE COMMON USE OF OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT
THAT IS SOUTH 27.5 FEET FROM THE NORTHWEST CORNER OF LOT 3 BLOCK 50 OF THE
ORIGINAL TOWNSITE OF REXBURG, MADISON COUNTY, IDAHO AS PER THE RECOR-DED
PLAT THEREOF; AND RUNNING THENCE EAST 146.0 FEET; THENCE SOUTH 10.0 BEET;
THENCE WEST 146.0 FEET; THENCE NORTH 10.0 FEET TO THE POINT OF BEGINNING.
b lr::4Y RPI Lir . II I ,.IIua I .7 a III= - 9k];;,.2;"H0S'! 1', o';
FISO TOGETHER WITH A CENTERLINE EASEMENT DESCRIPTION OF 20.0 FOOT' STRIP
THAT ADJOINS THE ABOVE INGRESS AND EGRESS TO BE USED IN COMMON WI'T'H
OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT THAT IS 53.5 FEET SO UTIs
FROM THE NORTHWEST CORNER OF LOT 3 BLACK 50 OF THE ORIGINAL TOWNSITE OF
REXBURG, MADISON COUNTY, IDAHO, AS PER THE RECORDED PLAT THEREOF; AND
RUNNING THENCE EAST 165.0 FEET.
ALSO TOGETHER WITH A CENTERLINE EASEMENT DESCRIPTION FOR 20.0 FOOT STRIP
THAT ADJOINS THE ABOVE FOR INGRESS AND EGRESS TO BE USED IN COMMON WITH
OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT THAT IS 473 FEET SOUTH
FROM THE NORTHWEST CORNER OF LOT 3 BLACK 50 OF THE ORIGINAL TOWNSIT'L OF
REXBURG, MADISON COUNTY, IDAHO, AS PER THE RECORDED PLAT THEREOF; AND
RUNNING THENCE EAST 165.0 FEET.
TRACT 3: COMMENCING AT A POINT 16.5 FEET NORTH AND 94 FEET EAST OF TILE
NORTHWEST CORNER OF LOT 3 IN BLOCK 50 OF THE TOWNSITE OF REXBURG, MADISON
COUNTY, IDAHO, AS PER THE RECORDED PLAT THEREOF; AND RUNNING THENCE EAST
52 FEET, THENCE SOUTH 54 FEET, THENCE WEST 146 FEET, THENCE NORTH 10 FEET,
THENCE EAST 94 FEET, THENCE NORTH 44 FEET TO THE POINT OF BEGINNING.
TRACT 3E: TOGETHER WITH AN EASEMENT FOR INGRESS AND EGRESS TO BE USED IN
COMMON WITH OTIIERS BEING 20 FEET WIDE; DESCRIBED AS FOLLOWS: COMMENCING
AT A POINT 37.5 FEET SOUTH OF THE NORTHWEST CORNER OF LOT 3 IN BLACK 50 OF
THE TOWNSITE OF REXBURG, MADISON COUNTY, IDAHO, AS PER THE RECORDED PLAT
THEREOF; AND RUNNING THENCE EAST 146 FEET, THENCE SOUTH 20 FEET; THENcr
EAST 146 FEET, THENCE NORTH 20 FEET TO THE POINT OF BEGINNING.
TRACT 4: BEGINNING AT A POINT THAT IS NORTH 16.5 FEET OF THE NORTHWEST
CORNER OF IAT 3 BLACK 50 OF THE ORIGINAL TOWNSITE OF REXBURG, MADISON
COUNTY, IDAHO, AS, PER THE RECORDED PLAT THEREOF; THENCE EAST 42 FEET;
THENCE SOUTH 44.0 FEET; THENCE WEST 42 FEET; THENCE NOR'T'H 44.0 FEET TO THE
POINT OF BEGINNING.
TRACT 4E: TOGETHER WITH PARKING DESCRIPTION FOR INGRESS AND EGRESS FOR
THE COMMON USE OF OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT
THAT IS SOUTH 27.5 FEETFROM THE NORTHWEST CORNER OF IAT 3 BLOCK 50 OF THE
ORIGINAL TOWNSITE OF REXBURG, MADISON COUNTY, IDAHO, AS PER THE RECORDED
PLAT THEREOF; AND RUNNING THENCE EAST 146.0 FEET; THENCE SOUTH 10.0 FEET;
THENCE WEST 146.0 FEET; THENCE NORTH 10.0 FEET TO THE POINT OF BEGINNING.
ALSO TOGETHER WITH A CENTERLINE EASEMENT DESCRIPTION FOR 20.0 FOOT STRIP
THAT ADJOINS THE ABOVE FOR INGRESS AND EGRESS TO BE USED IN COMMON WITH
OTHERS, DESCRIBED AS FOLLOWS: BEGINNING AT A POINT THAT IS 53.5 FEET SOUTH
FROM THE NORTHWEST CORNIER OF LOT 3 BLOCK 50 OF THE ORIGINAL TOWNSI'11, OF
REXBURG, MADISON COUN'T'Y, IDAHO, AS PER THE RECORDED PLAT THEREOF; AND
RUNNING THENCE EAST 165.0 FEET.
LONCi'f T%l PLAN FOR SAFETY REPAIRS FOR AMERICAN MANOR
LONG I'ERIVI PLAN TO CORRECT ITEMS WMFRATED ON THE SAFE7Y
VIOLATION LIST FROM THE CnY OF RF,XBLJRG FOR AMERICAN MANOR
DATED FEB. 2, 1996 RESUBMUM-.D BY TARILA RENCHER ON JLir'F 24, 1998.
Each item listed on the safety check list w.is evaluated. Most have already been con•ected.
The fullowing is a plsm of long tams action to correct till- items remaining.
7/1j98 1) histall smake dehwctors in every bedroom.
t 2) Ail gutters and leaderw will cotulect into a 3 iudt perforaled pipe widt gravel as a leach
( field and connect into the city sewer.
3) West of apartinent complex 1-A remove existing concrete in sidewalk, excavate to
pr Opel- level, refunir concrete over di ainage, roan around and above, and iustull proper
1 ABS pipe to e1in»nt3to hipping haz ard. r
4) histalI double layer of 518" fire resistAnt gypaon bow -d to ubtain one how- fire resistance
ql q? to meet code.
5) Construct 4 foot retaining wall of concrete on nortli side of building 1-A 5" thick for
length of complex. Backfill to cover exposed foundation footings and to raise pound level
it -20 of building 1-A to such an elevation dint div bottom floor will qualify as a "baaenient".
q�l I 6) Reroof entire complex with 30 year asphalt or fiberglass shingles, soliet venting along
with ridge roll venting, replacing corroded plywood its needed.
7) All theililostats will be examined and apps opi iah ly replaced or, repaired in die heating
system to provide an adequtde heating facility that will maintain 70 degrees F.
ll 8) All w iadowi will be replaced to meet egt eis Quite. All Wth'oom windows will be
replaced and meet proper required escape dimension;
9) All balcony acid exterior stairs will be replaced acid cvidened to meet section 3303 (A)
qt k `i,Qg acid etaittrea d will"be extended to 11112" wide and 7 1/2" stair rise.
10) All necessary exterior doors will be replaced to match interior and exterior floor
It L -kw landitigs. All landings will be corrected and have a minimum of 48" widdL
qj ('
11) All interior staircases will meet required heaih•oom of 6'6" as listed ir, section 3306.
41 The rise of every step and die tread will meet requirements
12) The floor or iwrding will not exceed over 1" over die du eshold doorway. The lengdi of
the downstairs; landing in apartment # 108 will be extended to die required 44" before die
first step outward from the door.
REXBURG MADISON COUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
THIS IS TO GIVE NOTICE THAT:
An inspection of the American Manor Apartments located at 151 South
lgt East in Rexburg, Idaho was conducted on this date and that as
nearly as could be determined, was found to be in compliance with
the Uniform Fire Code and ordinances of the City of Rexburg that
are presently in effect, with the following exceptions:
The majority of items listed below are existing problems and will
take time to correct. Attached is a list of items found in the
initial inspection on this date.
Sec 902 Fire apparatus road is required It would need to be a
minimum of 20 _fes wide with a turn around in the complex because
it would be over 150 feet and a dead end.
Sec 903 Water supply needs to be fiaured and hydrants installed
within the complex as required.
Sec, 1202 1 am concerned that the storage on the back of the one
_• -•
1002 Portable • to be maintained,
1 •��• • - u. •
WARM• -� ••
••1 •• • -• • ••
Note: This inspection was necessarily limited to items and areas in
plain and full view of the inspector. This inspection cannot
ensure or verify the compliance of the items or areas that are
obstructed from the inspector's view by construction or access.
The City of Rexburg can accept no responsibility for verification
of code compliance in such areas. Such verification becomes the
sole responsibility and liability of the property owner. Persons
preforming corrective action should contact the Rexburg Madison
County Fire Department at (208) 359-3010 for specifics or questions
Feb 12, 1999
Ricks College Housing Department
Rexburg, Id 83440
Dear Sharon Tuckett,
I am very anxious to receive an extension from the Rick& College Housing Department for
this coming year. Numerous inquires have been made by students and parents. Like all of
the other complexes, it is now time to advertise and send contracts for the coming year.
Concerning your "few additional questions".
A. The city has never required a parking plan from American Manor. Hence, the
city does not have a copy of documents regarding our parking plan. The parking is not
mentioned on the enclosed violation list presented to Applewood. The city has never
withheld approval because of parking. Parking has never and is not now an item of
concern for approval with the city.
I am petitioning for an EXTENSION of the temporary approval of American
Manor for student occupancy for 1999-2000. As originally agreed by both Ricks College
and the City of Rexburg, approval is being granted building by building.. With the present
limited number of approved student apartments, the parking is not an issue at this time at
American Manor.
The parking has become an issue only to Ricks College Housing. My legal counsel
is prepared to produce necessary documents to show that according to Rexburg City
Ordinance #478 passed in 1968 (which required one parking space per every 2 students
up to and including 24 students and then one parking space for each additional 3 students)
Country Cove/ Applewood/ American Manor was is compliance at the time of occupancy.
Further, he has docmnents to show student occupancy ending April of 1997( in the form of
signed contract) and commencing Feb of 1998 (in the form of signed contract). This will
agree vvith the housing department records. Hence, Hre complex was NOT out of the
single -students rental market for over a year, and the 1999 standard parking requirements
do not apply and falls under the condition known as the "Ch-andfither" clause.
In October of 1998 the fire marshal mentioned his concerns about the changes in
pavement paint striping --so we agreed, as soon as the snow melts, this striping will return
to the approved parking plan that was been in effect for 11 years. The old paint is still
visible and will be duplicated Since the old parking plan was approved and used for 11
years, and nothing has changed as to the use of the complex and/or number of students
occupying premises, by city ordinance, the parking plan is still approved.
B. 'The long-tetyn plats fGt` A net`ieati .ianor was Subtaitted to die city iii 1995.
Without it, they refused to grant approval of any of die. complex. With it, they have granted
approval to 4 of the buildings. The city is pleased with the improvements that are being
made and are eager to see the project succeed.
We are progressing as scheduled. Yes, the items to be finished by 1998 have
been completed successfully.
I will be more than happy to send another copy of this long-term plan to the city if
they so request it
C. The ownership of tracts 2 and 3 have had no changes since temporary approval
was granted last year. At die present time, rhiunerous legalities are being worked out with
MY attorney. It is for this reason that we are petitioning for an extension of the tenhporar,
approval. There are unpaid back taxes, IP s liens, and NIR, appraisals to be ordered slid
reviewed before clear title can be given to these properties These problems are being
resolved, but it will require more time and legal paper work.
Nothing has transpired in regard to M -act 2 and 3 that has changed the situation
from last year. That is, both tracts and die aparhnents thereon do not have, nor can they
obtain a city issued certificate of occupancy. Hence, no one can occupy them. They can be
used onuly for storage. There is no additional documentation needed for the status quo.
.Enclosed is a copy of the city's notification that no one can occupy tract 2 and 3.
This complies with die Rick's Housing Regulations.
If you could please review these items aid grant all extension of die approval to American
Manor as quickly as possible, I would be most appreciative. We ;would like the swine
opporfinuty as all of the other complexes in Rexburg to advertise early to fill treir
apartments with quality students.
Sincerely,
_;lam an
Tamla Rencher
1748 Jeppson Ave
Idalio Falls, Id 83440
(208) 529-3836
cc: Robert Wilkes
Mike Orme, Legal Counsel
Dear Blair Mamvaring:
Enclosed in a copy of the long-term plan for American Manor that was submitted in 1998.
We are progressing as scheduled. The items to be finished by 1998 have been completed
successfully.
I am petitioning for student occupancy for 1999-2000. Ricks College Housing requires an
updated signature. Would you be so kind as to review the following and sign or initial
below.
Thank you for your time
LONG TERM PLAN FOR SAFETY REPAIRS FOR AMERICAN MANOR
LONG TERM PLAN TO CORRECT ITEMS NUMERATED ON THE SAFETY
VIOLATION LIST FROM THE CITY OF REXBURG FOR AMERICAN MANOR
DATED FEB. 2, 1996 RESUBMITTED BY TAMLA RENCHF_R ON JUNE 24, 1998.
(approximate time line for completion --each apartment will be repaired simultaneously --
repairs to the entire complex will then be accomplished)
Each item listed on die safety check list was evaluated. Moat have already been corrected.
The following is a plan of long term action to correct the items remaining.
9/1/1998 1) Install smoke detectors in every bedroom
9/1/2000 2) All gutters and leaders will connect into a 3 inch perforated pipe with
gravel as a leach field and connect into the city sewer. ?
9/1/2000 3) West of apartment complex 1-A remove existing concrete in sidewalk,
excavate to proper level, reform concrete over drainage, form around and
above, and install proper ABS pipe to eliminate tripping hazard.
9/1/1998 4) Install double layer of 5/8" fire resistant gypson board to obtain one
hour fire resistance to meet code.
9/1/2001 5) Construct 4 foot retaining wall of concrete on north side of building 1-A
5" thick for length of complex. Backfill to cover exposed foundation
footings and to raise ground level of building 1 A to such an elevation that
the bottom floor will qualify as a "basement'.
9/1/2000 6) Reroof entire complex with 30 year asphalt or fiberglass shingles, soffet
venting along with ridge roll venting, replacing corroded plywood as
needed.
9/1/1998 7) All thermostats will be examined and appropriately replaced or repaired
in the heating system to provide an adequate heating facility that will
maintain 70 degrees F.
9/1/2000 8) All windows will be replaced to meet egress code. All bedroom
windows will be replaced and meet proper required escape dimensions.
9/1/1998 9) All balcony and exterior stairs will be replaced and widened to meet
section 3303 (A) and stairtread will be extended to 11 1/2" wide and 7 1/2"
stair rise.
9/1/2000 10) All necessary exterior doors will be replaced to match interior and
exterior floor landings. All landings will be -corrected and have a niinimwn
of 48" width.
9/1/1999 11) All interior staircases will meet required headroom of 64' as listed in
section 3306. The rise of every step and the tread will meet requirements
9/1/1999 12) The floor or landing will not exceed over 1" over the threshold
doorway. The length of the downstairs landing in apartment #108 will be
extended to the required 44" before the first step outward from the door.
PARKING: (Note: This was not listed on the requirements for reapproval by the city.
However, Ricks Housing as deemed it necessary to clarify the city's position on parking.
9/1/2002 13) There will be no changes as to number of students occupying premises,
hence the complex is presently "Grandfathered" as to existing number of
parking spaces and number of students. The design, lay -out, and striping of
the parking lot will be restored to orginal approved design.
However, in the future parking is to be increased as conditions allow.
1) Manager's house to be moved and property to be paved for parking. 2)
Spaces to be rented from Carlson House. 3) When adjoining properties
(presently owned by Dr. Young) to come available, to be purchased and
paved for additional parking 4) Housing contracts to restrict number of
vehicles to be brought by students (a refimdable deposit to be sect to those
reserving aparking space.)
None of these improvements are connected with present plan to
receive approval by the city. If for the past 11 years the number of students
and the lay -out, design, and number of parking spaces have remained
unchanged, the city approval must also be unchanged.
Ricks College requires an updated signature for approval for student housing in 1999-2000
(Blair Manwaring) (Date)
MEMO:
TO: JOE LAIRD, BUILDING OFFICIAL
FROM: CHRIS HUSKINSON, FIRE DEPARTMENT
DATE: JULY 10, 1998
RE: AMERICAN MANOR APARTMENTS
Joe,
Attached please find an inspection form highlighting items found deficient during an inspection
at the site located at 151 South First East in Rexburg. All noted items have been resolved with
the exception of water supply, fire apparatus access, and a storage unit located behind one unit.
These will be worked on as the remodeling project progresses.
Chris Huskinson
•.u��uvi.v airu Oulx l,v V1v1 riAn onrANIMLN'r
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
THIS IS TO GIVE NOTICE THAT:
An inspection of the American Manor Apartments located at 151 South
st East in Rexburg, Idaho was conducted on this date and that as
nearly as could be determined, was found to be in compliance with
the Uniform Fire Code and ordinances of the City of Rexburg that
are presently in effect, with the following exceptions:
The majority of items listed below are existing problems and will
take time to correct. Attached is a list of items found in the
initial inspection on this date.
Sec 902 Fire apparatus road is reau;rad It would need to be a
minimum of 20 feet wide with a turn around in the complQx because
it would be over 150 feet and a dead end.
sec, 903 water supply needs to be figured and hydrae install
within the complex�gguirpd
Sec 1202 I am concerned hat the storage on the back of the one
apartment complexcould block the egress windows (Behind units_ 212
and 213) --
SQc, 8504 Electrical outlet and switch Qovers in some room needs
replaced.
lec. 1007.,2.9,2 Some. of your sm.Dke e '•-�T.•i-1-lR•tRlla
rooms,0�- Sec. 1103.3.2.4 Combustible materials ah -all not be stored in boiler
mechaniQal roomsoL,,electrical eauil2ment rooms,
Note: This inspection was necessarily limited to items and areas in
plain and full view of the inspector. This inspection cannot
ensure or verify the compliance of the items or areas that are
obstructed from the inspector's view by construction or access.
The City of Rexburg can accept no responsibility for verification
of code compliance in such areas. Such verification becomes the
sole responsibility and liability of the property owner. Persons
preforming corrective action should contact the Rexburg Madison
County Fire Department at (208) 359-3010 for specifics or questions
- -- --amu- y i111 icyuii ILLI IiUO. t ny uu,3e vaoie aeIlciencles Wnich
are a distinct hazard to life and/or property are subject to
criminal enforcement if they are not remedied immediately.
July 7, 1998.
Chris Huskinson Date
Fire Inspector
Noted deficiencies at American Manor located at 151 South First East
July 7,1998
Units #111 and #112:
-service and maintain fire extinguishers
-smoke detectors are mounted in dead air space, need to be moved
-front door sticks
Unit #210:
-attach outside railing to main railing
-fill in gap around porch light
-move fire extinguisher and maintain
-move smoke detectors
Unit #211:
-foam fire stops in the soffit
-maintain extinguisher
-move smoke detectors
Unit # 108:
-railings need to be fixed
-remove smoke detector (hardwired) upstairs
-move battery detectors
-maintain and service fire extinguisher
Unit #109:
-weatherstripping on front door needs replacing (gap between door and jamb)
-spackle around cable jack
-finish enclosing space between upstairs units
-outside gas line needs securing
-move smoke detectors
-maintain and service fire extinguisher
Unit #208:
-upstairs storage area has gaps in sheetrock
-foam safeties
-needs attic access
-move smoke detectors
-maintain and service fire extinguishers
Unit #110:
-fix exterior drain pipe (north wall)
Water Room: (water heater room at rear of building)
-spackle holes in walls
-replace outlet covers
Unit # 213:
-Rear storage/porch area needs to be cleared out and maintained for egress requirements.
It was noted that it will be removed as the renovation project moves forward.
-move smoke detectors
-maintain and service fire extinguishers
Unit #212:
- foam safeties
-seal around kitchen light
Maintenance room:
-replace plate over electrical box
-replace outlet covers
-spackle all gaps
-foam pipes leading into north wall
b
MEMO:
TO: JOE LAIRD, BUILDING OFFICIAL
FROM: CHRIS HUSKINSON, FIRE DEPARTMENT
DATE: JULY 10, 1998
RE: AMERICAN MANOR APARTMENTS
Joe,
Attached please find an inspection form highlighting items found deficient during an inspection
at the site located at 151 South First East in Rexburg. All noted items have been resolved with
the exception of water supply, fire apparatus access, and a storage unit located behind one unit.
These will be worked on as the remodeling project progresses.
Chris Huskinson
,�f C
s�Y
�,���•s slso f�GGP�y ,
d �d
iu UIZWN WUNTY FIRE DEPARTMENT
P.O. Box 280
26 North Center
Rexburg, Idaho 83440
(208) 359-3010
THIS IS TO GIVE NOTICE THAT:
An inspection of the American Manor Apartment3 located at 151 South
lst East in Rexburg, Idaho was conducted on this date and that as
nearly as could be determined, was found to be in compliance with
the Uniform Fire Code and ordinances of the City of Rexburg that
are presently in effect, with the following exceptions:
The majority of items listed below are existing problems and will
take time to correct. Attached is a list of items found in the
initial inspection on this date.
Sec. 902 Fire apparatus road is reaujred It would ne d to be a
minimum of 20 feet wide with a turn around in the rom 1 x ecs
it would be over 150 feet and a dead end,p eat e
SPc• 903 _Water supply needs LQ be figured and hydrants in�Ied
within_ the compl x as r guired.
Sec. 1202 I am concern d that the storage on the back of the one
apartment complex could block the ear ss windows. (Behind units 212
and 213)
V Sec, 85(14 Electri 1 out I and switch covers in m oom n �9
C/� re is .e .
Sec. 1002 Portable fire extinguishers ne d to be maintained The
attached nanor ovni �, ., _._ _ „
�C. 1007 2.9.2 Some of your smoke detectors are located in the
wrong areas,
Sec. 110 3.2.4 Combustible materials shall not be st r d In boiler
rooms, mechanical rooms or elec rival quipm nt room
s.
Note: This inspection was necessarily limited to items and areas in
plain and full view of the inspector. This inspection cannot
ensure or verify the compliance of the items or areas that are
obstructed from the inspector's view by construction or access.
The City of Rexburg can accept no responsibility for verification
Of code compliance in such areas. Such verification becomes the
sole responsibility and liability of the property owner. Persons
preforming corrective action should contact the Rexburg Madison
County Fire Department at (208) 359-3010 for specifics or questions
are a distinct hazard to life and/or property are subject to
criminal enforcement if they are not remedied immediately.
Chris Huskinson
Fire Inspector
i
July 7, 1998
Date
Noted deficiencies at American Manor located at 151 South First East:
July 7,1998
Units # 111 and # 112:
-service and maintain fire extinguishers
-smoke detectors are mounted in dead air space, need to be moved
-front door sticks
Unit #210:
-attach outside railing to main railing
-fill in gap around porch light
-move fire extinguisher and maintain
-move smoke detectors
Unit #211:
-foam fire stops in the soffit
-maintain extinguisher
-move smoke detectors
Unit #108:
-railings need to be fixed
-remove smoke detector (hardwired) upstairs
-move battery detectors
-maintain and service fire extinguisher
Unit # 109:
-weatherstripping on front door needs replacing (gap between door and jamb)
-spackle around cable jack
-finish enclosing space between upstairs units
-outside gas line needs securing
-move smoke detectors
-maintain and service fire extinguisher
Unit #208:
-upstairs storage area has gaps in sheetrock
-foam safeties
-needs attic access
-move smoke detectors
-maintain and service fire extinguishers
Unit #110:
-fix exterior drain pipe (north wall)
Water Room: (water heater room at rear of building)
-spackle holes in walls
-replace outlet covers
Unit # 213:
-Rear storage/porch area needs to be cleared out and maintained for egress requirements.
It was noted that it will be removed as the renovation project moves forward.
-move smoke detectors
-maintain and service fire extinguishers
Unit #212:
- foam safeties
-seal around kitchen light
Maintenance room:
-replace plate over electrical box
-replace outlet covers
-spackle all gaps
-foam pipes leading into north wall
io miron Tuckett
Ricks College
Rexburg, Idaho 83440
Re: American Manor Apartments
Dear Sharon:
STATE OF IDAHO
PO Box 280
12 North Center Street
Rexburg, Idaho 83440
Phone (208) 359-3020
Fax (208) 359-3022
e-mail rexburg@srv.net
An inspection was made at American Manor by the Fire Department, Electrical Inspector,
Plumbing Inspector and myself. There were several minor deficiencies that were present. I'm
confident that Scott Caffar6would have them completed by Friday the 10'h of July. None of
them were so significant that it would preclude rental to students for the third summer term.
The following units were inspected 108, 109, 208, 209, 111, 112, 210, 211, 212, 213. If you
have any questions don't hesitate to call me.
Very Truly Yours,
Blair Manwaring, Building Inspector