HomeMy WebLinkAboutINSPECTION TICKET - 17-00340 - 888 & 890 Parkside Dr - Temporary PowerInspection Ticket Temporary Electrical Service on 06/26/2017: PASS Permit Number: 17-00340Permit Details Electrical Only Residential Permit Issued Date: 06/23/2017 Final Inspections Required 888 Parkside Dr 888 & 890 Parkside Dr - Temporary Power Inspection Details bret.stoddard@rexburg.org Inspected By: Bret Stoddard Temporary Electrical Service on 06/26/2017: PASS D ESCRIPTIO N CO MMEN TS STATUS Unused openings have been effectively closed (K.O. seals, etc.) 110.12(A), 408.7 COMPLETED Securely mounted gear-panels, meter base, etc. 110.13 COMPLETED Proper clearances about electrical equipment indoors and outdoors. 110.26 (A), (E),(E)(2) and (F) COMPLETED •Grounding electrode system installed-ufer, ground rods, etc. 250.52(A)(4-7) COMPLETED Grounding electrode system conductors sized and protected appropriately. 250.66, 250.64(F), 250.64(A)(B) COMPLETED Grounding electrode conductor is either un-spliced or spliced using approved methods. 250.64(C)(F) COMPLETED Temporary 125V & 250V 15A & 20A receptacles must have GFCI protection. 590.4(D) Three GFCI receptacles 120V and one 240V installed all with GFCI protection provided. COMPLETED Temporary receptacles in wet/damp locations must have in-use extra duty covers. 590.4(D)(2), 406.9(A)(B) COMPLETED Any associated wiring with service meets article 300 wiring methods. COMPLETED Identify wet and damp locations for panels-NEMA 3R, etc. 408.16, 408.37, 312.12 COMPLETED Panel or switchgear service rated. 408.3(C)COMPLETED Approved to be energized for temporary power (will send permit with temporary note to utility) To be energized for temporary power.COMPLETED