HomeMy WebLinkAboutAVAIL FAULT CURRENT - 16-00478-482 - Campus Courtyard 2E:7*N
BUSSMANN
SERIES
Your System Details
Project Name: w,Campus courtyard l
System Type: Single -Phase
Creator Name: TIM Clarkson
Creator Email: clarksin2004@cableone.net
Creator Company/Organization: Castle electric
Creator Title/Position: Owner
Creation Date: Jul 18, 2016 @ 2:21pm
LVA
TRANSFORMER
KVA 100
Voltage _d„a. 240
%Z 1.50
%Z TOL -10% (Max Fault)
bowl.,.. mu 30,867 AMPS.
Im„is.,. n_ro 46,301 AMPS
Voltage (L -L) 240 V
LENGTH 60FT
SIZE 250
QTY 3
(per phase)
TYPE Three -Conductor Cable
CONDUIT Nonmagnetic
WIRE Al, 600 V
22,227AMPS
21,377 AMPS
Voltage (L -L) 240 V
F�2 available fault
current calculator
Created Using Eaton's Bussmann Series - Available Fault Current Calculator 1.5 Page 1