HomeMy WebLinkAboutAVAIL FAULT CURRENT - 16-00478-482 - Campus Courtyard 2E:7*N BUSSMANN SERIES Your System Details Project Name: w,Campus courtyard l System Type: Single -Phase Creator Name: TIM Clarkson Creator Email: clarksin2004@cableone.net Creator Company/Organization: Castle electric Creator Title/Position: Owner Creation Date: Jul 18, 2016 @ 2:21pm LVA TRANSFORMER KVA 100 Voltage _d„a. 240 %Z 1.50 %Z TOL -10% (Max Fault) bowl.,.. mu 30,867 AMPS. Im„is.,. n_ro 46,301 AMPS Voltage (L -L) 240 V LENGTH 60FT SIZE 250 QTY 3 (per phase) TYPE Three -Conductor Cable CONDUIT Nonmagnetic WIRE Al, 600 V 22,227AMPS 21,377 AMPS Voltage (L -L) 240 V F�2 available fault current calculator Created Using Eaton's Bussmann Series - Available Fault Current Calculator 1.5 Page 1