FS PLANS REVISIONS 5-15-17 - 16-00482 - Campus Courtyard 2 Bld 8
State of Idaho _ DEPARTMENT OF INSURANCE C.L. "BUTCH" OTTER 700 West State Street, 3rd Floor- -- Governor P.O. Box 83720 Boise, Idaho 83720-0043 Phone (208) 334.4370 KNUTE C. SANDAHL Fax (208) 334-4375 State Fire Marshal PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS nnnrcr�r. .. r, .� .Z: ,. A •-ra- SY STREET ADDRESS: rr UW. CITY R - R R. FIRE PROTECTION CONTRACTOR: pffoeAiix .r i Rt ii o r - cJr C,N ADDRESS: - p A /CZPUez, I Rd AQ CITY: STATE: ;S' D: ZIP: 8-3-6&7 PHONE NO: 2cg. lCG - Q115 FAXNO: Z c>8 -%46t— ci%(T SIGNATURE ON PLAN: J e 9 S C c!*_ f3 c V A R O DATE ON PLAN: M A y Z.o i -T DATE PLAN RECEIVED: S 17 DATE APPROVED: ITEM NO. CODE REFERENCE DEFICIENCY NOTED -r"i% a.J GT wAS APPmc�VeD a^t If -z$-17 -"o 14x5 r3EFP`+ RLLSuI3Mt "t7 PLACE Tm .. crjCtip+MC,C-`S Gt= Q.Ut4©W C°Itlwt t, li� 5`(sre: M I5,c.k EVI q2 u LN 1145 C/�Lcut .e. ait t.4,%'re,9.ijkL- LI SAC A,rrhC 6Q F�?R T1+Ca Fih'/•� PIba+V L. OBP Tvlauisun = Y Y FF w� AYE "d Det. 6 -IS -17 NOTE: NOTE: SYSTEMS EXCEEDING 20 SPRINKLERS IN SIZE SHALL BE CONSTANTLY SUPERVISED AT A CENTRAL LOCATION - I.F.C. 903.4 IT IS ACKNOWLEDGED THAT AN UNAPPROVED BACRFLOW PREVENTER IS INSTALLED PER THE DEMAND OF THE LOCAL WATER PURVEYER. DUE TO THE HIGH PRUPORTED FAILURE RATE, STATE FIRE MARSHAL'S OFFICE, AND ITS PERSONNEL, DOES NOT APPROVE OF OR TAKE ANY RESPONSIBILITY FOR THE BACKFLOW DEVICE. REVIEWED BY: Mel Fletcher P.O. Box 8 Fairfield, Idaho 83327 PLANS REVIEWER: Mel Fletcher Ph: 208-764-2337 Fax: 208-764-2090 CC TO: Knute Sandahl Idaho Survey &Ratin Y 8 File File A.H.J. R C X 3 u R (-1 t^ t RC D C V r' APPROVED -Ibjectt acies inspection. corrected and subject to a field inspection. F1 DISAPPROVED- Resubmit with items noted corrected. 0 ADDITIONAL -Information requested I/2015 HOT TAP EXI5TINe LATER LINE. CITY / (BY OTHER5) DV M SRC W NEUJ HYDRANT N S E FIRE PROTLCTIO.v PLA_b'.5' FOR CAMPUS r_.110URTYARD BLDC. X7,5 .5. 5TH Xg. RCYIJL%Pl; ID 8�3-140 N UJ C141iFU6 OLEO 1E TO 5E FULLY 51RINKLERED A5 FEF, NFPA 13R, 201(o, AND ALL 5TATE AND LOCAL CODE5 AND ORD INANCE5 A�IROX, 11,168 TOTAL 50 FT d 107 8 sa x • . ` • u... _ n v , 4 • _ ..... _. •_ _ 1. +`.�. _.. r. 77 .fs F s d R� ✓ a � VICINITY MAP • PROJECT LOCATION UNDERGROUND INSULATED C1445E U5ED TO FIFE 2" FIRE 1 IAIN E3ETLUEEN 5UILDING5. R15ER FOR 5LDG. #1 GL4910 LOCATED IN 4.9 5LDG, MEGALW RETAINING FLANGE #a R15ER SUPPLY SIDE PSI GAUGE ROOM. 6 R15ER R00M 1/2" WITH 2" BUTTERFLY VALVES ELECTRICALLY SUPERVISED OPEN 15 1 Q HR RATED UJ/ EXTERIOR DOORt NO f.I.v. REQUIRED. 2" Clear Space 5LDG. r STYLE 5 A1=1=ROX. 261 L.P. (o" OF UJATER 1141N (15Y OTHER5) SITE PLAN SCf..F - Al`. I - ALL UNDERGROUND FIRE MAIN PIPING TO BE INSTALLED IN ACCORDANCE WITH NFPA 1113, 24. PHOENIX P.O.G. TO BE AT FF ABOVE FINISH FLOOR. 2 - SCOPE OF WORK TO COMMENCE AS INDICATED ON SITE PLAN. 3 - UNDERGROUND PIPING SHALL BE C-900 WITH CLASS 50 DUCTILE IRON THROUGH FLOOR SLAB 4 - CHANGES IN DIRECTION OF PIPING TO BE MADE BY THE USE OF MECHANICAL JOINT FITTINGS 5 - THRUST RESTRAINTS TO BE PROVIDED AT ALL TURNS AND ENDS OF MAINS PER NFPA X13 6 - FLUSHING AND TESTING OF UNDERGROUND PIPING TO BE PERFORMED AS PER NFPA 013 1 - NUTS, BOLTS, RODS, WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES ON ALL UNDERGROUND PIPING ARE TO BE COATED WITH BITUMINOUS OR OTHER APPROVED CORROSION RETARDING MATERIAL 6- AS PER NFPA 13 10.4 THE DEPTH OF COVER FOR BURIED PIPE, AS DETERMINED BY THE STATE FIRE MARSHAL, SHALL NOT BE LESS THEN 5411, TO THE TOP OF THE PIPE, BELOW THE FINISHED GRADE. 9 - ALL BURIED U.G. PIPING TO MEET THE REQUIREMENTS OF NFPA 13 10.4.1 THRU 10.4.6, AND LOCAL AUTHORITIES. 10 - TRACER WIRE TO BE USED ON ALL UNDERGROUND PIPE. MEGALUG Retaining Flange__. Finished Floor Slab MEGALUG g \/ • .� — .✓ A STATIC: aO RESIDUAL: I& FLOWING 1310 epm DATE: 3=30=2011 LOCATION: ON SITE TESTED Y: FHOENIX T=IRE min ^:"''' 11 i 6" C-900 PLL-1--l' Concrete Thrust Block Protect Fitting W/ Visqueen RISER STUB -11V DETAIL NTS :i • . FF co 5Y5FE> l R15ER 5EE 5TU5 IN DETAIL I` I I I I 120V ELEC ALARM BELL 51NC LE AKI T SDC 101 1 111 1 1 1 A� ROX. 30 L.�. O1a r" 0900 T=IRE M/41N (15Y OTHERS) I LDG. #15 5TYLE A PHOENIX POINT OF coNNEcrioN TO aE 'I Al THE FIRST FLANGE INSIDE THE BUILDING. NOT TAP AND NRS GATE VALVE TO BE INSTALLED 51' OTHERS. 1 THRUST BLOCK SIZED IN ACCORDANCE V NFPA 13 ®� 2 ti I FINISH ESCUTCHEON I QTY. b" DUCTILE IRON THROWN FLOOR GL4910 3 SLEEVE AT FLOOR SLAB W12" CLEAR SPACE AROUND PIPE 4.9 4 MEGALW RETAINING FLANGE WHITE RECESSED 5 SUPPLY SIDE PSI GAUGE RA3533 6 2" DERRINGER DOUBLE CHECK BACKFLOW PREVENIER 5.8 1/2" WITH 2" BUTTERFLY VALVES ELECTRICALLY SUPERVISED OPEN RECESSED Q 2" EJTTERFLY VALVE SUPERVISED OPEN AND 2" RISER v RELIABLE DRY HSW MANIFOLD TO BLDG.'S ® <g> 2" BUTTERFLY VALVE SUPERVISED OPEN AND 2" RISER MANIFOLD TO BLDG, e1 2" Clear Space B T CPVC TO STEEL ADAPTOR R5734 RELIABLE F3QR56 4 WAY EQUAKE BRACE AT TOP OF EACH RISER r 1" SPRIWLER HEAD CABINET W1 MIN b SPARE HEADS CHROME N A 6 © NOT USED o ~ a ALL ELECTRICAL WIRING BY OTHERS a SIGNS AS REQUIRED OL4910 MAX HEAD SPACING 20' RA3533 HSW SPACING 20' RA1664 DRY HSW SPACING X 20' X 20' 28' X ® ® 0 O MAIN DRAINS TO BE TIED TOGETHER AND DRAINED min ^:"''' 11 i 6" C-900 PLL-1--l' Concrete Thrust Block Protect Fitting W/ Visqueen RISER STUB -11V DETAIL NTS :i • . FF co 5Y5FE> l R15ER 5EE 5TU5 IN DETAIL I` I I I I 120V ELEC ALARM BELL 51NC LE AKI T SDC 101 1 111 1 1 1 A� ROX. 30 L.�. O1a r" 0900 T=IRE M/41N (15Y OTHERS) I LDG. #15 5TYLE A PHOENIX POINT OF coNNEcrioN TO aE 'I Al THE FIRST FLANGE INSIDE THE BUILDING. NOT TAP AND NRS GATE VALVE TO BE INSTALLED 51' OTHERS. ')" TO RISER MANIFOLD W/: (1) DRAIN AND TEST O (2) FLOW SWITCH t 2 a (3) PRESSURE GAUGE 0 (4) PRESSURE RELIEF o VALVE > o z RISER MANIFOLD DETAIL CAMPUS COURTYARD BLDG. 48 SPRINKLER SCHEDULE & LEGEND I ISYMBOLI 1 THRUST BLOCK SIZED IN ACCORDANCE V NFPA 13 ®� 2 b" C -W0 FROM CITY WATER SUPPLY I FINISH ESCUTCHEON I QTY. b" DUCTILE IRON THROWN FLOOR GL4910 3 SLEEVE AT FLOOR SLAB W12" CLEAR SPACE AROUND PIPE 4.9 4 MEGALW RETAINING FLANGE WHITE RECESSED 5 SUPPLY SIDE PSI GAUGE RA3533 6 2" DERRINGER DOUBLE CHECK BACKFLOW PREVENIER 5.8 1/2" WITH 2" BUTTERFLY VALVES ELECTRICALLY SUPERVISED OPEN RECESSED Q 2" EJTTERFLY VALVE SUPERVISED OPEN AND 2" RISER v RELIABLE DRY HSW MANIFOLD TO BLDG.'S ® <g> 2" BUTTERFLY VALVE SUPERVISED OPEN AND 2" RISER MANIFOLD TO BLDG, e1 ® B T CPVC TO STEEL ADAPTOR R5734 RELIABLE F3QR56 4 WAY EQUAKE BRACE AT TOP OF EACH RISER r 1" SPRIWLER HEAD CABINET W1 MIN b SPARE HEADS CHROME N A 6 © NOT USED o ~ a ALL ELECTRICAL WIRING BY OTHERS a SIGNS AS REQUIRED OL4910 MAX HEAD SPACING 20' RA3533 HSW SPACING 20' RA1664 DRY HSW SPACING X 20' X 20' 28' X ® ® 0 O MAIN DRAINS TO BE TIED TOGETHER AND DRAINED TOTAL COUNT THIS BUILDING = TO SAFE LOCATION OUTSIDE. LOCATION TO BE ® ® FIELD VERIFIED ® NOTE: U.G. TO BE FLUSHED AND HYDROSTATICALLY TESTED AS PER NFPA 13 AND LOCAL CODES PRIOR TO CONNECTION TO SPRINKLER SYSTEM O RISER DETAIL PROVISIONS FOR FORWARD FLOW OF SFF THRU 1" OUTLET 114° _ VA„ CONNECTION CAPABLE OF FLOWING 117 GPM @ PITOT OF P5116 ')" TO RISER MANIFOLD W/: (1) DRAIN AND TEST O (2) FLOW SWITCH t 2 a (3) PRESSURE GAUGE 0 (4) PRESSURE RELIEF o VALVE > o z RISER MANIFOLD DETAIL CAMPUS COURTYARD BLDG. 48 SPRINKLER SCHEDULE & LEGEND I ISYMBOLI SIN I SPRINKLER DESCRIPTION RESP. I K—FAC NPT. TEMP. I FINISH ESCUTCHEON I QTY. 0 GL4910 GLOBE RES. PEND OR 4.9 2" 155 WHITE RECESSED 44 14 RA3533 RELIABLE HSW 20 x 20 OR 5.8 1/2" 155WHITE RECESSED 21 4 RA1664 RELIABLE DRY HSW 28 x 8 OR 5.6 155 CHROME N A 24 +4 R5734 RELIABLE F3QR56 DRY HSW QR 5.6 1" 155 CHROME N A 6 OL4910 MAX HEAD SPACING 20' RA3533 HSW SPACING 20' RA1664 DRY HSW SPACING X 20' X 20' 28' X MAX MIN SPACING 8'-0" MAX 4" — 6" DOWN 8' MAX 4" — 6" DOWN HEAD CABINET WITH MIN. 6 SPARE HEADS & WRENCH ES PROVIDED TOTAL COUNT THIS BUILDING = 95 GENERAL NOTES: AFIRE PROTECTION SYSTEM TO BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE APPLICABLE BUILDING CODES, STATE AND LOCAL FIRE MARSHALS REQUIREMENTS, NFPA 13R, 2016 EDITION. (�) ALL ELECTRICAL WIRING OF FIRE PROTECTION SYSTEM AND COMPONENTS TO BE PERFORMED BY OTHER TRADE DIVISIONS. ®ALL PAINTING OF FIRE PROTECTION PIPING AND RELATED COMPONENTS TO BE PERFORMED BY OTHER TRADE DIVISIONS. O ALL INSULATING OF FIRE PROTECTION PIPING AND RELATED COMPONENTS TO BE PERFORMED BY OTHER TRADE DIVISIONS. Is5 SPRINKLER PIPING TO BE HUNG AS PER NFPA 13R. PIPING LAID ON OPEN JOISTS OR RAFTERS SHALL BE SUPPORTED IN A MANNER THAT PREVENTS LATERAL MOVEMENT. Oi NOT USED. Os ALL WELDING TO BE DONE BY A CERTIFIED WELDER IN A FABRICATION SHOP PER NFPA STANDARDS. @SPRINKLER PIPING SHALL BE SUPPORTED IN A MANNER THAT PREVENTS MOVEMENT OF PIPING UPON SPRINKLER OPERATION 10 ALL SPRINKLER FITTINGS SHALL MEET OR EXCEED THE REQUIREMENTS OF NFPA 13 TABLE 6.4.1. 11 ALL SPRINKLER PIPING SHALL CONFORM TO NFPA 13 TABLE 6.3.1.1 STANDARDS AND LOCAL REQUIREMENTS. l2 SPARE SPRINKLER CABINET AND WRENCH TO BE FURNISHED PER NFPA 13. l3 ROOM OCCUPANCY AND CEILING HEIGHT SHOWN AS: ROOM N41E la DOMESTIC MATERIAL NOT REQUIRED. l5 ELEVATION OF PIPE SHOWN AS [0-01 IS FROM ABOVE FINISHED FLOOR FLOOR AND ELEVATIONS SHOWN AS [0-0 bts] ARE FROM BOTTOM OF TOP OF STRUCTURE DOWN. is PIPING: CPVC PIPING CONFORMING TO NFPA 13, ASTM F442 17 SPRINKLERS ARE NOT REQUIRED IN ATTICS PENTHOUSE EQUIPMENT DOM, ELEVATOR MACHINE ROOM AND SHAFTS CRAWL SPACES AND OTHER CONCEALED SPACE NOT USED OR INTENDED FOR LIVING PURPOSES PER NFPA 13R 6.6.6 le ON SYSTEMS WHERE THE PRESSURE AT THE SPRINKLER EXCEEDS 100 P.S.I., BRANCH LINES SUPPORTING SPRINKLERS IN A PENDENT POSITION BELOW A CEILING SHALL BE SUPPORTED BY A HANGER THAT PREVENTS UPWARD MOVEMENT OF THE PIPE. AND THE UNSUPPORTED LENGTH OF PIPE BETWEEN THE HANGER AND END SPRINKLER IN A PENDENT POSITION SHALL NOT BE GREATER THAN 12" NFPA 13 9.2.3.4.3.1 & 2, AND BRANCH LINES SUPPORTING PENDENT SPRINKLERS BELOW CEILING SHALL NOT HAVE UNSUPPORTED ARM OVERS THAT EXCEED 12". AS PER NFPA 13 9.2.3.5.2.1. l3 PER NFPA 13D 8.2.5.7 SHADOW AREAS SHALL BE PERMITTED AS LONG AS THE DRY AREA DOES NOT EXCEED 15 SQ FT. PEI PHOENIX FIRE PR 0 TE C TION 4130 AIRPORT ROAD NAMPA IDAHO 83687 (208) 468-9115 (208) 461-9117 fax 1D. LIC. F.P.S.C, #108 1APUBLIC FORKS LIC. 116630-A-4(13930) UTAH LIC, # 6579958-5501 S370 OREGON LIC. # 181692 WYOMING ID # 2008-000553828 WASHINGTON LIC. # PHOENFP911KL JOB INFORMIATION CAMPUS COURTYARD BLDG. 18 215 S. 5TH W. REXBURG, ID 83440 DRAWN BY : JESSICA 50VARD CHECKED BY : TRENT BICE NICET * 101524 DATE : MAY 2011 CODES : NFPA 13R, 201(o - IBC 2012 OCCUPANCY CLASS: RESIDENTIAL CONSTRUCTION TYPE : TYPE V B SQUARE FOOTAGE : 11,168 NUMBER OF FLOORS : 3 SITE PLAN SCALE : AS NOTED ON PLANS NOTICE IT IS THE OWNER'S RESPONSIBILITY TO PROVIDE HEAT ADEQUATE TO PREVENT FREEZING THROUGH— OUT THE WET PIPE SPRINKLER SYSTEM AREAS AND ALSO IN ENCLOSURES FOR DRY PIP, DELUGE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO THE SPRINKLER SYSTEMS. CONTRACT WITH: SOMMER MASONRY IN CONSTRUCTION 4113 N 4154 E RIG15Y, ID 83442 PHONE NUMBER: 208-145-8232 NATIONAL INSTITUTE FOR CERTIFICATION ` IN ENGINEERING TECHNOLOGIES The racmde of this argmiaUm shin that TRENT BICE Automatic Sprinlder System Isymt 00301 / LEVEL III is emuueA mum teenmml area(e) Twbniden CerU9rstma No. 101524 ceruticauo0s) valid nra 04/01/2018 NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES The raor& dude myasiseum shoe that JAVIER CERVANTES Ad—tic SpdUMW System lgmt LEVEL II Is amtltlod in the techNsel mea(s) Teanddsn CmHNaum No. 140350 cmuNauan(s) valla Thra 06/01/2018 NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES The ra & of this m{aniaation &I that BROOK STEWART Ad—tic SpI System West LEVEL I u a11W m the technical mals) Teohddan CeruNation No. 141221 cmusc&I valid Thra 10/01/2018 io ST ATE FIRE iAARSHAL'S O s ICE RINK' IPI FLAN REVIEW R8COMIMENDATION SUB4790 C.,1 WITHATTA0QQCG+ENTV ARK -0S L: C/BPI //// Li COMMENT5MAR1(•UPSATTACHED ATURE AGENCY NAME [] REJECTED .�� ,_ DATE_E�1 7 FF1 SHEET I OF Z INSULATION -TENT OVER PIPE WITH VISQEEN TO AVOID FILLING IN BETWEEN PIPE AND CEILING. COLD AREA STRUCTU SPRINKLER PIPING TO STAT VISQUEEN AS CLOSE TO TRUSS HEATED AREA BOTTOM CHORDS AS POSSIBLE TENT IN6ULATION DETAIL SCALE: NTS I CPVC DOUBLE FASTENER STRAP TYPE HANGER NOT TO SCALE HARDENED HEX HEAD SELF THREADING SCREW IS FURNISHED WITH THE HANGER AND 15 THE MINIMUM FASTENER SIZE ACCEPTABLE o 101 I CPVC OFFSET NO BLOCK TYPE HANGER NOT TO SCALE LISTED RESTRAINT FOR 3/411 TO 2" CPVC FOR VERTICAL OR HORIZONTAL INSTALLATION I CPVC DOUBLE FASTENER STRAP TYPE HANGER NOT TO SCALE HARDENED HEX HEAD SELF THREADING SCREW IS FURNISHED WITH THE HANGER AND IS THE MINIMUM FASTENER SIZE ACCEPTABLE ss HANGER TICKS SYMBOLS ARE SHOWN AS A GRAPHIC REPRESENTATION ONLY. ACTUAL LOCATIONS MAY VARY PER FIELD CONDITIONS. ALL HANGERS IN ACCORDANCE WITH NFPA 13 9.2.2, TABLE 92.2.1 AS PER NFPA 13R, MINIMUM DISTANCE FOR SPRINKLERS ARE AS FOLLOWS: R RMA A 11,16L3 ft 2 FRONT OF FIREPLACE -------------------- 6011 • KITCHEN RANGE, WALL OVEN ------------ IS" HOT AIR FLUES, UNI INSULATED GPM AT 53.9 w AT FF HEAT DUCTS GLOBE RES. PEND • UNINSULATED HOT WATER PIPES --------- 1211 • SIDE OF CEILING OR WALL---------------- 2411 MOUNTED HOT AIR DIFFUSERS WATER SUPPLY INFORMATION: ll Paswa: 80 Pei, Fill PRE l 11109 lam 1310 aPM RDMxD FRONT OF WALL MOUNTED ---------------- 3611 HOT AIR DIFFUSERS IVA. • HOT WATER HEATER OR FURNACE --------- 611 • LIGHT FIXTURE OW-25OLU------------------ 611 LIGHT FIXTURE 25OW-413SW--------------- 12" CENTER OF CELING FAN CENTER OF HEAD----- 3611 CAMPUS COURTYARD BLDC, So 6—Fff fro 1,0 8344® RELIABLE RA3533 20X20 SIDEWALL THROUGHOUT 3RD FL UP FROM BELOW (TYPICAL) (TYPICAL) /\ I \ I FIRE SPRINKLER MAIN RUNS UNDERGROUND IN AN INSULATED CHASE TO BLDG. "1 SEE FPI FOR CONTINUATION OF HYDRAULIC CALCULATIONS. J i RELIABLE 85134 DSW TO COVER EXTERIOR STAIRWELLS (TYPICAL) FIRE SPRINKLER SYSTEM RISER SEE DETAIL SHEET FPI ---� - - FROM BELO� r LijN N (TYPICAL) R — -= — RELIABLE RAI664 N 28X8 D5W TO COVER BLDG #f EXTERIOR WALKWAY w e APPROX] (TYPICAL) 1^1/� z� 5 5-81s "Fall GLOBE GL4310 20X20 SSP THROUGHOUT IST 4 2ND FLS ('S) IM (S7 SPRINKLERS ARE NOT REQUIRED IN BATHROOMS NOT EXCEEDING 55 S.F. • SPRINKLERS ARE NOT REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES WHERE THE SPACE DOES NOT EXCEED 24 S.F. AND THE LEAST DIMENSION IS it, OR = 3'. • SPRINKLERS ARE NOT REQUIRED IN OPEN ATTACHED PORCHES, CARPORTS, AND OTHER SIMILAR STRUCTURES. • SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS, CRALUL SPACES, AND OTHER CONCEALED SPACES THAT ARE NOT INTENDED FOR LIVING PURPOSES OR STORAGE. • SPRINKLERS ARE NOT REQUIRED IN ENTRANCE FOYERS THAT ARE NOT THE ONLY MEANS OF EGRESS. • SHADOW AREAS SHALL NOT EXCEED 15 SQ FT UNIT A_ 014. TELY 3,402 SQ FT 4-4 a 0 015 4-91: a TION PLAN R LIN ITf�OJ•I.t2 INITI 1 /LI I�TF C� l D -P/ I UP TO 3RD FLOOR d u (TYPICAL) L*J N BLDG. #8 2ND FLOOR FIRE PROTECTI w e APPROXIMATELY 3,402 SQ FT 1/8" = 1' - 0" 9 8 16 14 1210 8 16 24 L*U 3 ll' -- W1T cs ox s3a1 / WC B-0 ) L 9 o -n, uca-Nr 8'-81/2' o -u uc 2-84 4-611 3-5 8-411 3-10 4-4 3-5 4-91: 3-41s 8-51s UNIT C WIT ON. Wj �8 LINIT 13W ZN F l F l w..*NBLS e APPRG s FLOOR FIRE PRO 4,364 SQ FT 1/8" = V - 0" CAMPUS COURTYARD BLDG. #8 SPRINKLER SCHEDULE & LEGEND TYP. SECTION NTS SYSTEM DESIGN DATA" SYSTEM " I R=EMOTE AREA 1 tt 2$W9p RE5D R RMA A 11,16L3 ft 2 DESGx CEMStt .05 DPM/so PT 2 A.S. o 404 sow xEAD A... 100 GPM AREA OF APPLICAnON 214 40 PT RroEWatt"p1""e' 1601 ill 64.1 MAT FF AREA v APPuanox 436 GD T �a� � 193.5 GPM AT 53.9 w AT FF GL4910 GLOBE RES. PEND WATER SUPPLY INFORMATION: W.. PAev.c 80 PS, RESWAL PREeaURE 16 Ps wn1 1310 GPM rtorAxc 1`AETr. An ON SITE By. PHOENIX FIRE DAX 3-30-11 APPROVALS REQUIRED: STATE FIRE DEPT., OLLNER 1 WHITE I WATER SUPPLY INFORMATION: ll Paswa: 80 Pei, Fill PRE l 11109 lam 1310 aPM RDMxD 1$Aktx An ON SITE BY: PHOENIX FIRE THIS IS A SAFETY OF 113.8 p5i or 24% of SUPPLY RA3533 IVA. x 20 OR 5.8 1/2" 1 155 1 WHITE THIS IS A SAFETY OF 20 si or 250 of SUPPLY ------ 4 RA1664 RELIABLE DRY HSW 28 x 8 QR 5.6 155 1 CHROME N/A 24 4 R5734 RELIABLE F3QR56 DRY HSW QR 5.6 155 CHROME N/A r r 1:Y107 ,r �. .r �r GL4910 MAX HEAD SPACING 20' RA3533 HSW SPACING 20' RA1664 DRY HSW SPACING .:YI •l •�� MAX MIN SPACING 8'-0" MAX 4" - 6" DOWN 8' MAX 4" - 6" DOWN HEAD CABINET WITH MIN. 6 SPARE HEADS & WRENCH ES PROVIDED TOTAL COUNT THIS BUILDING 5 EVA - A X. I W cry w I . �!► cr A M �- i FIRE SPRINKLER SYSTEM RISER SEE DETAIL SHEET FPI ---� - - FROM BELO� r LijN N (TYPICAL) R — -= — RELIABLE RAI664 N 28X8 D5W TO COVER BLDG #f EXTERIOR WALKWAY w e APPROX] (TYPICAL) 1^1/� z� 5 5-81s "Fall GLOBE GL4310 20X20 SSP THROUGHOUT IST 4 2ND FLS ('S) IM (S7 SPRINKLERS ARE NOT REQUIRED IN BATHROOMS NOT EXCEEDING 55 S.F. • SPRINKLERS ARE NOT REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES WHERE THE SPACE DOES NOT EXCEED 24 S.F. AND THE LEAST DIMENSION IS it, OR = 3'. • SPRINKLERS ARE NOT REQUIRED IN OPEN ATTACHED PORCHES, CARPORTS, AND OTHER SIMILAR STRUCTURES. • SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS, CRALUL SPACES, AND OTHER CONCEALED SPACES THAT ARE NOT INTENDED FOR LIVING PURPOSES OR STORAGE. • SPRINKLERS ARE NOT REQUIRED IN ENTRANCE FOYERS THAT ARE NOT THE ONLY MEANS OF EGRESS. • SHADOW AREAS SHALL NOT EXCEED 15 SQ FT UNIT A_ 014. TELY 3,402 SQ FT 4-4 a 0 015 4-91: a TION PLAN R LIN ITf�OJ•I.t2 INITI 1 /LI I�TF C� l D -P/ I UP TO 3RD FLOOR d u (TYPICAL) L*J N BLDG. #8 2ND FLOOR FIRE PROTECTI w e APPROXIMATELY 3,402 SQ FT 1/8" = 1' - 0" 9 8 16 14 1210 8 16 24 L*U 3 ll' -- W1T cs ox s3a1 / WC B-0 ) L 9 o -n, uca-Nr 8'-81/2' o -u uc 2-84 4-611 3-5 8-411 3-10 4-4 3-5 4-91: 3-41s 8-51s UNIT C WIT ON. Wj �8 LINIT 13W ZN F l F l w..*NBLS e APPRG s FLOOR FIRE PRO 4,364 SQ FT 1/8" = V - 0" CAMPUS COURTYARD BLDG. #8 SPRINKLER SCHEDULE & LEGEND TYP. SECTION NTS SYSTEM DESIGN DATA" SYSTEM " I R=EMOTE AREA 1 tt 2$W9p RE5D R RMA A 11,16L3 ft 2 DESGx CEMStt .05 DPM/so PT 2 A.S. o 404 sow xEAD A... 100 GPM AREA OF APPLICAnON 214 40 PT RroEWatt"p1""e' 1601 ill 64.1 MAT FF AREA v APPuanox 436 GD T �a� � 193.5 GPM AT 53.9 w AT FF GL4910 GLOBE RES. PEND WATER SUPPLY INFORMATION: W.. PAev.c 80 PS, RESWAL PREeaURE 16 Ps wn1 1310 GPM rtorAxc 1`AETr. An ON SITE By. PHOENIX FIRE DAX 3-30-11 APPROVALS REQUIRED: STATE FIRE DEPT., OLLNER 1 WHITE I WATER SUPPLY INFORMATION: ll Paswa: 80 Pei, Fill PRE l 11109 lam 1310 aPM RDMxD 1$Aktx An ON SITE BY: PHOENIX FIRE THIS IS A SAFETY OF 113.8 p5i or 24% of SUPPLY SYSTEM DESIGN DATA SYSTEM " I REMOTE AREA " O xD;CA o.. RES m".,."A 11168 ft s G9a CEMStt .05 cPwnG PT 4 A.S. ®224 sD sT xEAox.aa 100 GPM AREA v APPuanox 436 GD T �a� � 193.5 GPM AT 53.9 w AT FF GL4910 GLOBE RES. PEND OR 4.9 1/2" 1 155 1 WHITE I WATER SUPPLY INFORMATION: ll Paswa: 80 Pei, Fill PRE l 11109 lam 1310 aPM RDMxD 1$Aktx An ON SITE BY: PHOENIX FIRE DAs 3-30-I1 RA3533 APPROVALS REQUIRED: STATE FIRE DEPT., OWNER x 20 OR 5.8 1/2" 1 155 1 WHITE THIS IS A SAFETY OF 20 si or 250 of SUPPLY 21 SYSTEM DESIGN DATA REMOTE AREA " 0 �� CA RES . mx" 11168 ft2 Dl ul .05 GPM,SG R 2 A.S. @ 320 ll 100 GPM AREA Di APPLICATgI 214 GGTO fl KEfr3 140.1 GPM AT 38.3 n AT FF WATER SUPPLY INFORMATION: MIC.l W PS, RE9GlIM Mill 16 PS "w 1310 CPM nowxo }KTEn AT: ON SITE en PHOENIX FIRE DAM 3.30-17 APPROVALS REQUIRED: STATE FIRE DEPT., OWNER THIS IS A SAFETY OF 41.1 Pei or 52% of SUPPLY SYMBOL I SIN I SPRINKLER DESCRIPTION I RESP. K—FAC NPI. I TEMP. FINISH IESCUTCHEON OTY. • GL4910 GLOBE RES. PEND OR 4.9 1/2" 1 155 1 WHITE I RECESSED 44 04 RA3533 RELIABLE HSW 20 x 20 OR 5.8 1/2" 1 155 1 WHITE RECESSED F 21 4 RA1664 RELIABLE DRY HSW 28 x 8 QR 5.6 155 1 CHROME N/A 24 4 R5734 RELIABLE F3QR56 DRY HSW QR 5.6 155 CHROME N/A 6 GL4910 MAX HEAD SPACING 20' RA3533 HSW SPACING 20' RA1664 DRY HSW SPACING X 20' X 20' 28' X MAX MIN SPACING 8'-0" MAX 4" - 6" DOWN 8' MAX 4" - 6" DOWN HEAD CABINET WITH MIN. 6 SPARE HEADS & WRENCH ES PROVIDED TOTAL COUNT THIS BUILDING 5 GENERAL NOTES: AFIRE PROTECTION SYSTEM TO BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE APPLICABLE BUILDING CODES, STATE AND LOCAL FIRE MARSHALS REQUIREMENTS, NFPA 13R, 2016 EDITION. ® ALL ELECTRICAL WIRING OF FIRE PROTECTION SYSTEM AND COMPONENTS TO BE PERFORMED BY OTHER TRADE DIVISIONS. ALL PAINTING OF FIRE PROTECTION PIPING AND RELATED COMPONENTS TO BE PERFORMED BY OTHER TRADE DIVISIONS. 0 ALL INSULATING OF FIRE PROTECTION PIPING AND RELATED COMPONENTS TO BE PERFORMED BY OTHER TRADE DIVISIONS, I5 SPRINKLER PIPING TO BE HUNG AS PER NFPA 13R. 6 PIPING LAID ON OPEN JOISTS OR RAFTERS SHALL BE SUPPORTED IN A MANNER THAT PREVENTS LATERAL MOVEMENT. NOT USED. a ALL WELDING TO BE DONE BY A CERTIFIED WELDER IN A FABRICATION SHOP PER NFPA STANDARDS. ( SPRINKLER PIPING SHALL BE SUPPORTED IN A MANNER THAT PREVENTS MOVEMENT OF PIPING UPON SPRINKLER OPERATION 10 ALL SPRINKLER FITTINGS SHALL MEET OR EXCEED THE REQUIREMENTS OF NFPA 13 TABLE 6.4.1. GALL SPRINKLER PIPING SHALL CONFORM TO NFPA 13 TABLE 6.3.1.1 STANDARDS AND LOCAL REQUIREMENTS. 12 SPARE SPRINKLER CABINET AND WRENCH TO BE FURNISHED PER NFPA 13. 13 ROOM OCCUPANCY AND CEILING HEIGHT SHOWN AS: ROOM ®NAME 14 DOMESTIC MATERIAL NOT REQUIRED. 0-0 15 ELEVATION OF PIPE SHOWN AS [0-0] IS FROM ABOVE FINISHED FLOOR FLOOR AND ELEVATIONS SHOWN AS [0-0 bts] ARE FROM BOTTOM OF TOP OF STRUCTURE DOWN. 16 PIPING: CPVC PIPING CONFORMING TO NFPA 13, ASTM F442 1D17 SPRINKLERS ARE NOT REQUIRED IN ATTICS PENTHOUSE EQUIPMENT OOM, ELEVATOR MACHINE ROOM AND SHAFTS CRAWL SPACES AND OTHER CONCEALED SPACE NOT USED OR INTENDED FOR LIVING PURPOSES PER NFPA 13R 6.6.6 1a ON SYSTEMS WHERE THE PRESSURE AT THE SPRINKLER EXCEEDS 100 P.S.I., BRANCH LINES SUPPORTING SPRINKLERS IN A PENDENT POSITION BELOW A CEILING SHALL BE SUPPORTED BY A HANGER THAT PREVENTS UPWARD MOVEMENT OF THE PIPE. AND THE UNSUPPORTED LENGTH OF PIPE BETWEEN THE HANGER AND END SPRINKLER IN A PENDENT POSITION SHALL NOT BE GREATER THAN 12x NFPA 13 9.2.3.4.3.1 & 2, AND BRANCH LINES SUPPORTING PENDENT SPRINKLERS BELOW CEILING SHALL NOT HAVE UNSUPPORTED ARM OVERS THAT EXCEED 12'. AS PER NFPA 13 9.2.3.5.2.1. 1e PER NFPA 13D 8.2.5.7 SHADOW AREAS SHALL BE PERMITTED AS LONG AS THE DRY AREA DOES NOT EXCEED 15 SQ FT. I �YL••�Yi F�f Froh�isoa J { PHOENIX FIRE PROTECTION 4130 AIRPORT ROAD NAMPA IDAHO 83687 (208) 468-9115 (208) 461-9117 fax ID. LIC. F.P.S.C. #108 IRPUBLIC NORIS LIC. 116630-A-4(13930) UTAH LIC. # 6579958-5501 5370 OREGON LIC. # 181692 WYOMING ID # 2008-000553828 WASHINGTON LIC. # PHOENFP911KL JOB INFORMATION CAMPUS COURTYARD BLDG. "8 215 5, 5TH W. REXBURG, ID 83440 DRAWN BY : JESSICA BOVARD CHECKED BY : TRENT BICE NICET M 101524 DATE : MAY 2011 CODES: NFPA 13R, 2016 - IBC 2012 OCCUPANCY CLASS : RESIDENTIAL CONSTRUCTION TYPE : TYPE V B SQUARE FOOTAGE : 11,168 NUMBER OF FLOORS : 3 SIRE PROTECTION PLAN SCALE : AS NOTED ON PLANS NOTICEIT IS THE OWNER'S RESPONSIBILITY TO PROVIDE HEAT ADEQUATE TO PREVENT FREEZING THROUGH- OUT THE WET PIPE SPRINKLER SYSTEM AREAS AND ALSO IN ENCLOSURES FOR DRY PIP, DELUGE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO THE SPRINKLER SYSTEMS. CONTRACT WITH: SOMMER MASONRY IN CONSTRUCTION 4113 N 4154 E RIGBY, ID 83442 PHONE NUMBER: 206-145-8232 NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES Tha fill of two DTpdanon show that TRENT BICE Antl Spdohla S*= IM -t 00301 / LEVEL III 6 maw in we techDial axle) Tbchill cwoftuon No. 101524 cauePa l.) v.ua rm 04/01/2018 NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES N leawds d wb apdaUm show that JAVIER CERVANTES Anto=ano By.tem laywt LEVEL II V catl8aa In we taohoioel aaa(s) TaahDtdeD Ceruffal ND. 140350 catincstlon(.) vaua Thm 06/01/2018 NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES The noad. of 1Ws mpDWtion show that BROOK STEWART Antamdlo spmHa aTl Ierwt b Dmtl d m the LtaMatdal itl Taehddan ceftestlm Na. 141221 catlmdhall vena ThTD 10/01/2018 APPROVAL STAMP IDAHO STATE FIRE MARSHAL'S OFFICE SPRINKLER PLAN REVIEW RECOMMENDATION (]ACCEPTANCEA6$UBMITTEC 0WITH Mill CCAIp1EMVIlpt41PS 00 111 (aCDMMENTEWM-UPSATTACHED SIGNATURE ` DAI FORUSE BY LOCAL R AGI t JURISDI� C� TION yU APP - ❑ REJECTED SIGNATURE/ _ DATE FIRE AGENCY NAME FF2 SHEET � OF Z