Loading...
HomeMy WebLinkAboutALL DOCS - 16-00610 - Life Safety 445, 447 Steglemeier, 1066 N Yellowstone HwyPermit Inspection Summary Permit Status of (Open) as of Report Date: 06/21/2017 4:39 pm Permit Details Permit Number: 16-00610 Life Safety 445, 447 Steglemeier, 1066 N Yellowstone Hwy 445 Stegelmeier Lane Consultation case Permit Issued Date: Permit Inspection Statistics Total Inspections Completed: Total Inspections Passed: Inspection Pass Rate Permit Inspection History *Refer to Individual Inspection Report for more Details Building Inspection Type 09/08/2016PARTCOMPLYQuinton OwensBuilding Inspector Consultation Duplex apartments at 1066 N. Yellowstone, 445 Stegelmeier, & 457 Stegelmeier. All apartments require a class 2A-10B-C fire extinguisher. GFCI protected outlets are required in bathrooms and at kitchen countertop areas (some are installed but all will be tested for approval) 457 (basement): needs a handrail at exterior stairs (return ends to post or wall) 445 (basement): Laundry room requires protected separation from upstairs unit(drywall ceiling), or from basement unit (drywall all walls and install metal or solid wood door to laundry room). Clearance between exhaust vent and outlet above stairs will be reviewed. Is there a light switch at bottom of stairs for stair lighting? 445 (upstairs): Guardrail (36" high) required at front stairs where step is more than 30" above adjacent grade. Smoke detector missing in upper unit bedroom. 1066 (West apt.): Egress window is too small for code requirements, but as an existing window it will be checked for approval with the Life Safety ordinance. Inspector Comments: