Building Inspection Type
09/08/2016PARTCOMPLYQuinton OwensBuilding Inspector Consultation
Duplex apartments at 1066 N. Yellowstone, 445 Stegelmeier, & 457 Stegelmeier.
All apartments require a class 2A-10B-C fire extinguisher.
GFCI protected outlets are required in bathrooms and at kitchen countertop areas
(some are installed but all will be tested for approval)
457 (basement): needs a handrail at exterior stairs (return ends to post or wall)
445 (basement): Laundry room requires protected separation from upstairs
unit(drywall ceiling), or from basement unit (drywall all walls and install metal or
solid wood door to laundry room).
Clearance between exhaust vent and outlet above stairs will be reviewed.
Is there a light switch at bottom of stairs for stair lighting?
445 (upstairs): Guardrail (36" high) required at front stairs where step is more
than 30" above adjacent grade.
Smoke detector missing in upper unit bedroom.
1066 (West apt.): Egress window is too small for code requirements, but as an
existing window it will be checked for approval with the Life Safety ordinance.