HomeMy WebLinkAboutSTRUCTURE CALC - 16-00551 - 1070 Washington Blvd - New SFRYork Structural Design (801) 876-3501 pyyoIsT wa e 9737 Structural Calculations Jamestown Founders Square BI L2 Rexburg, ID 83440 Prepared For: KARTCH N ER H O M E S Kartchner Homes 601 W. 1700 S. Bldg B Logan Utah 84321 435.755.9530 July 25, 2016 Structural Calculations July 25, 2016 For: Kartchner Homes Plan #: Jamestown Location: Founders Square B l L2 From: York Engineering Inc. 4883 Old Highway Road, Suite A Morgan, Utah 84050 (801) 876-3501 Design Criteria 2015 IRC: Roof Load; Roof Live Load (PSF) 40 Dead Load (PSF) 15 Floor Load; Live Load (PSF) 40 Dead Load (PSF) 10 Seismic Zone: D Wind Speed: '115 mph ult. Exposure C or 150 mph ult. Exposure B Material Properties & Assumptions Concrete (fc'): 3000 psi(found.) to 4000 psi (cusp. slab) Concrete Reinforcement: ASTM A615 Grade 60 & Grade 40 Site Conditions: Dry & Stable granular based, 1500 PSF Bearing Capacity, Granular Based Backfill (KH=35 pcf),Slope not to exceed 20%, Setback from slopes is minimum of 25' Dimensional Lumber: Doug Fir 42 & BTR Steel: ASTM A36 Use Simpson straps and tie downs, and meet nailing, reinforcement and other structural requirements as noted on the drawing and within the pages of this document. These structural calculations are based on conditions and assumptions listed above. If the conditions listed herein are not met or are different it shall be brought to the attention of the engineer. Roof Truss and beam system to be engineered by the supplier. This engineering assumes that the building site is dry and stable, a high water table or adverse soils such as plastic clays, fills etc. could cause future flooding, settlement, site instability, or other adverse conditions. Verification of and liability for the soil bearing pressure, site stability, and all other site conditions, including site engineering as required, is the responsibility of others. These calculations and engineering are for the new building structure only and do not provide any engineering analysis of or liability/warranty for the non-structural portions of the building, or the site itself. York Engineering Inc. does not assume the role of "Registered Design Professional in Responsible Charge" on this project. The purpose of these calculations and engineering is to help reduce structural damage and loss of life due to seismic activity and/or high wind conditions. The contractor shall verify all conditions, dimensions and structural details of the drawing. All exterior walls shall be sheathed with 7/16" APA rated structural wood panel. Block all horizontal edges 1 %z" nominal or wider. Sheathing shall extend continuous from floor to top plate and be nailed at least 4" O.C. along sill plate. Nails shall be placed not less than %z" from edge of panel and driven flush but shall not fracture the surface of the sheathing. Extend sheathing over gable end to wall joints & over rim joist between floors and nail to rim and wall plates 6" O.C. The following general requirements shall be followed during construction: 1. Contractor to verify all dimensions, spans, & conditions and notify engineer of any errors, omissions, or discrepancies prior to construction. 2. Use Simpson A35 ties each cantilevered joist to sill or top plate. 3. Use Simpson Hl, H2.5 or equiv. ties each end of each truss. 4. Use 1/2" x 10" J bolts 32" O.C. all foundation walls up to 8'. Use 5/8" bolts with all walls over 8' high. Use 3" x 3" x 1/4" washers 5. If discrepancies are found, the more stringent specification shall be followed. 6. All multiple beams and headers to be nailed using 16d two rows 12" O.G. 7. Contractor shall assure that all materials are used per manufactures recommendations. 8. Site engineering and liability shall be provided by the owner/builder as required. 9. Connect beams & headers over 6 ft., to trimmers with appropriate connectors/hangers. 10. Contractor shall assure that footings are properly drained and that soil is dry and that footings rest on undisturbed native soil and that building horizontal clearance from footings to adjacent slopes be a minimum of 25 feet and that the intent of IRC section R403.1.7.2 is met. If set back requirements of R403.1.7.2 cannot be met then contact engineer for further design requirements. 10. The contractor shall conform to all building codes and practices as per the 2015 IRC. 11. Use balloon framing method when connecting floors in split level designs. 12. Nail all shear walls to floorjoist using 2: 16d 16" O.C. Add additional floor joist as reqd. 13. Provide joist and rafter hangers as per manufacturers' specifications. 14. Foundation steps shall not exceed 4 feet or 1/2 the horizontal distance between steps. Horz. re -bar shall be 12" O.C. through step downs and extend 48" either side of step 15.If garage return walls are less than 32" wide then extend headers across return walls with 2 king studs on either end extending from the top of the header to the bottom plate or install (2) MST 36 straps each end of header extend across wing walls. 16. Use a minimum of 2-9 ''/z" LVLs for all headers carrying girder loads. 17. Use 1 1/8" wide timberstrand or equiv. for all rim joist 18. Provide solid blocking through structure down to footing for all load paths. 19. Builder shall follow all recommendations found in all applicable Geotechnical reports. 20. Stacking of two sill plates is permitted with 5/8" J -bolts through both plates. Stacking more than two plates is not permitted without special engineering 21. Minimum strength requires 2,500 PSI concrete; however, as per IRC 402.2 3,000 PSI concrete shall be used. Plan: Jamestown Date: 19 August 2014 Location: FS2B1 Footing Calculations back front left right interior Concrete Specs Density (pcf) 150 150 150 150 150 Strength (psi) 2500 2500 2500 2500 2500 Clear Cover Thickness (in) 3 3 3 3 3 Foundation Height Above Grade (ft) 0.67 0.67 0.67 0.67 0.08 Height Above Grade (in) 8 $ 8 8 1 Wall Thickness (ft) 0.67 0.67 0.67 0.67 0.67 Thickness (in) 8 8 8 8 8 Weight (kips/Ift) 0.07 0.07 0.07 0.07 0.01 Footing Specs Width (ft) 1.67 1.67 1.67 1.67 1.33 Width (in) 20 20 20 20 16 Height (ft) 0.83 0.83 0.83 0.83 0.83 Height (in) 10 10 10 10 10 Weight (kips/Ift) 0.21 0.21' 0.21 0.21 0.17 Area per Ift 1.67 1.67 1.67 1.67 1.33 Soil Specs Density (pcf) 125 125 125 125 125 Soil Pressure (psf) 1500 1500 1500 1500 1500 Weight (kips/Ift) 0.04 0.04 0.04 0.04 0.00 Building Loads Roofspan 35 35 10 10 0 Roof (kips/Ift) 0.96 0.96 0.28 0.28 0.00 Wall Height (ft) 12 12 12 12 12 Wall Load (kips/Ift) 0.24 0.24 0.24 0.24 0.18 Floor span 19 16 2 2 35 Floor Loads (kips/Ift) 0.46 0.40 0.05 0.05 0.88 Total (kips.lft) 1.67 1.60 0.57 0.57 1.06 Calculations Total Weight on Soil (kips) 1.94 1.88 0.84 0.84 1.23 Soil Load (ksf) 1.16 1.13 0.50 0.50 0.92 Required Footing Width (in) Zu ZD Zb zu 16 ' II Required Footing Depth (in) 10 10 10 10 10 Plan: Jamestown Date: 19 August 2014 Location: FS281 Seismic Calculations Loading Summary Floor Dead Load (psf) 10 Floor Live Load(psf) 40 Walls (Ext)(pso 20 Roof LL(pso 40 Walls (Int)(psf) 10 Roof DL(psf) 15 Roof Dead Load(pso 15 Roof Slope 7112 Exterior combination Snow Load Reduction Seismic Parameters Slope 30.26 V=Cs*W/1.4 Snow 40.00. Fa= 1 Table 11.4-1 Pitch over 20 R= 6.5 table 1617.6 Rs Ss= 1.772 Reduction SMS= 1.77 eq. 16-16 L.L.-Reduction 40.00 Sds= 1.18 eq 16-18 Total Load 55.00 Cs= 0.218 per eq. 16-49 Adj. Factor 1.4 Cs= 0.1556 Roof Length W(psl) Lb/ft Width W(lb) 61 23 1403 42 58926 roof wall 9270 Total Mass Tributary to Roof Levels = 68196 Shear M(lbs) Roof Levels = 10613 Floor Length Mal) Ib/ft Width W(lb) 61 10 610 42 0 wall height 0 9270 Total Mass Tributary to Floor 2= 0 Shear M(lbs) Floor Levels = 0 Floor( Length W(psf) Ib/ft Width W(lb). 61 10 610 42 17240 wall height 9 11330 Total Mass Tributary to Floor 1= 28570 Shear M(lbs) Floor Levels = 4446 Floor 1 Lateral Force u Floor 2'. Lateral Force U ROOF Lateral Force 1U613 Total Seismic Mass = 96/66 Total Lateral Force = 1OU13 SeISmiC Force Distribution *** Roof Sections **` H(x) W(x) kip W(x)H(x) % Force Total Sheer F Roof 15.0 68 1020 100.00% 10.612964 FIOCr1 1.0 U U U.UU% 1U.b12Y64 hloor2 0.0 0 U O.UU% 10.612964 Totals 68 1020 1 V/SUm(WPNI) U.U1U4U Total Shear (lbs) 1U613 tsasement bneer Wall F(Iotal) Length Total Load (kips) 10.6 Shear Wall Load (ply right Side b.3 10 Not Applicable lett side b.3 10 Not Applicable front b.3 10 Not Applicable back b.3 10 Not Applicable Floor 1 sneer wau F(total) Length Total Load (kips) 10.6 Shear Wall Load (plf) right side b.3 33 161 lett sloe b.3 2a 190 tront b.320 26b Deck 0.6 30 It/ Floor z sneer wail F(total) Length Total Load (kips) 10.6 Shear Wall Load (plo right Side 5.3 10 Not Applicable lett side 5.3 10 Not Applicable iron( 5.3 10 Not Applicable back b.3 10 Not Applicable wall height 9 ft Front Bed 3/ Bed 2 Force Transfer N 36 Ib/ft a 0 r 2 ft 1631b/ft 361b/ft 488 lbs <Seismic 488 Its m 840 psi F.S. t Bolts 1/2 in 159 Ib/ft c 5 ft 1591b/ft c 0 Capacity 281.25 bs/ft 0 F.S. 3.89 3.49 width 6 ft 455.9 lbs N 100.0% right 0 Shear Wall selection SW -1 361b/ft 0 2 ft 2631b/ft 36 Ib/ft 0 350.0 lbs/ft Seismic F.S. a 800 lbs <Wnd wall length 796 lbs <Seismic Vital! M 651 lbs 840 psi F.S. 14.51 Bolts 1/2 in Location Spacing 32 in 4.51 Capacity 281.25 bs/ft connection F.S. 3.89 3.49 Tension 455.9 lbs stud 2.50 ft wall length 11.0 ft 2.5 ft Vital! M 651 lbs 840 psi F.S. 14.51 Tie Down 651.3 lbs stud 2X6 stress 57.9 psi Ft 525 psi F't 840 psi F.S. 14.51 Tie Down STHD10 Location Corner F.S. 4.51 Window CS16 connection Nails F.S. 3.49 Aspect ratio left 100.0% right 100.0% Shear Wall selection SW -1 350 lbs/ft 4" edge nailing & 12"field nailing w/ reduction 350.0 lbs/ft Seismic F.S. 2.15 wall height 9 f Front Entry/Flex Room Force Transfer 18 lb/ftn 115 0 2 ft 255 lb/ft 145 lb/ft 765 lbs 765 lbs Bolts m Spacing 32 in L 281.25 lbs/ft F.S. 2371b/ft 5 ft 713.8 1b. 237 Wit stud m stress 90.6 Psi 0 0 525 psi Ft 840 psi widtr 6 ft Tie Down a Location Corner 18 lb/ft o 2 ft 255 Wit 145 lb/ft CS16 j 0 connection Nails F.S. a Aspect ratio wall length 11.5 ft 2 ft 1020 Ib 1300 16s s 3.50 ft 1020 lbs 1303 ms wall length 11.5 ft 2 ft 1020 Ib 1300 16s s < Wind 1303 ms < Seismic Bolts 112 in Spacing 32 in Capacity 281.25 lbs/ft F.S. 2.48 Tension 713.8 1b. stud 2X6 stress 90.6 Psi Ft 525 psi Ft 840 psi F.S. 8.27 Tie Down STHD10 I' Location Corner F.S. 2.88 Window CS16 j connection Nails F.S. 2.23 Aspect ratio left 100.0% right 80.0% '. Shear Wall selection SW -1 350 lbs/ft 4" edge nailing & 12"field nailing w/ reduction 324.5 Ibs/ft�I Seismic F.S. 1.37 wall height 9k A Perforated Shear Wall 1500 Its Wind Bolts 1/2 in 1454 Its Seismic Spacing 32 in Capacity 281.25 lbs/ft F.S. 3.09 Tension 572.5 lbs stud 2X6 stress 72.7 psi Ft 525 psi. F't 840 psi. F.S. 11.55 Tie Down STHD14 Location Corner F.S. 2.33 Aspect ratio left 88.89% right 88.89% 4 n wall length 16.0ft 4 ft Perforated Shear wall reduction opening height 3 % sheathing 50.00% 1636 lbs 1636 lbs C, 1.00 Shear Wall selection PLR 240 lbs/ft 6" edge nailing & 12"field nailing w/ reduction 213.3 lbs/ft Seismic F.S. 1.17 Wind F.S. 1.79 Wall Height,h Maximum i h/3 0.33 Plan: Jamestown Date: 18 August 2014 Location: FS281 Wind Loading Calculations using Main Wlndforc r -Resisting System (MWFRS) Longitudinal Direction Wind Design Coof iclents P=Wind load'exp wa Iw P=Design Pressure Horizontal Wind Load From Figure 28.6-1 Wall Load (pan= end no (A) 23.6 Interior zone (C) 18.8 Roof Load (pan= end zone (B) 16.1 interior zone (D) 12.9 Vertical Wind Load from figure 28.6-1 Roof Load (pan= end zone windward (E) 1.8 end zone leeward (F) -8.7 interior zone windward(G) 0.6 interior zone leeward (H) -12.3 Exposure Coefficient from figure 28.6-1 1.21 Apply Load combination factor (ASCE 7-10 2.4.1 0.6 Wind speed= 115 Roof Height 9.92 Exposure C Meanroof HefO Truss Span 34 Wind Load u 0.6 Roof Slope^ '7112 Rom Angle (deg)= 30.26 Sind 0.8039 Minimum Pressure P=wind load'exp coeff Iw Adjusted horizontal wail interior 13.65 13.65 horizontal wail end zone 17.13 17.13 horizontal roof interior 9.37 10.00 horizontal mof end zone 11.69 11.69 vertical end zone windward 1.31 1.31 vertical end zone leeward -6.32 0.00 vertical interior zone windward 0.44 0.44 vertical intedorzone leeward -8.93 0.00 .4-Hmean 5.9833333 .1 -base 4.2 End Zone Width (g). 4.2 2nd storyEndZone Width (ft) 4.2 Interior Zone W4dih(ft) 33.6 2nd Storyinterior Zone NALth(ft) 33.6 Gable Roof Load Width Height Wind Load force (be) End 4.2 2.3 17.13 '167 Interior 33.6 3:80 13.65 2805 Sum= 2971.5 Area Wind Load Force (]be) Hip Row Load End 416.5 11.69 4868 Interior 50.96 10.00 510 Total 5378 Well Load Width Height Wind Load Force pbIHI End 4.2 9.0 17.13 144 Interior 33.6 1.00 13.65 459 Sum= 602.522 Vertical Force Width length Wind Load Farce fibs) end zone windward 4 28.40 TRUE 60 leeward 4 28.40 FALSE 0 interiorzonewim[wardl 34 28.40 TRUE 477 leeward 34. 28.40 FALSE. 0 Floor Diaphragm Shear Shear Wall Loads (pill Total Shear (lad 5378 Front Wall Length 10 Not Applicable Beck Wall Length 10 Not Applicable Floor 1 Diaphragm shear Shear Wall Loads (pit) Total Shear(Ibs) 10801 Front Wall Length 20 270 Back Wall Length 30 180 basement Diaphragm shear Shear Wall Loads (pin Total Shear (lbs) 11403 Front Wall Length 10 Not Applicable Back Wall Length 10 Not Applicable Critical Wall Length (@)= Front Wall Dead Load (pin= 0 Total 16487 Front Wall Critical Length(ft)= -30 Total (pin 80 Beck Wall Dead Load (pin= 0 Back Wall Cribcal Length (ft)= -20 2nd Stor Force Her 143.92 458.6 602.52 Plan: Jamestown Dale: 19 August 2014 Location: F82B1 Wind Loading Calculations using Main W ndforce-Resisting System (M WFRS) Transverse Direction Wind Design Coefficients P=wind load -exp wef -le/ P=Design Pressure Horizontal Wind Load From Figure 28.6-1 Wall Load (psf)= end zone (A) 23.6 interior zone (C) 18.8 Roof Load lost)= end zone (B) 16.1 interior zone (D) 12.9 Vertical Wind Load from figure 28.6-1 Roof Load (psg= end zone windward (E) 1.8 end zone leeward F) -8.7 interior zone windward (G) 0.6 interior zone leeward (H) 42.3 Exposure Coefficient from figure 28.6-1 1.21 Apply Load combination factor (ASCE 7-10 2.4.1 0.6 Wind speed= 115 Roof Height 9.916667 Exposure C Wall Height 10 Truss Span 34 Roof slope= 7112 Roof Angle(dego 30.26 Sine 0,5039 Minimum Pressure P=wind load"exp weWlw Adjusted horizontal wall interior 13.65 13.65 horizontal wall end zone 17.13 17.13 horizontal roof interior 9.37 10.00 horizontal mot end zone 11.69 11.69 vertical end zone windward 1.31 1.31 vertical end zone leeward 6.32 0.00 vertical Interior zonewridward 0.44 0.44 verdeal Interior zone leeward -8.93 0.00 End Zane Worn (ft) 4.2 2nd sloryEnp Zone Width (ft) Inlaor Zone Width (ft) 52.6 2nd Storylntedor Zone Width (ft) Gable Roof Lead Width Haight Wind Load Force (lbs) End 4.2 2.3 17.13 167 Interior 52.6 3.80 13.65 4391 Sum= 4557.581 Area Hip Roof Load End 604.9167 11.69 7071 Interior 79.77667 10.00 798 Total 7868 Wall Load Width Height Mind Load Force flus) End 4.2 1.0 17.13 144 Interior 52.6 1.00 13.65 718 Bum= 861.8491 Vertical Force Width length Wind Lead Force(Ibs) and zone windward 4 55.40 TRUE 116 leeward, 4 55.40 FALSE 0 interior zone windward 53 55.40 TRUE 1457 leeward 53 55.40 FALSE 0 Flood Diaphragm Shear Shear Wall Loads (elf) Total Shear(Ibs) 7868 Left Well Length 10 Not Applicable Right Wall Length 10 Not Applicable Floor f Diaphragm shear Shear Wall Loads (pit) Total Shear (lbs) 15625 Left Well Length 28 279 Right Wall Length 33 237 basement Diaphragm Shear Shear Wall Loads (pig Total Shear (lbs) 16487 Left Wall Length 10 Not Applicable Right Wall Length 10 Not Applicable Critical Wall Length (ft)= Left Wall Deed Load (plp= 0 Total 11403 Left Wall Critical Length (ft)= -55 Total (pig 46 Right Wall Dead Load (plf)= 0 Right Wail Critical Length (ft)= -47 4.2 52.6 2nd Story 143.92224 717.92688 861.84912 Plan: Jamestown Date: 19 August 2014 Location: FS281 RBA RB -2 RB -3 RB -4 RS -6 RB -8 RB -9 RB -10 RB -11 FB -1 FB -2 FB -3 Grade LVL Sawn LVL Sawn LVL Sawn Sawn Sawn Sawn Sawn LVL LVL Load Parameters Elev B Floor Live Load(pso 40 40 40. 40 40 40 40 40 40 40 40 40 Floor Total Load(psf) 50 50 50 50 50 50 50 50 50 50 50 50 Floor Span(ft) 0 0 0 0 0 0 0 0 0 34 21 10 Total Floor Load(plo 0 0 0 0 0 0 0 0 0. 850 525 250 Wall Height (11) 6 0 0 0 0 0 0 0 0 0 0 0 Wall Weight (pso 20 20 20 20 20 20 20 20 20 20 20 20 Wall Load(plf) 120 0 0 0 0 0 0 0 0 0 0 0 Roof LL (pso 40 40 40 40 40 40 40 40 40 40 40 40 Total Roof Load(pso 55 55 55 55 55 55 55 55 55 55 55 55 Roof Span(ft) 4 10 40 40 30 8. 36 24 10 0 0 0 Total Roof Load(fill) 110 275 1100 1100 825 220 990 660 275 0 0 0 Beam Weight(plo 12.1 5.6 9.6 5.6 9.6 5.6 5.6 5.6 5.6 4.4 9.6 6.0 Live Load(plo 80 200 .800 800 600 160 720. 480 200 680 420 200 Total Load(plo 242 281 1110 1106 835 226 996 666 281 854 535 256 Reactions & Moment Duration Increase 1 1 1 1 1 1 1 1 1 1 1 1 Beam Span(ft) 16 6 6 4 8 4 4 4 4 3 9.5 4 Reaction 1(Ib) 1936 842 3329 2211 3339 451 1991 1331 561 1282 2540 512 Reaction 2(Ib) 1936 842 3329 2211 3339 451 1991 1331 561 1282 2540 512 Max Moment FtLb 7746 1262 4993 2211 6677 451 1991 1331 561 961 6031 512 Max Shear Lb 1936 842 3329 2211 3339 451 1991 1331 561 1282 2540 512 Determine Beam Size Depth Estimate (in) 11.88 9.25 9.50 9.25 9.50 9.25 9.25 9.25 9.25 7.25 9.50 11.88 Width Estimate (in) 3.50 3.00 3.50 3.00 3.50 3.00 3.00 3.00 3.00 3.00 3.50 1.75 Cv= 1.00 1.00 1.00 1.00 1.00. 1.00 1.00 1.00 1.00 1.00 1.00 1.00 Cf = 1.00 1.10 1.00. 1.10 1.00 .1.10 1.10. 1.10 1.10 1.20 1.00 1.00 Area = 41.58 27.75 33.25. 27.75 33.25 27.75 27.75 27.75 27.75 21.75 33.25 20.79 Momemt of Inertia 1 = 489 198 250 198 250 198 198 198 198 95 250 245 Maximum Bend Stress= 1129 354 1138 620 1522 127 558 373 157 439 1375 149 Allowable bend Stress 2604 935 2684 935 2684 935 935 935 935 1020 2684 2604 Allowable Moment 17862 3333 11775 3333 11775 3333 3333 3333 3333 2234 11775 8931 Factor Of Safety = 2.31 2.64 2.36 1.51. 1.76 7.39 1.67 2.50 5.94 2.32 1.95 17.44 Allowable Sheer Stress 285 165 285 165 285 165 165 185 165 180 285 285 Max Shear Cap(Ibs)= 7900 3053 6318 3053 6318 3053 3053 3053 3053 2610 6318 3950 Factor Of Safety = 4.08 3.63 1.90 1.38 1.89 6.77 1.53 2.29 5.44 2.04 2.49 7.71 Bearing Required = 0.74 0.69 1.27 1.82 1.27 0.37 1.64 1.10 0.46 1.05 0.97 0.39 E (psi) 2000000 1300000 2000000 1300000 2000000 1300000 1300000 1300000 1300000 1300000 2000000 2000000 Deflection LL (in) 0.12 0.02 0.05 0.02 0.11 0.00 0.02 0.01 0.00 0.01 0.15 0.00 LLoad Def. Limit U 360 360 360 360 360 360 360 360 360 360 360 360 Allowable Deflection (in) 0.53 0.20 0.20 0.13 0.27 0.13 0.13 0.13 0.13 0.10 0.32 0.13 LL Deflection FIS 4.42 8.82 4.29 7.44 2.41 37.21 8.27 12.40 29.77 9.99 2.06 56.60 Deflection TL (in) 0.36 0.03 0.06 0.02 0.15 0.01 0.02 0.01 0.01 0.01 0.20 0.00 TLoad Def. Limit 240 240 240 240 240 240 240 240 240 240 240 240 Allowable Deflection (in) 0.8 0.3 0.3 0.2 0.4 0.2 0.2 0.2 0.2 0.15 0.475 0.2 TL Deflection FIS 2.19 9.43 4.64 6.08 2.60 39.60 8.97 13.42 31.84 11.93 2.42 66.32 LVL Sawn LVL Sawn LVL Sawn Sawn Sawn Sawn Sawn LVL LVL Selection 2:117/8• 2 2x1 2:9 i• 2:2x10 2:9s° 2:2x10 2:2x10 2:2x10 2:2x10 2:2x& 2: SW 11171&^ Plan: Jamestown Date: 19 August 2014 14" Location: FS2131 4490 TJIJoist 210 Span (ft) 18.5 Depth 14 Load Parameters 2.00 Floor Dead Load 10 Floor Live Load 40 Total Floor Load 50 Simple Span Joist 0.41 Duration Increase 1 Joist Span(ft) 18.5 Joist Spacing 19.2 Joist Weight (plf) 3.1 Joist Loading (plf) 83 Max Reaction (lbs) 769 Max Moment (FtLb/If) 3555 Max Shear Lb 769 Determine Joist Size Depth 14" Max Moment 100% (ft -lbs) _ 4490 F. S. for moment = 1.26. Max Shear 100% (lbs) = 1945 F. S. for shear = 2.53 Bearing Required (in.)= 2.00 Live Load (1-/360) = 0.62 Total Load (L/240) = 0.93 EI x 10^6 (Ib-in42) 462 Live Load Deflection (in) 0.41 Total Load Deflection (in) 0.53 Live Load F of 1.52 Total Load F of S 1.75 Selection 14" 210's @ 19.2" o.c Depth = Plan: Jamestown Max Moment 100% (ft-Ibs) = Date: 19 August 2014 F. S. for moment = Location: FS2131 BCI JOISTS 6000 Span (ft) 18.5 Depth 14 Load Parameters 0.93 Floor Dead Load 10 Floor Live Load 40 Total Floor Load 50 Simple Span Joist 0.53 Duration Increase 1 Joist Span(ft) 18.5 Joist Spacing 19.2 Joist Weight (plf) 2.7 Joist Loading (plf) 83 Max Reaction (Ibs) 765 Max Moment (FtLb/If) 3538 Max Shear Lb 765 Determine Joist Size Depth = 14" Max Moment 100% (ft-Ibs) = 4350 F. S. for moment = 1.23 Max Shear 100% (Ibs) = 1175 F. S. for shear = 1.54 Live Load (U360) = 0.62 Total Load (L/240) = 0.93 EI x 10"6 (Ib-in^2) 445 K x 10^6 (Ibs) 8 Live Load Deflection (in) 0.41 Total Load Deflection (in) 0.53 Live Load F of S 1.50 Total Load F of S 1.74 Selection 14" 6000 @ 19.2" I Plan: Jamestown Date: 19 August 2014 Location: FS2131 Micro -Lam Beam RB -5 RB -7 Uniform Loads Uniform Floor Span (ft) 0 0 Total Uniform Floor Load (pif) 0 0 Wall Height (ft) 0 0 Wall Weight (psf) 20 20 Wall Load (plf) 0 0 Uniform Roof Span (ft) 0 0 Total Uniform Roof Load golf) 0 0 Point Loads 1 Distance from Left (ft) 2 2 1 Point Live Load (lb) 0 0 1 Point Dead Load (lb) 0 0 2 Distance from Left (ft) 4 2 2 Point Live Load (lb) 2720 2720 2 Point Dead Load (lb) 1020 1020 Partialy Uniform Loads 1 Uniform Span (ft) 0 0 1 Live Load (plf) 0 0 1 Dead Load (pif) 0 0 1 Distance of left side (ft) 1 1 1 Distance of right side (ft) 6 6 2 Uniform Span (ft) 35 35 2 Live Load (plf) 700 700 2 Dead Load (plf) 262.5 262.5 2 Distance of left side (ft) 4 0 2 Distance of right side (ft) 6 2 Tapered Load Tapered load left (plf) 213 275 Tapered load right (pll) 275 110 Left Distance (ft) 0 2 Right Distance (ft) 4 9 Beam Weight (pig 9.64 12.06 Reactions & Moment Duration Increase 1 1 Beam Span(ft) 6 9 Left Reaction (lb) 2233.3 5273.2 Right Reaction (lb) 4465.5 1847.9 Max Moment FtLb 6981.7 8554.2 Max Mom dist from Left 4.0 2.0 Max Shear Lb 4465.5 5273.2 Max Shear Stress (psi) 134.3 126.8 Determine Size Depth Estimate (in) 9.50 11.88 Wdih Estimate (in) 3.5 3.5 Cross Area (in"2) 33.25 41.58 Max Moment 100%= 11406.60 17837.82 Momemt of Inertia I = 250.07 489.03 Factor Of Safety = 1.63 2.09 Max Shear 100%= 201.45 190.23 Factor Of Safety = 1.41 1.50 Bearing Required= 2.32 2.74 Load S 32.22 39.48 Beam S 52.65 82.33 S Factor of Safety 1.63 2.09 E (psi) 1900000 1900000 Deflection LL (in) 0.06 0.09 L/360 0.20 0.30 LL Deflection F of S 3.25 3.32 Deflection TL (in) 0.08 0.12 1/240 0.30 0.45 TL Deflection F of S 3.71 3.89 Selection 2:91/2" 2:117/8" LVL LVL