HomeMy WebLinkAboutRESCHECK - 16-00551 - 1070 Washington Blvd - New SFR1ZREScheck Software Version 4.6.2
Compliance Certificate
Project FS2B1 - Jamestown
Energy Code:
2012 IECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Orientation:
Bldg. faces 90 deg. from North
Conditioned Floor Area:
3,530 ft2
Glazing Area
20%
Climate Zone:
6 (8693 HDD)
Permit Date:
Permit Number:
0
Construction Site:
Owner/Agent:
Rexburg, ID 83440
0.057
Designer/Contractor:
Kartchner Homes
84321
435-755-7080
John@kartchnerhomes.com
Compliance: Passes using LIA trade-off
Compliance: 1.4% Better Than Code Maximum UA: 292 Your UA: 288
The % Better or Worse Than Cade Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Ceiling 1: Flat Ceiling or Scissor Truss
Main Wall Front: Wood Frame, 16" o.c.
Orientation: front
Window 4: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Front
Door 1: Solid
Orientation: Front
Main Wall Right: Wood Frame, 16" o.c.
Orientation: Right side
Main Wall Rear:. Wood Frame, 16" o.c.
Orientation: Back
Window 5: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Back
Main Wall Left: Wood Frame, 16" o.c.
Orientation: Left side
Basement Wall Front: Solid Concrete or Masonry
Orientation: Front
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 6: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Front
1,765
50.0
0.0
0.026
46
608
21.0
0.0
0.057
27
90
0.320
29
40
0.010
0
175
21.0
0.0
0.057
10
488
21.0
0.0
0.057
21
125
0.320
40
278
21.0
0.0
0.057
16
608
0.0
13.0
0.047
28
20 0.320 6
Project Title: FS2B1 - Jamestown Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2Bl.rck Page 1 of 9
Basement Wall Right: Solid Concrete or Masonry 174 0.0 13.0 0.047 8
Orientation: Right side
Wall height: 8.0'
Depth below grade: 8.0'.
Insulation depth: 8.0'
Basement Wall Rear: Solid Concrete or Masonry 488 0.0 13.0 0.047 20
Orientation: Back
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 7: Vinyl/Fiberglass Frame:Triple Pane 60 0.320 19
Orientation: Back
Basement Wall Left: Solid Concrete or Masonry 278 0.0 13.0 0,047 12
Orientation: Left side
Wall height: 8,0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 8: Vinyl/Fiberglass Frame:Double Pane with Low -E 20 0.320 6
Orientation: Left side
Compliance Statement., The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in
REScheck Version 4.6.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name -Title Signature Date
Project Notes:
Founder Square Subd
Block: 1, Lot: 2
Rexburg, ID 83440
Project Title: FS2B1 - Jamestown Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2Bl.rck Page 2 of 9
fZREScheck Software Version 4.6.2
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
Pre-Inspection/Plan Review
Plans Verified' Fleld`Verified
'.. Value Ualue Complies? Comments/Assumptions
103.1,
;Construction drawings and
❑Complies
103.2
;documentation demonstrate,.,
° '",. "�, u,<<^,_ $ :- ❑Does Not
,
[PR1]1
:energy code compliance for the
a ra ❑Not Observable j
4building
envelope.
�„ i' X
t.'[]Not Applicable
103.1.
103 2,
;Construction drawings and
;documentation demonstrate
1[ - ` °�r� ❑Complies
v� ° ' ❑Does Not
403.7
[PR3]1
: energy code compliance for
:li htin and mechanicals stems
:lighting Y
va
+" dna " < '° , ❑Not Observable
„s
'Systems servingmultiple
�❑Not Applicable
„
;dwelling units must demonstrate
(compliance with the IECC
;Commercial Provisions.
3Q2.1,
;Heating and cooling equipment is;
Heating: ; Heating;❑Complies
403.6
;'sized per ACCA Manual S based
1 Btu/hrBtu/hr ❑Does Not
[PR2]2
'.; on loads calculated per ACCA
Cooling: I Cooling:❑Not Observable
U
Manual J or other methods
approved by the code official.
Btu/hr j Btu/hr❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12;: Medium Impact (Tier 2) 1, 3'1 Low Impact (Tier 3)
Project Title: FS2B1 - Jamestown Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2Bl.rck Page 3 of 9
Section
#
`Foundation Inspection
Plans Verified Field Verified
Complies? Comments/Assumptions
& Req.ID
-::
value Value
402.1.1
!Conditioned basement wall
R-
R- _
;❑Complies ;see the Envelope Assemblies
[F0411
;insulation R -value. Where interior;
R
R -❑Does
Not table for values.
119)
insulation is used, verification
j❑Not Observable
i may need to occur during
i Insulation Inspection. Not
;❑Not Applicable
;required in warm -humid locations;
in Climate Zone 3.
303.2
(Conditioned basement wall
❑Complies
[F0511
insulation installed per
, ref"`'' '�
J❑Does Not
manufacturer's instruction❑Not
a
Observable
,',
❑Not Applicable
402.2.8
Conditioned basement wall
ft ft
;❑Complies ;See the Envelope assemblies
[F0611
'insulation depth of burial or
;❑Does Not ;table for values.
lgJ❑Not
distance from top of wall.
Observable
❑Not Applicable
303.2.1
JA protective covering is installed
`.
3 " �� s° ,„ al#
❑Complies
[F011]2
�to protect exposed exterior
, ], } �'[ ``r"�.
[]Does Not
'
1 insulation and extends a
'
❑Not Observable
minimum of 6 in. below grade
+rf�' }i
[]Not Applicable
403.8
f Snow- and ice -melting system
�` z
❑Complies
[F012]2
controls installed..
] [' a�,�{,r
❑Does Not
❑Not Observable
❑Not Applicable j
1 _*
Additional Comments/Assumptions:
11 High Impact (Tier 1) 271 Medium Impact (Tier 2) 1 3 Low Impact (Tier 3)
Project Title: FS2B1 - Jamestown Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS261.rck Page 4 of 9
Section
#
Framing1.Rough-In Inspection
Plans Verified Field Verified
Value.` Value
Complies? `. Comments/Assumpt[ons
& Req.113
-
402.1.1,
;Door U -factor.
; U-_ ; U-
I❑Complies ; See the Envelope Assemblies
402.3.4
!❑Does Not ; table for values.
[FR1]1
;❑Not Observable
❑Not Applicable
402.1.1,
;Glazing U-factor(area-weighted
U-_ U-
;❑Complies ; See the Envelope Assemblies
402.3.1,
average).
;❑Does Not table for values.
402.3.3,
402.3.6,
;❑Not Observable
402.5
;❑Not Applicable
[FR2]1
303 1.3
; U -factors of fenestration products?
Y ,„s ❑Complies
[FR411
;are determined in accordance
;with the NFRC test or,�
< ;`� i�. ry +
❑Does Not
44
procedure
(taken from the default table
u�uF1f
❑Not Observable
„< ,r❑Not
Applicable
402.4.1.1
;Air barrier and thermal barrier
1.*^ +� ?
[FR2311
installed per manufacturers
h§❑Complies
s.. ' ❑Does Not
linstructions.
❑Not Observable
❑Not Applicable
402.4.3
I Fenestration that is not site built
i °� '. "
❑Complies
[FR2011
is listed and labeled as meeting
.< �J ' ` i�'la
❑Does Not
AAMA /WDMA/CSA 101/I,S.2/A440
"",
❑Not Observable
or has infiltration rates per NFRC�-'
;400 that do not exceed code
..
❑Not Applicable
!limits.
402.4.4 ,,SIC
-rated recessed lighting fixtures
�`a+ �''x�M 'i*"if
['rf`1`
❑Complies
[FR16]1
;sealed at housing/interior finish
r�',>,` �„, I�
❑Does Not
V
and labeled to indicate <2 0 cfm
7, t
:. ❑Not Observable ;
leakage at 75 Pa.
° , w,' a phi
❑Not Applicable
403.2.1
Supply ducts in attics are
; R-_ R-
;❑Complies
[FR1211
insulated to aR-8. All other ducts
; R_ R-
;❑Does Not
in unconditioned spaces or
'1
outside the building envelope are
;
;❑Not Observable
.insulated to aR-6.
;❑Not Applicable
403.2.2
;All joints and seams of air ducts
t1 `v' +s `'r"" ` " '.
❑Complies
[FR13]1
lairhandlers, and filter boxes
;sealed.
❑Does Not
❑Not Observable
x �' , l,'
- ❑Not Applicable
403 2 3
;Building cavities are not used as-��
'ducts
; r �rS��x�,u"r
'r
❑Complies
[FR15]3
or plenums.
� -' f � a� re
❑Does Not
❑Not Observable ;
❑Not Applicable
403.3
j HVAC piping conveying fluids
1 R- ; R-
;❑Complies
1,FR17]'
I above 105 OF or chilled fluids
UDoes Not
Ibelow 55 °F are insulated to >_R-
;❑Not Observable
-;3.
;❑Not Applicable
403.3.1
[FR2411
',Protection of insulation on HVAC
)piping.
'� r
❑Complies
❑ Does Not
I
`
❑Not Observable
,
❑Not Applicable
403.4,.2
Hot water pipes are insulated to
; R- R-_
;❑Complies ;
[FRl8)2 'i
aR-3.
❑Does Not
;❑Not Observable
I❑Not Applicable
1 I High Impact (Tier 1) 12, 1 Medium Impact (Tier 2) 13!1 Low Impact (Tier 3)
Project Title: FS2B1 - Jamestown Report date: 07/20/16
Data filename: C:\Users�hoellein\Documents\REScheck\FS2Bl.rck Page 5 of 9
Section
#
Framing / Rough -in Inspection
Plans Verified
Value
Field Verified
Value
Complies? Comments/Assumptions
4015 i,;
Automatic or gravity dampers are
�1 ga,�; V'Uffl,� "U'lElcomplies
[Fft�9]2
1 installed on all outdoor air
E]Does Not
intakes and exhausts.
E]Not Observable
AWdiOpnaUCmnmmmemts/&ssmmmptioms:
111 High Impact (Tier 1) 1,2 1 Medium Impact (Tier 2) 13 1 Low impact (Tier 3)
Project Title: [3ZDl'Jamestown Report date: 07/28/l0
Data filename: [:\Usecs�hoeUein\Docunoeot$K[5check\FSZOl.rrk Page 6of 9
+SectionPlans
#.
Insulation Inspection
Verified Field Verified
Value Value
Complies? Comments/Assumptions'.
.& Req.ID
303.1
!All installed insulation is labeledi•.`
❑Complies
[IN13]2
j or the installed R -values
'`
°
❑Does Not
:I provided.
;r s '`
[-]Not Observable
❑Not Applicable
402.1.1,
:Wall insulation R -value. If this is a;
R-
Ry-_
I❑Complies ;See the Envelope Assemblies
402.2.5,
:mass wall with at least 1h of the
❑ Wood
; E]Wood❑Does
Not ;table for values.
402.2.6
wall insulation on the wall
E] Mass
El Mass❑Not
Observable
[IN3]1
, exterior, the exterior insulation
:requirement applies (FR10).
❑ Steel
I❑ Steel❑Not
Applicable
303.2
:Wall insulation is installed per
❑Complies
[IN4]1
:manufacturer's instructions
❑Does Not
,
a�
NI'M
❑Not Observable
�
ik
",yf *,�.t- - a�
t:. ❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) ' 3 +1 Low Impact (Tier 3)
Project Title: FS2Bl - Jamestown Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2B1.rck Page 7 of 9
Section
#
I Final Inspection Provisions
Plans Verified Field Verified
a Value .Value
Complies? Comments/Assumptions '..
Re .[D.
402.1.1,
;Ceiling insulation R -value.
R- R-_
;❑Complies See the envelope Assemblies
402.2.1,
Wood ; ❑ Wood
:❑Does Not table for values.
402.2.2,
Steel ❑ Steel
;❑Not Observable
402.2.6
[Fill'
❑ Not Applicable
iV
303.1.1.1,
;Ceiling insulation installed per
Fq '°'�"
I ` '' ,,tti` d;�.MElNot
❑Complies
303.2
; manufacturer's instructions
r ,�' a�
❑Does Not
[F1211
:Blown insulation marked every
3, r y ";300ft'.❑NotbbservableYr,
,,�
Applicable
402.23
[FI2212
;Vented attics with air permeable„
1 insulation include baffle adjacent
Y
. r �'b� r
❑Complies
❑Does Not
soffit and eave vents that
i
"
Ito
extends over insulation.
_'
❑Not Observable
',
❑Not Applicable
402.2.4
;Attic access hatch and door
; R-_ ; R -_❑Complies
[F1311
>_R -value of the
j❑Does Not
!adjacent
; adjacent assembly.
�.
;❑NotObservable
❑Not Applicable
402.4.1.2
Blower door test @ 50 Pa. <=5
ACH 50 =_ ACH 50 =_❑Complies
[FI1711
ach in Climate Zones 1-2, and
;❑Does Not
<=3 ach in Climate Zones 3-8.
❑Not Observable 1
❑Not Applicable
403.2.2
Duct tightness test result of <=4
I cfm/100 cfm/100❑Complies
[F1411.
cfm/100 ft2 across the system or
; ft' I ft'
I❑Does Not
U!
<=3 cfm/100 ft2 without air❑Not
Observable
:handler@ 25 Pa. For rough -in
!tests,
Applicable
verification may need to❑Not
l occur during Framing Inspection.;
f❑Complies
403.2.2.1
:Air handler leakage designated
:;`°.„ sF .� /• 4
':
[F[24]1
l by manufacturer at <=2% of
❑Does Not
l design air flow.
[]Not Observable
!
❑Not Applicable
403.1.1.
Programmable thermostats
;k'.T °�.�. �,�,.,
�'°
' ❑Com
�. p'
lies
[FI9]2
hnstalled on forced air furnaces
i "`3�
' ❑Does Not
❑Not Observable
e;=
❑Not Applicable
403.1;2
Heat pump thermostat installed
tL.;_
❑Complies
[Fllbl? '
i on heat pumps.
t
. ❑Does Not
U
( sg❑Not
Observable
❑Not Applicable
�.❑Complies
403.4:1
:! Circulating service hot water
1 _1'e,`,E
[Fill]?systems
have automatic or
, ` `vt
❑Does Not
:;accessible manual controls
't"•.
y �
- ❑Nat Observable
uAlr
❑Not Applicable
403.5.1
All mechanical ventilation system
' " : 1 1n
� a
• ❑Complies
[FI25]2
fans not part of tested and listed
#w s 1 ° s
❑Does Not
.
; HVAC equipment meet efficacy
;and airflow limits,
°r
1, "-❑Not Observable
'i
❑Not Applicable
ce,„
404.1
:75% of lamps in permanent
'",' `�,1 �''#u r�"Etd4+�r,❑Complies
[F1611
'fixtures or 75% of permanent
!fixtures
1' ,JM, ❑Does Not
V
have high efficacy lamps
§,. E :
❑Not Observable
Does not apply to low -voltage
" ' �,
",
❑Not Applicable
!lighting.
1 High Impact (Tier 1) 1 2: Medium Impact (Tier 2) 1 3'1 Low Impact (Tier 3)
Project Title: FS2B1 - Jamestown Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\F52Bl.rck Page 8 of 2
Section
# Final Inspection Provisions
Plans Verified Field Verified
',. Value
- Complies? Comments/Assumptions
&:Req.11)
,Value
, . ,
494.7,.1 !Fuel gas lighting systems have
�,w❑Does
";gi,��
'';, ,"NEINot
[]Complies
1Fi231s !no continuous pilot light.
4 ��.l,i,tjry�, Er
Not
',n'Ite,y❑Not
Observable�
Applicable
.�Compliance certificate posted
?
❑Complies
[0I)2
❑Does Not
�J
0105
❑Not Observable
5..:' Sf^7,.r
❑Not Applicable
3033 I Manufacturer manuals for❑Complies
[FI1813. +mechanical and water heating
�hra
❑Does Not
,g r�'a;
`v
`systems have been provided
,r;`�¢'`�t , t
?'
[]Not Observable
❑Nob Applicable
Additional Comments/Assumptions:
1 IHigh Impact (Tier 1) 12 1 Medium Impact (Tier 2) 1,3JLow Impact (Tier 3)
Project Title: FS2B1-Jamestown Report date: 07/20/16
Data filename: C:\Users\jhoellein\Documents\REScheck\FS2Bl.rck Page 9 of 9
2012 IECC Energy
Efficiency Certificate
Above -Grade Wall
21.00
Below -Grade Wall
13.00
Floor
0.00
Ceiling / Roof
50.00
Ductwork (unconditioned spaces):
Window 0.32
Door 0.01
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments