Residential Electrical Service Inspection on 03/09/2017: PASS
Permit Number: 17-00095Permit Details
Electrical Only Residential
Permit Issued Date: 03/07/2017
Final Inspections Required
112 N 1st E
112 N 1st E - Service Upgrade
Inspection Details
bret.stoddard@rexburg.org
Inspected By: Bret Stoddard
Residential Electrical Service Inspection on 03/09/2017: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Overhead service conductors have proper
clearances. 230.24(A)&(B)
Overhead conductors at about 14'.COMPLETED
Service disconnects and overcurrent devices
are located outside or inside nearest the point of
entrance of the service conductors. 230.70(A)
(1), 230.91
COMPLETED
Service disconnects are grouped together,
with no more than six in any one location.
230.71, 230.72, 408.36(B) Exc.
COMPLETED
The point of attachment is adequate and will
provide required support and clearances above
roofs
and grade. 230.24, 230.26, 230.54(C)
COMPLETED
Panelboards are grounded by an appropriate
and properly sized equipment grounding
conductor (or
conductors). 408.40, 215.6, 250.118, 250.122
COMPLETED
Unused openings have been effectively closed
(K.O. seals, etc.) 110.12(A), 408.7
COMPLETED
Securely mounted gear-panels, meter base, etc.
110.13
COMPLETED
Temperature ratings of equipment-lugs,
breakers, splices, etc. 110.14(A), (B), (C)
COMPLETED
Proper clearances about electrical equipment
indoors and outdoors. 110.26 (A), (E),(E)(2) and
(F)
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc. 250.52(A)
(4-7)
Two ground rods installed.COMPLETED
Grounding electrode system conductors sized
and protected appropriately. 250.66, 250.64(F),
250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved methods.
250.64(C)(F)
COMPLETED
Page 1 of 2
(Continued)
Permit Number: 17-00095
D ESCRIPTIO N CO MMEN TS STATUS
Grounding electrode connection(s) are accessible
if not irreversible. 250.68(A)
COMPLETED
Any associated wiring with service meets article
300 wiring methods.
COMPLETED
Identify wet and damp locations for
panels-NEMA 3R, etc. 408.16, 408.37, 312.12
COMPLETED
Proper wiring bending space in panel &
associated enclosures, gutters, etc. 408.3(G),
312.6, 408.55(A)(B)&(C)
COMPLETED
Panel or switchgear service rated. 408.3(C)COMPLETED
Approved to be energized for permanent power
(will send permit to utility).
To be re-energized for permanent power.COMPLETED
Page 2 of 2
Transaction detail for payment to City of Rexburg. Date: 03/07/2017 - 11:58:09 AM
Billing Information
Leishman Electric Leishman
Electric
, 83440
leishmanelectric@yahoo.com
City of Rexburg
35 N 1st East | PO Box 280
Rexburg, ID 83440
208-359-3020
ub@rexburg.org
XBP Confirmation Number: 27432590
Transaction Number: 65112314PT
Visa — XXXX-XXXX-XXXX-6337
Status: Successful
Account # Item Quantity Item Amount
Electrical Permit 1 $65.00
Notes: Permit # 17-00095
TOTAL:$65.00
Transaction taken by: coltonm
Xpress Bill Pay - Payment Processing https://secure.xpressbillpay.com/common/payment_process.php
1 of 1 3/7/2017 11:58 AM