HomeMy WebLinkAboutALL DOCS - 17-00056 - 412 Violet - New Pedestal ServiceInspection
Ticket
Residential Electrical Service Inspection on 02/14/2017: PASS
Permit Number: 17-00056Permit Details
Electrical Only Residential
Permit Issued Date: 02/13/2017
Final Inspections Required
412 Violet
412 Violet - New Pedestal Service
Inspection Details
bret.stoddard@rexburg.org
Inspected By: Bret Stoddard
Residential Electrical Service Inspection on 02/14/2017: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Underground fed services have proper strapping
and expansion fittings. 352.30(A)(B), 352.44
COMPLETED
Service disconnects and overcurrent devices
are located outside or inside nearest the point of
entrance of the service conductors. 230.70(A)
(1), 230.91
COMPLETED
The point of attachment is adequate and will
provide required support and clearances above
roofs
and grade. 230.24, 230.26, 230.54(C)
COMPLETED
Panelboards are grounded by an appropriate
and properly sized equipment grounding
conductor (or
conductors). 408.40, 215.6, 250.118, 250.122
COMPLETED
Unused openings have been effectively closed
(K.O. seals, etc.) 110.12(A), 408.7
COMPLETED
Securely mounted gear-panels, meter base, etc.
110.13
COMPLETED
Temperature ratings of equipment-lugs,
breakers, splices, etc. 110.14(A), (B), (C)
COMPLETED
Proper clearances about electrical equipment
indoors and outdoors. 110.26 (A), (E),(E)(2) and
(F)
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc. 250.52(A)
(4-7)
Two ground rods installed.COMPLETED
Grounding electrode system conductors sized
and protected appropriately. 250.66, 250.64(F),
250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved methods.
250.64(C)(F)
COMPLETED
Grounding electrode connection(s) are accessible
if not irreversible. 250.68(A)
COMPLETED
Page 1 of 2
(Continued)
Permit Number: 17-00056
D ESCRIPTIO N CO MMEN TS STATUS
Any associated wiring with service meets article
300 wiring methods.
50A receptacle installed for mobile home cord
to plug into.
COMPLETED
Identify wet and damp locations for
panels-NEMA 3R, etc. 408.16, 408.37, 312.12
COMPLETED
Panel or switchgear service rated. 408.3(C)COMPLETED
Main bonding jumper sized to 250.28(D), and all
panels bonded together using an equipment
bonding conductor sized in accordance with
250.122 or 250.66 as appropriate.
COMPLETED
Service conductors are adequate size and rating.
230.23, 230.31, 230.42
COMPLETED
Approved to be energized for permanent power
(will send permit to utility).
To remain energized for permanent power.
Service was energized over the weekend due to
a failure in the meter base.
COMPLETED
Page 2 of 2
Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 03/01/2017 2:18 pm
Permit Details Permit Number: 17-00056
412 Violet - New Pedestal Service
412 Violet
Electrical Only Residential
Permit Issued Date: 02/13/2017
Permit Inspection Statistics
1Total Inspections Completed:
1Total Inspections Passed:
Inspection Pass Rate
100.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Electrical Inspection Type
02/14/2017PassBret StoddardResidential Electrical Service Inspection