Loading...
HomeMy WebLinkAboutINSPECTION SUMMARY - 16-00602 - 121 E main - ConsultationPermit Inspection Summary Permit Status of (Open) as of Report Date: 01/30/2017 3:14 pm Permit Details Permit Number: 16-00602 121 E main - Consultation 121 E Main Consultation case Permit Issued Date: Permit Inspection Statistics Total Inspections Completed: Total Inspections Passed: Inspection Pass Rate Permit Inspection History *Refer to Individual Inspection Report for more Details Building Inspection Type 2 exits meeting certain criteria are required for spaces with more than 49 occupants. A design professional is required to verify existing structural integrity for added loads and new structural design of added level. Extending building over a property line is not allowed unless a legal agreement is in place that ties the two properties together (see Planning & Zoning for available options). Inspector Comments: 09/06/2016COMPLETEDQuinton OwensBuilding Inspector Consultation Option for separating existing single apartment into two: One hour fire rated separation is required between the units and common area and to other occupancies (including rated doors). Smoke alarms required in bedrooms and just outside bedrooms (CO detectors outside bedrooms if gas appliances are in the building). Further details of floor plan to be reviewed prior to obtaining a permit. Inspector Comments: