Building Inspection Type
2 exits meeting certain criteria are required for spaces with more than 49
occupants. A design professional is required to verify existing structural integrity
for added loads and new structural design of added level.
Extending building over a property line is not allowed unless a legal agreement is
in place that ties the two properties together (see Planning & Zoning for available
options).
Inspector Comments:
09/06/2016COMPLETEDQuinton OwensBuilding Inspector Consultation
Option for separating existing single apartment into two:
One hour fire rated separation is required between the units and common area
and to other occupancies (including rated doors). Smoke alarms required in
bedrooms and just outside bedrooms (CO detectors outside bedrooms if gas
appliances are in the building).
Further details of floor plan to be reviewed prior to obtaining a permit.
Inspector Comments: