COM & MFR Electrical Service Inspection on 09/19/2016: PASS
Permit Number: 16-00622Permit Details
Electrical Only Commercial
Permit Issued Date: 09/16/2016
Final Inspections Required
330 S 1st W
330 S 1st W - Power Supply Cable One Ele Only
Inspection Details
bret.stoddard@rexburg.org
Inspected By: Bret Stoddard
COM & MFR Electrical Service Inspection on 09/19/2016: PASS
D ESCRIPTIO N CO MMEN TS STATUS
AIC ratings are adequate for the conditions of
installations. 110.9
COMPLETED
Securely mounted gear-panels, meter base, etc.
110.13
COMPLETED
Check temperature ratings of equipment-lugs,
breakers, splices, etc. 110.14(A), (B), (C)
COMPLETED
Proper clearances about electrical equipment
indoors and outdoors. 110.26 (A), (E),(E)(2) and
(F)
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc. 250.52(A)
(4-7)
COMPLETED
Grounding electrode system conductors sized
and protected appropriately. 250.66, 250.64(F),
250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved methods.
250.64(C)(F)
COMPLETED
Grounding electrode connection(s) are accessible
if not irreversible. 250.68(A)
COMPLETED
Any associated wiring with service meets article
300 wiring methods.
COMPLETED
Identify wet and damp locations for
panels-NEMA 3R, etc. 408.16, 408.37, 312.12
COMPLETED
Proper wiring bending space in panel &
associated enclosures, gutters, etc. 408.3(G),
312.6, 408.55(A)(B)&(C)
COMPLETED
Panel or switchgear service rated. 408.3(C)COMPLETED
Service conductors are adequate size and rating.
230.23, 230.31, 230.42
COMPLETED
Approved to be energized for permanent power
(will send permit to utility).
To be energized for permanet power-pedestal
only. #2 AL conductors are going to be pulled
to the pedestal to keep the AIC under 10K as
per RMP.
COMPLETED
Page 1 of 2
Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 01/30/2017 1:01 pm
Permit Details Permit Number: 16-00622
330 S 1st W - Power Supply Cable One Ele Only
330 S 1st W
Electrical Only Commercial
Permit Issued Date: 09/16/2016
Permit Inspection Statistics
1Total Inspections Completed:
1Total Inspections Passed:
Inspection Pass Rate
100.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Electrical Inspection Type
09/19/2016PassBret StoddardCOM & MFR Electrical Service Inspection
Transaction detail for payment to City of Rexburg. Date: 09/15/2016 - 2:50:15 PM
Billing Information
Blane Robbins Electric, Inc. Blane
Robbins Electric, Inc.
, 83221
sbsrobbins@aol.com
City of Rexburg
35 N 1st East | PO Box 280
Rexburg, ID 83440
208-359-3020
ub@rexburg.org
XBP Confirmation Number: 21631206
Transaction Number: 57084313PT
Visa — XXXX-XXXX-XXXX-1077
Status: Successful
Account # Item Quantity Item Amount
16-00622 Electrical Permit 1 $84.00
TOTAL:$84.00
Transaction taken by: markd
Xpress Bill Pay - Payment Processing https://secure.xpressbillpay.com/common/payment_process.php
1 of 1 9/15/2016 2:52 PM