HomeMy WebLinkAboutALL DOCS - 16-00622 - 330 S 1st W - Power Supply Cable One Ele OnlyInspection Ticket COM & MFR Electrical Service Inspection on 09/19/2016: PASS Permit Number: 16-00622Permit Details Electrical Only Commercial Permit Issued Date: 09/16/2016 Final Inspections Required 330 S 1st W 330 S 1st W - Power Supply Cable One Ele Only Inspection Details bret.stoddard@rexburg.org Inspected By: Bret Stoddard COM & MFR Electrical Service Inspection on 09/19/2016: PASS D ESCRIPTIO N CO MMEN TS STATUS AIC ratings are adequate for the conditions of installations. 110.9 COMPLETED Securely mounted gear-panels, meter base, etc. 110.13 COMPLETED Check temperature ratings of equipment-lugs, breakers, splices, etc. 110.14(A), (B), (C) COMPLETED Proper clearances about electrical equipment indoors and outdoors. 110.26 (A), (E),(E)(2) and (F) COMPLETED Grounding electrode system installed-ufer, ground rods, metal water piping, etc. 250.52(A) (4-7) COMPLETED Grounding electrode system conductors sized and protected appropriately. 250.66, 250.64(F), 250.64(A)(B) COMPLETED Grounding electrode conductor is either un-spliced or spliced using approved methods. 250.64(C)(F) COMPLETED Grounding electrode connection(s) are accessible if not irreversible. 250.68(A) COMPLETED Any associated wiring with service meets article 300 wiring methods. COMPLETED Identify wet and damp locations for panels-NEMA 3R, etc. 408.16, 408.37, 312.12 COMPLETED Proper wiring bending space in panel & associated enclosures, gutters, etc. 408.3(G), 312.6, 408.55(A)(B)&(C) COMPLETED Panel or switchgear service rated. 408.3(C)COMPLETED Service conductors are adequate size and rating. 230.23, 230.31, 230.42 COMPLETED Approved to be energized for permanent power (will send permit to utility). To be energized for permanet power-pedestal only. #2 AL conductors are going to be pulled to the pedestal to keep the AIC under 10K as per RMP. COMPLETED Page 1 of 2 Permit Inspection Summary Permit Status of (Open) as of Report Date: 01/30/2017 1:01 pm Permit Details Permit Number: 16-00622 330 S 1st W - Power Supply Cable One Ele Only 330 S 1st W Electrical Only Commercial Permit Issued Date: 09/16/2016 Permit Inspection Statistics 1Total Inspections Completed: 1Total Inspections Passed: Inspection Pass Rate 100.00% Permit Inspection History *Refer to Individual Inspection Report for more Details Electrical Inspection Type 09/19/2016PassBret StoddardCOM & MFR Electrical Service Inspection Transaction detail for payment to City of Rexburg. Date: 09/15/2016 - 2:50:15 PM Billing Information Blane Robbins Electric, Inc. Blane Robbins Electric, Inc. , 83221 sbsrobbins@aol.com City of Rexburg 35 N 1st East | PO Box 280 Rexburg, ID 83440 208-359-3020 ub@rexburg.org XBP Confirmation Number: 21631206 Transaction Number: 57084313PT Visa — XXXX-XXXX-XXXX-1077 Status: Successful Account # Item Quantity Item Amount 16-00622 Electrical Permit 1 $84.00 TOTAL:$84.00 Transaction taken by: markd Xpress Bill Pay - Payment Processing https://secure.xpressbillpay.com/common/payment_process.php 1 of 1 9/15/2016 2:52 PM